Follow general and special fire safety regulations in force in all fields of applications. In
any case ensure the following minimum safety clearances from materials or objects in
the surroundings of the heater:
Floors and ceilings must be made of fireproof materials in the place where the heater is
operated.
Do not connect direct-fired heaters to air ducts.

6. Instructions for Use

6.1. Start-up
Fill tank with clean fuel. Only use Diesel or Kerosene.
The fuel gauge on top of the tank allows to check fuel level
Connect the power cord plug to a 230 V 50 Hz earthed electrical supply system.
Earthing is mandatory.
Models CT2142:
When complete "start-up" above, the power indicator will light, the display window will show the
ambient temperature value.
Push the power switch to "on" position.
If the thermostat control knob setting temperature is higher than the ambient temperature, the
electrodes start sparking and after 7 seconds, the heater starts.
If the thermostat control knob setting temperature is lower than the ambient, turn thermostat control
knob to desired temperature setting, the electrodes start sparking and after 7 seconds, the heater
starts.
Model BGO1601-50
When complete "start-up" above, the left display window shows "--", the right display window shows
ambient temperature value.
Push the power switch to "on" position.
The default temperature setting is 20 , be showed on the left display window.
If the ambient temperature is lower than default temperature, the electrodes start sparking, after 7
seconds, the heater starts.
If the ambient temperature is higher than default temperature, turn thermostat control knob to desired
temperature, the electrodes start sparking, after 7 seconds, the heater starts.
COLD START-UP: at low temperature keep the air vent hole (see Fig. 6) closed by a finger during
ignition to make start-up easier.
ABNORMAL OPERATION: in case of malfunction (flame failure, reduced air flow, bad combustion,
etc.) the heater stops and the indicator light starts FLASHING (THE LOCK-OUT MODE code will be
showed on the display window).
6.2. Manual reset/restart
If the heater is in lock-out mode, check and remove the cause of lock-out before restarting the heater.
To reset, turn the ON/OFF switch to 0 and then again to I. In case of repeated malfunction, call
technical service. Turning the thermostat control knob will NOT reset the heater.
Side:
Air inlet side:
Top:
Hot air outlet side:
Floor:
0.6 m
1 m
1.5 m
3 m
0 m