Initial Desuperheater Start Up - WaterFurnace AT022C/D Installation And Maintenance Manual

Geothermal system single-speed
Table of Contents

Advertisement

Initial
Desuperheater
Start Up
10
PREMIER 2 SINGLE-SPEED INSTALLATION AND MAINTENANCE MANUAL
Figure 12 - Typical Desuperheater Installation
Long
Elbow
Figure 13 - Desuperheater Installation In Preheat Tank
Do not connect electrical to pre-heat tank.
Waste Valve
Long Elbow
WATER TANK REFILL
Steps:
1)
Close the drain valve to the water heater.
2)
Open the cold water supply to the tank.
3)
Open the hot water faucet in the house to bleed air from the system. Then close when full.
4)
Depress the handle on the pressure relief valve to bleed any remaining air from the tank
then close.
5)
If so equipped, unscrew the indicator plug on the motor end of the pump (located in the
Premier 2 unit) until all air is purged from the pump, then tighten the plug. Use vent cou-
plings to bleed air from the lines.
6)
Carefully inspect all plumbing for water leaks and correct as required.
7)
Before restoring electrical supply to the water heater, adjust the temperature setting on the
tank.
• On tanks with both upper and lower elements, the lower element should be turned down to
the lowest setting, approximately 100°F. The upper element should be adjusted to 120°F to
130°F. Depending upon the specific needs of the customer, you may want to adjust the
upper element differently.
• On tanks with a single element, lower the thermostat setting to 120°F.
8)
After thermostat(s) is adjusted, replace the access cover and restore electrical supply to the
water heater.
Hot
Cold
Venting
Waste Valve
P/T Relief
or Vent
Valve
Coupling
Out
In
Coaxial
Drain Valve
Drain Tee
Cold
Venting
or Vent
P/T Relief
Coupling
Valve
Out
In
Coaxial Drain
Tee
Drain Valve
Hot
P/T Relief
Valve
Drain Valve