9.3.2 Manual transport

For the manual transport, the wooden pallet can be used. Using ropes or carrying straps, a second or third handling configuration
is possible. With this type of handling, it is advised that the maximum permissible inclination angle of 45 degree is not exceeded.
If transport in an inclined position cannot be avoided, the unit should be taken into operation one hour after it has been moved
into final position.
ATTENTION: due to the high center of gravity, low overturning moment, the unit must be secured against tipping
over.
ATTENTION: the cover of the unit cannot withstand stress, so it cannot be used for transport.
ATTENTION: the unit can be inclined only on the opposite side of the handle (see above drawing), in other words
only on the left side respect of the control panel.
The unit is equipped with a handle to make easy the transport. The handle is supplied unassembled: in case of need, it shall be
fixed with two M8 screws to the two threaded inserts.

9.4 REQUIRED SERVICE SPACE

Below you will find the minimum space required to be able to complete service and maintenance tasks on the units.
Moreover, re-circulation of discharge air has to be avoided; failure to observe this point will result in poor performance or
activation of safety controls. For these reasons it is necessary to observe the following clearances.