Page 3
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans Monoblock Unit HP Inverter UM 06-08-12-16 UM Plus 06-08-12-16 08-2015 A.B. Date Author Supervisor Notes Possible wasted electrical or electronic devices/products should not be located together with normal domestic waste, but disposed according to the current WEEE law in compliance with the European Directive 2012/19/UE.
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans INDEX AIM AND CONTENTS OF THE MANUAL ....................... 5 HOW TO KEEP THIS MANUAL ..........................5 GRAPHIC SYMBOLS ..............................5 SAFETY LAWS ..............................5 PERMITTED USES ..............................5 GENERAL SAFETY GUIDELINES ..........................
Page 5
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans HEAT PUMPS AVAILABLE HEAD PRESSURE ....................20 14.1 MODELS UM / UM P ............................20 WATER PUMP CURVES ..........................21 15.1 MODELS UM / UM P 06-08 ..........................
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans The manual of UM / UM Plus units contains all the necessary information for the better use of the equipment under safety conditions for the operator thus meeting the requirements listed in the 2006/42/CE Equipment Directive and following amendments.
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans 4 GENERAL SAFETY GUIDELINES Before beginning to operate on UM / UM Plus units every user has to be perfectly knowledgeable about the functions of the equipment and its controls and has to have read and understood the information listed in this manual.
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans 4.4 REFRIGERANT SAFETY DATA SHEET Name: R410A (50% Difluoromethane (R32); 50% Pentafluoroethane (R125). RISKS INDICATIONS Major risks: Asphyxia Specific risks: The rapid evaporation may cause freezing. FIRST AID General information: Never give anything by mouth to an unconscious person.
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans 5 TECHNICAL CHARACTERISTICS The UM / UM Plus water chillers and heat pumps series are designed for applications in residential and commercial areas, These units are extremely versatile and can operate in heat pump mode with the ability of producing hot water at a temperature of 58°C for environmental heating and sanitary applications.
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans 7 INSTALLATION WARNING: All the operation described in next chapters MUST BE DONE BY TRAINED PEOPLE ONLY. Before any operation on the unit, be sure that the electric supply is disconnected. 7.1 GENERALITY When installing or servicing the unit, it is necessary to strictly follow the rules listed in this manual, to conform to all the specifications of the labels on the unit, and to take any possible precautions.
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans Models UM / UM Plus 06 1500 UM / UM Plus 08 1500 UM / UM Plus 12 1500 UM / UM Plus 16 1500 * The recommended minimum distance for installation and maintenance.
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans During the operations of charging/topping up, the plugs of the air vent valves must be partially unscrewed to allow air to flow freely out of the valves. (1) Plug of the air vent valve You can use the service valve, when it is necessary to refill the plant or adapt the concentration of glycol.
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans 7.5 REFRIGERANT DIAGRAM OF UM/UM Plus 06-08 COMPRESSOR COMPRESSOR LIQUID SEPARATOR COMPRESSOR INLET TEMPERATURE COMPRESSOR OUTLET TEMPERATURE HIGH PRESSURE TRANSDUCER HIGH PRESSURE FLOW SWITCH LOW PRESSURE TRANSDUCER LIQUID SEPARATOR (only for model 09) VALVE FO INVERTING CYCLE LIQUID RECEIVER...
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans 7.7.1 Wiring terminal block Electrical wiring have to be done only by qualified personnel. The electrical connections have to be realized by qualified personnel. The terminal block is located under the plastic cover on the side of the hydraulic connections (for the models 12 and 16, it is necessary to remove the protective carter).
Page 16
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans Analogue (ST9)/digital (DI8) input Sanitary water boiler sensor terminal DO5N Digital output (DO5) 230 Vac Neutral output (for other configuration) Digital output (DO5) 230 Vac Phase output (for other configuration) Neutral output (230V, 50Hz, 5A resistive, 1 A inductive) (optional to be DO4N...
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans 7.7.2 Removal of protective carter for models 12 and 16 The following shows the procedure for removing the protective carter so you can access the terminal block in models 12 and 16. 1)Remove the indicated screws 2) Push down the right side panel 3) Turn the right side panel in the...
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans 9 SHUTDOWNS FOR LONG PERIODS The types of shutdown depends on the weather of the site where the unit is installed and on the period of the stop. The antifreeze system, if it’s installed, stay on work also with the on-board control unit in “OFF”...
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans 10.1 ENVIRONMENTAL PROTECTION According to the norms dealing with the use of depleting stratospheric ozone substances, it is forbidden to release refrigerants fluids in the atmosphere. They have to be collected and delivered to the seller or to proper gathering points at the end of their operating life.
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans 12 TECHNICAL DATA UM / UM Plus Model TECHNICAL CHARACTERISTICS Unit Power supply V/Ph/Hz 230V/1/50Hz 230V/1/50Hz 230V/1/50Hz 400V/3P+N+T/50Hz Total power input 2,76 4,55 5,67 7,85 Electric data Maximum starting current 12,9...
(3) p. 19. The circuit’s plant must be designed so as to ensure the nominal water flow rate corresponding to the operating points indicated below. 14.1 MODELS UM / UM Plus UM 06 UM 08 UM 12 UM 16...
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans 15 WATER PUMP CURVES 15.1 MODELS UM / UM Plus 06-08 [kPa] 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 Q [m³/h] Q [l/s] Q [m³/h]...
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans 16 PERFORMANCE 16.1 MOD. UM / UM Plus 06 air 45 ° C air 40 ° C air 35 ° C air 30 ° C air 25 °...
Page 25
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans air 12 °C air 7 °C air 2 °C air -2 °C air -7 °C air -10 °C air -15 °C Heating Capacity [kW] air 12 °C air 7 °C air 2 °C air -2 °C...
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans 16.2 MOD. UM / UM Plus 08 air 45 °C air 40 °C air 35 °C air 30 °C air 25 °C air 20 °C Cooling Capacity [kW] air 45 °C air 40 °C...
Page 27
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans air 12 °C air 7 °C air 2 °C air -2 °C air -7 °C air -10 °C air -15 °C 10,0 Heating Capacity [kW] air 12 °C air 7 °C air 2 °C...
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans 16.3 MOD. UM / UM Plus 12 air 45 °C air 40 °C air 35 °C air 30 °C air 25 °C air 20 °C 10,5 11,5 12,5...
Page 29
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans air 12 °C air 7 °C air 2 °C air -2 °C air -7 °C air -10 °C air -15 °C Heating Capacity [kW] air 12 °C air 7 °C air 2 °C air -2 °C...
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans 16.4 MOD. UM / UM Plus 16 air 45 °C air 40 °C air 35 °C air 30 °C air 25 °C air 20 °C 10,0 10,5 11,0 11,5 12,0 12,5 13,0 13,5 14,0 Cooling Capacity [kW] air 45 °C...
Page 31
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans air 12 °C air 7 °C air 2 °C air -2 °C air -7 °C air -10 °C air -15 °C Heating Capacity [kW] air 12 °C air 7 °C air 2 °C air -2 °C...
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans 17 OPERATING LIMITS 17.1 EVAPORATOR WATER FLOW RATE The nominal water flow rate is referred to a ∆T equal to 5°C, between the evaporator’s inlet and outlet temperatures. The allowed maximum flow rate is corresponding to ∆T=3°C;...
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans WATER CHILLER/HEAT PUMP MODE SANITARY HOT WATER MODE 18 CORRECTION FACTORS FOR USE OF GLYCOL Glycol rate Freezing point (°C) IPCF WFCF PDCF -3,2 0,985 1,02 1,08 -7,8...
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans 19 DIMENSIONS 19.1 MODELS UM / UM Plus 06 IN/OUT: 1”M 19.2 MODELS UM / UM Plus 08 IN/OUT: 1”M...
UM / UM PLUS Chillers and inverter air / water heat pumps with axial fans 21 REMOTE CONTROL (OPTIONAL ACCESSORY) The Remote Control allows you to set the operating mode of the chiller and fan coils units connected to a RS485 network. The network can consist of up to 5 chillers in cascade and fan coils up to 70 units in 9 heating zones.
Need help?
Do you have a question about the UM 06 and is the answer not in the manual?
Questions and answers