Preset Single Register - Function Code 06; Preset Single Register Query; Preset Single Register Response; Loopback Test - Function Code 08 - ABB C1900 Installation Manual

Circular chart recorder and recorder/controller, modbus (rtu) communications option
Hide thumbs Also See for C1900:
Table of Contents

Advertisement

5.4
Preset Single Register – Function Code 06
5.4.1

Preset Single Register Query

The preset single register allows the user to modify the contents of a holding register.
Note. Function codes 5, 6 and 16 are the only messages that are recognized as valid for broadcast.
Example – a preset single register request to write the value 500 to holding register address 121 (alarm trip A1) in slave 01 is
shown below.
Note. To write to a register, the register's offset address must be used, e.g. to write to register 121, the offset address
120(78H) is transmitted.
Address
Function
01
06

5.4.2 Preset Single Register Response

The normal response to a preset single register request is to retransmit the query message after the register has been altered.
:
Example
Address
Function
01
06
5.5
Loopback Test – Function Code 08
5.5.1

Loopback Test Query

The purpose of the loopback test is to test the Modbus system, it does not affect the content of the controller. Variations in the
response may indicate faults in the Modbus system. The information field contains 2 bytes for the designation of the diagnostic
code followed by 2 bytes to designate the action to be taken.
:
Example
Data Diagnostic
Address
Function
01
08
*These are considered to be the information fields for diagnostic mode.
5.5.2

Loopback Test Response

The response always echoes the query, only diagnostic code 0 (bytes 3 and 4) can be used.
:
Example
Data Diagnostic
Address
Function
01
08
Register
Register
Offset High
Offset Low
00
78
Register
Register
Offset High
Offset Low
00
78
Data Diagnostic
Code High
Code Low
00
00
Data Diagnostic
Code High
Code Low
00
00
Data Value High
Data Value Low
01
Data Value High
Data Value Low
01
F4
Data*
Data *
A5
Data
A5
5 MODBUS FUNCTIONS...
Error Check Field (CRC-16)
F4
09
Error Check Field (CRC-16)
09
Error Check Field (CRC-16)
37
DA
Data
Error Check Field (CRC-16)
37
DA
C4
C4
8D
8D
11