6
Requirement on local AHU design
6.3 Requirement on DX (Direct expansion) coil
(1) Heat exchanger volume of DX coil
Make sure to keep the DX coil capacity within the following range.
If the piping length is 30m or shorter, DX coil capacity can be increased as follows.
Model capacity of outdoor unit
Max. volume [cm
3
]
Pipe length
Min. volume [cm
3
]
Note: Calculate them by linear interpolation in case of other piping lengths not shown on this table.
(2) Structure of DX coil
When multiple outdoor units are connected, basically select one interlaced DX coil which has multiple refrigerant circuit, or multiple coil placed in parallel to the
air flow. If multiple coils are placed in series with the air flow, maximum 2 coils in series are acceptable. (See figure 6-1.)
Interlaced
Air flow
OK
(3) Diameter of header
With a bigger size header, the refrigerant flow velocity decreases and this disturbs the sufficient circulation of refrigerant oil. As a result, the refrigerant oil
does not flow properly and could cause a serious damage of compressor.
Use the pipe whose outside diameter is less than the value shown in the table below.
Model capacity of outdoor unit
Max. diameter of header [mm]
Model capacity of outdoor unit
Max. diameter of header [mm]
(4) Withstanding pressure
Design pressure of outdoor unit is 4.15 MPa. Following must be satisfied for burst pressure of connecting application.
Burst pressure : More than 12.45 MPa (3 times more than design pressure)
(5) Contamination maintenance
1. Wash the inside of heat exchanger to keep it clean. Be sure to rinse not to leave flux. Do not use chlorine detergent when washing.
2. Be sure that the amount of contamination per unit cubic content of heat transfer pipe is less than the following amount.
Example) In case of ø9.52mm
Residual water : 0.6 mg/m, Residual oil : 0.5 mg/m, Solid foreign object : 1.8 mg/m
6.4 Additional refrigerant charging amount
Regarding additional refrigerant charging amount of PUZ-ZM100, 125, 140 models, follow the table below.
For other models, see the installation manual of each outdoor unit.
Permitted pipe
Model
length
ZM100 - 140
- 85m
14
ZRP
35
50
P
SHW
ZM
35
50
30m -
1050
1500
20m
1350
1800
10m
1650
2100
350
500
Parallel
Air flow
HP 1 HP 2
OK
<Fig. 6-1: Example of DX coil structure>
ZRP
35
50
P
SHW
ZM
35
50
Permitted vertical
difference
31 - 40m
- 30m
0.5kg
60
71
100
80
112
60
71
100
1800
2130
3000
2700
3030
3900
3600
3930
4800
600
710
1000
2 in series
Air flow
HP 1 2
HP 1 HP 2
60
71
100
80
112
{19
60
71
100
{14
Additional refrigerant charging amount
41 - 50m
51 - 60m
61 - 70m
1.0kg
1.5kg
2.0kg
125
140
200
200
140
230
125
140
3750
4200
6000
4650
5100
7800
5550
6000
9600
1250
1400
2000
3 in series
Air flow
3 4
HP 1
OK
NOT OK
125
140
200
200
140
230
{28
125
140
{21
◎ Maximum
amount of
71 - 85m
refrigerant
2.8kg
6.8kg
250
250
7500
9300
11100
2500
2
3
250
250

Hide quick links:

Advertisement

loading

This manual is also suitable for: