Fixing facility
22
Keep in mind that measurement is not possible below the fastening
point.
1
2
Fig. 12: Fasten the probe
1
Measuring probe
2
Retaining sleeve
If there is a risk of the cable probe touching the vessel wall during
operation due to product movements or agitators, etc., the measuring
probe can be strained.
For this purpose there is an internal thread (M12 or M8) in the gravity
weight.
Make sure that the probe cable is only hand tight. Avoid strong tensile
loads on the cable.
Keep in mind that measurement is only possible up to the tensioning
component. For this reason, order the cable probe 270 mm longer.
L = L1 + 270 mm (10.63 in)