Insulating The Refrigerant Piping - LG Multi V Water IV Installation Manual

Variable refrigerant flow water source units 6.0 to 48.0 tons
Hide thumbs Also See for Multi V Water IV:
Table of Contents

Advertisement

Always properly insulate the piping. Insufficient insulation will result in condensation, reduced heating/cooling performance, etc. Also, if the
pipes aren't insulated properly, condensation could potentially cause damage to building finishes. Pay special attention to insulating the
pipes installed in the ceiling plenum.
Follow locals codes and the designer's instructions when selecting EPDM insulation wall thickness.
Table 59: Minimum Refrigerant Pipe EPDM Insulation Wall Thickness Requirements.
Piping
Classification
(in. OD)
1/4
3/8
Liquid pipe
≥1/2
3/8
1/2
5/8
3/4
7/8
1
Vapor pipe
1-1/8
1-1/4
1-3/8
1-1/2
1-3/4
The thickness of the above insulation material is based on heat conductivity of 0.61 Btu/in/h/ft
1
1. Typical Conditioned Location
A building plenum or space that contains conditioned air that does not exceed 80°F DB.
2. Special Conditioned Location
1. When the location is air conditioned, but there is severe temperature/humidity difference due to high ceilings
• Church, auditorium, theater, lobby, etc.
2. When the location is air conditioned, but internal temperature/humidity are high
• Bathroom, swimming pool, locker room, etc.
3. Typical Unconditioned Location
An unconditioned space inside a building.
4. Special Unconditioned Location: If conditions 1 and 2 below are present.
1. An unconditioned space or plenum of a building.
2. An area where there is an elevated humidity level.
5. Additional Insulation for Indoor Units May be Required in Humid Environments.
The air conditioner factory insulation has been tested according to "ISO Conditions with Mist," and it satisfies the requirements. If the system
has been operating for a long time in a high humidity environment (dew point temperature: more than 73°F), condensate is likely to form. If
this happens, install 3/8 inch thick ethylene propylene diene methylene (EPDM) insulation that is plenum-rated with a heat-resistance factor
of more than 158°F.
REFRIGERANT PIPING INSTALLATION
Air-Conditioned Location
1. Typical Conditioned
2. Special Conditioned
Location
>1/2 inches
>1/2 inches
>1/2 inches
>3/4 inches
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.

Insulating the Refrigerant Piping

1
3. Typical Unconditioned
Location
Location
>1/2 inches
>1/2 inches
>1/2 inches
>1/2 inches
>3/4 inches
>3/4 inches
>1 inch
>1 inch
/°F.
2
Non-Air Conditioned Location
4. Special Unconditioned
Location
>1/2 inches
>1/2 inches
>1 inch
71