ABB Advant Controller 450 User Manual page 555

Advant ocs with master software
Hide thumbs Also See for Advant Controller 450:
Table of Contents

Advertisement

13:25:10 134
11
1
Type Code
Significance
134
20
AC 410/AC450, 24 V error
21
AC 410/AC450,
regulator error
22
AC 410/450,
battery error
23
AC 410/450,
backup power supply error
24
AC 410/450,
fan error
25
AC 450,
I/O 24 V error
3BSE 002 415R701 Rev A
Section I.3 List of System Messages and Corrective Actions
Type 134 System/Node Supervision
20
Table I-16. Type 134, Code
Data 1
Concept,
MSW: Direction
instance No.
LSW: Channel
MSW: Direction
LSW: Regulator
MSW: Direction
LSW: Battery
MSW: Direction
LSW: Backup
power supply
MSW: Direction
LSW: Not used
MSW: Direction
LSW: Channel
®
Advant
H'
H'
Data 2
Comments/Actions
H'EEEE ⇒ Error coming
H'2222 ⇒ Equip. in working order
1 ⇒ Channel 1
2 ⇒ Channel 2
H'EEEE ⇒ Error coming
H'2222 ⇒ Equip. in working order
AC450
0 ⇒ Common reg. error (any/none
of 1 - 4 erroneous).
1 ⇒ Regulator 1 error.
2 ⇒ Regulator 2 error.
3 ⇒ Regulator 3 error.
4 ⇒ Regulator 4 error.
AC410
101⇒ Regulator missing.
102⇒ Regulator error.
H'EEEE ⇒ Error coming
H'2222 ⇒ Equip. in working order
1 ⇒ Battery A (Only AC 450)
2 ⇒ Battery B (Only AC 450)
H'EEEE ⇒ Error coming
H'2222 ⇒ Equip. in working order
1 ⇒ Unit A (Only AC 450)
2 ⇒ Unit B (Only AC 450)
H'EEEE ⇒ Error coming
H'2222 ⇒ Equip. in working order
H'EEEE ⇒ Error coming
H'2222 ⇒ Equip. in working order
1 ⇒ Channel A
2 ⇒ Channel B
Controller 450 User's Guide
H'
I-27

Advertisement

Table of Contents
loading

Table of Contents