Page 1
BS-100 DYFI Operators Handbook Program Version P1-BS100-3-20 P5-BS100-3E20 Protecting environment, life and property... P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
Page 2
BS100 DYFI Operators handbook P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
Operators handbook Contents Please note! This handbook contains instructions for operation of fire alarm system BS-100 DYFI ready designed and assembled from the factory. If the system is to be expanded on site, please see separate handbooks covering internal mounting and internal connections.
Page 4
Appendix B - Replacing the paper roll in the optional printer....47 Appendix C - Multiple BS-100/-Control panels with common repeater units (BU-100/101/70) ............48 Appendix D - BS-100 master / Control unit with BS-60 slaves ....53 P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
* Lamps go steady when “Sounder silence” button is “Carry-out” (enter) key. Select the operated. menu part on which the cursor is pointed. Fig. no. 1: BS-100 DYFI operating/control panel with indication lamps. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
All active prewarnings may be seen through the menu function “SHOW STATUS”, “PREWARNING”. Access to the menu is obtained by pressing ↵ ↵ ↵ ↵ key on the front panel. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
If everything is in a normal condition the following text will appear in the display: RESET OK NORMAL CONDITION F. Close the door. In normal condition only the “MAINS” indication lamp should be illuminated when the door is closed. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
Example of text in the display if detectors with address no. 345 has initiated the alarm.: AL 01 ADDRESS NO. 0345 Print out on the optional printer: ****FIRE**** DATE: 15.08.91 T1.05.02 AL 01 ADERESS NO.: 0345 P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
If the “MORE ALARMS” indication lamp lights, please see section 4.1 Press “RESET”-button. The following text will appear in the text display: RESET PROCEDURE IN PROGRESS WAIT......P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
Page 10
STILL IN ALARM COND.” indication lamp also will be lit. If the alarm condition disappears, the indication lamp will turn off and the address automatically restored to the system. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
RESET PROCEDURE IN PROGRESS WAIT......This text will remain in the display for up to 60 seconds. The reset procedure is identical to the one described in section 2.2. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
Page 13
STILL IN ALARM COND.” indication lamp also will be lit. If the alarm condition disappears, the indicator lamp will turn off and the address automatically restored to the system. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
(sounder circuit). The nature of the fault can be identified by using the menu. ↵ ↵ ↵ ↵ Access to the menu is obtained by pressing the -button on the five elements key-pad. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
The internal buzzer is muted, and the amber (yellow) “FAULT” indication lamp will switch to steady light. Note the fault text indicated in the display and file the printout from the optional printer. Contact technical /serice personnel. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
That particular parts of the menu structure is shown prior to each section in order to ease the function overwiew. When the control panel front door is opened, the following text will appear in the display: Short form AUTRONICA FIRE ALARM SYSTEM BS-100 operators USER MENU instruction. This appears on...
The required function is selected by moving the cursor by means of the arrow keys in the key-pad on the control panel front. ↵ ↵ ↵ ↵ The function is selected, by pressing the -key. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
= number of addresses ready for disablement. The time limit is automatically set to 2 hours (default value). ↵ ↵ ↵ ↵ Press ß Ý to select other values and press P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
↵ ↵ ↵ ↵ If more than one zone is to be disabled select “YES”, press and repeat the disable procedure. Select “NO” to end the “DISABLE ZONE” procedure. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
The following text will appear in the display: DISABLEMENT OF BT-OUTPUTS DISABLEMENT EXECUTED ↵ ↵ ↵ ↵ Press and the system will return to “DISABLE CONTROLS”-menu with possibility to return to the main menu. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
The following text will appear in the display: DISABLE SOUNDERS DISABLEMENT EXECUTED ↵ ↵ ↵ ↵ Press , an the system will return to the “DISABLE”-menu with possibility to return to the main menu. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
Before restoring addresses it is always advisable to check the sensitivity to address ensure that an alarm is not present. By restoring the address(es), the addresses will revert to their normal function. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
Select zone number to be restored by means of the arrow keys and press ß Ý. It is also possible to move he cursor to “NEXT” and “PREVIOUS” and ↵ ↵ ↵ ↵ press to select zone number. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
OUTPUTS" are selected, the following text will appear in the display: RESTORE OUTPUT CONTROLS RESTORE COMPLETED ↵ ↵ ↵ ↵ Press , and the system will return to the "RESTORE CONTROLS" with possibility to return to the main menu. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
RESTORE: SELECT WITH ⇐ ⇐ ⇐ ⇐ Þ Þ Þ Þ PRESS RESTORE COMPLETED ↵ ↵ ↵ ↵ Press , and the system will return to the "RESTORE"-menu with possibility to return to the main menu. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
"SHOW STATUS” menu. "STORED EVENTS" is continually up-dated detailing the last 150 events in Stored events the system. The last event will always be shown first. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
Page 30
All functions entered (carried out) via password. Openings of the control panel front door. Closing of the control panel front door. "Cold-start", the system has been powered up. "Warm-start", ("watch-dog" internal function). P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
TEST OF TRANSMISS. LINE TO FIRE BRIGADE ↵ ↵ ↵ ↵ WHEN COMPLETED PRESS This function will activate the corresponding outputs. Inform the fire brigade if connected! P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
(This test is automatically carried out by the BS-100 every day at 10:00 AM). Before continuing operate the "SOUNDER SILENCE" and "RESET" pushbuttons. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
The built-in buzzer will be activated until the buzzer test sequence is ↵ ↵ ↵ ↵ terminated by pressing the key. Buzzers on all repeater units will also operate during this test sequence. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
SYSTEM SELECT WITH ⇐ ⇐ ⇐ ⇐ Þ Þ Þ Þ PRESS SENSITIVITY INTERNAL CONFIG. DATA MM The rest of the text will appear by pressing the ß key. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
The analogue value (sensitivity) is updated every 5th second. The value will alter slightly at each update due to minor environmental changes. (During the first few seconds of the sequence the display will show sensitivity = 000). P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
Page 36
The sequence is carried out the same way as described above and a selection between printer or display can be made. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
When an address reaches the monitoring level (Between 96 - 103 answer pulse), the BS-100 DYFI function will automatically raise the alarm limit so that the quiescent value and alarm level threshold is maintained. P-BS100/FE - Rev.F / Doc/ 980114...
The following text will appear in the display: INTERNAL PROGRAM VERSION PROGRAM: X-XX SYSTEM-TEXT: X-XX "SYSTEM TEXT" indicates the menu program version. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
The following text will appear in the display: SHOW DATE AND TIME DATE: dd.mm.yy TI: hh.mm RET MM 10.3 Configuration Configuration See "Commissioning Handbook" - BS-100. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
DATA CHANGE ADD PRINTOUT RET MM Select the required function by means of the arrow keys and press the ↵ ↵ ↵ ↵ key. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
ß ß ß ß Ý Ý Ý Ý PRINTER TEXT 0001 Change the ref. number for the printer text and move the cursor to the end of the line. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
If the key is kept constantly pressed, the paper feed continues until the pressure on the key is released. 12. Service Service Main menu Service See "Commissioning Handbook" - BS-100. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
P5 - BS100 - XNXX Version no. Language (N = Norwegian) Program no. Control panel type Menu program System Program P1 - BS100 - XXX Version no. System program P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
Page 44
Automatic disabling of detectors in alarm condition after reset has to be accepted within 10 seconds. No automatic disabling of detector in alarm condition after reset Reset time is programmed to be a minimum, also after alarm P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
Page 45
If the AK/BMA-outputs are required to be activated the silent alarm input must be removed or a manual call-point operated. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
Page 46
Internal buzzer is disabled when front door is open. Sounder silence and reset button must be pressed for more than 2 seconds to activate the function. Custom specified address text is presented on line 2. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
Location of the finger screw on the optional printer (front view). Feed the paper manually through the printer by turning the finger screw. (See fig. B) Close the control panel inner door. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
H1 Indicator lamp H2 Indicator lamp H3 Indicator lamp Device(s) still in alarm cond. Prewarning Fault Function disabled Mains More alarms Operation buttons More alarms Sounder silence Sounder silence (buzzer) Reset P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
Page 49
BS-100 control panel which registered the prewarning and on the BU- units. Only the BMFO-output on the control panel which registered the prewarning will be activated. Prewarning output on the EA- will be activated (output L58). P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
Page 50
BS-100 control panels which still has addresses in alarm condition. If this lamp lights on one of the BS-100 control panels, it will also light on the BU-units. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
Page 51
To reset the entire system (BS-100 and BU-units) operate the last control panel in abnormal condition. C.2.2.2 From EA- or BU-100 Operating of the "RESET" from EA 1/2/3 or BU-100 will reset the entire system. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
Page 52
The real-time clock in BS-100 control panels has to be set manually via menu. The EA- clock will be set equal to the clock in control panel with address A. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
Fire alarm from a BS-60 control panel is registered on the relevant BS-60 control panel and on the BS-100 control panel. There will be no display of info. on any other BS-60 control panel. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
Page 54
BS-100 control panel. There will be no display of info. on other BS-60 control panels. 2 alarms from 2 different BS-60 control panels will be registered as more alarms on the BS-100 control panel. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
Page 55
If the "RESET" function is set to "ON", the "RESET" can be operated from both the BS-100 and the BS-60 control panel. When operating the "RESET" from the BS-60 control panel, only the BS-60 which is operated will be reset. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
Page 56
BMA, BMF, BMFO outputs from the BS-100 control panel can only be disabled/restored from the BS-100 control panel. BMA, BMF, BMFO outputs from the BS-60 control panel can only be disabled/restored at the relevant BS-60 control panel. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
Page 57
D.4.2 Internal In all control panels the internal clock has to be set manually. The internal clocks of all control panels are independent and must be set individually. P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS...
Page 58
Norway and has a world-wide sales and service network. For more than 40 years Autronica’s monitoring systems have been saving lives and preventing catastrophes on land and at sea. Autronica Fire and Security’s most important business area is fire detection & security. Autronica Fire and Security stands for preservation of environment, life and property.