FUNCTIONAL FEATURES

The power supply unit is composed by a linear feeder, with function of limitation of constant current,
an analogic control circuit and a microcontroller supervision circuit.
The power supply is divided into 3 terminal outputs protected by the relative fuses.
- BAT : where buffer battery will be connected
- OUT 1 , OUT 2 , : for generic loads
Battery is charged with constant current (27,6 V @ 25
Maximum current supplied by feeder is 2 A (1 A for load and 1 A for battery).
LED in control card are close to respective fuses (see picture n. 1) to indicate:
- Interrupted fuse for each output (DL2, DL8, DL3 )
- Tension presence (RETE)
A microcontroller system, checks all possible anomalies, providing a FAILURE signal in the following
situations:
1. Output fuses interrupted
2. Low battery tension (<21 Vdc)
3. Over tension to output (> 29 Vdc)
4. Tension absence RETE
Both Failure and Power absence signals are located in a connector on the supervision and control
card.
In case of a power supply failure or power absence, feeding for logic and control circuits is provided
by battery.

ELECTRICAL FEATURES

- Feeding tension : 230 Vac +10% / -15%
- Frequency : 50 Hz
- Output tension : 27,6 Vdc ( -15% / +10%)
- Minimum output tension: 19,6 Vdc (in absence of voltage and with exhausted battery)
- Max output current: 2 A max.
- Adjustment on full charge power variations (+10% / -15%) : best than 1 %
- Adjustment on load variations (0 to 100%) : best than 1%
- Residual ripple on full load: 30mVpp (a 230 Vac )
- Fuses : [ battery:T 4 AL] [ OUT 1 , OUT 2 :T 1,6 AL: ] [ AC Power supply :T 1,6 AL]
[ Overtension: T 4 AL ]
Protection against battery polarity inversion: diodes
MA-AL-T272-01-01 Manual TUL272 eng rev1
POWER SUPPLY TUL 272
°
C) with environmental limitation of current.
Rev.1 Page 1 of 4

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TUL 272 and is the answer not in the manual?

Questions and answers

Summary of Contents for Venitem TUL 272

  • Page 1 POWER SUPPLY TUL 272 Installation Manual FUNCTIONAL FEATURES The power supply unit is composed by a linear feeder, with function of limitation of constant current, an analogic control circuit and a microcontroller supervision circuit. The power supply is divided into 3 terminal outputs protected by the relative fuses.
  • Page 2 MECHANICAL FEATURES Dimensions (mm) : width 280 ; height 373 ; depth 125 Weigth : 6,2 Kg ENVIRONMENTAL FEATURES ° ° Operating temperature: from -5 C to +40 ± Relative humidity: from 5% to 93% Cooling: air cooling Installation place: sheltered from atmospheric agents SECURITY INSTRUCTION 1.
  • Page 3 ALTERNING POWER SUPPLY TERMINALS L line connection ( 230 Vac) land protection connection N neutral connection Check and adjustments P1 e P2 check are calibrated from factory and must not be modified by operators. Tampering of these checks will cause guarantee loss. FRONT PANEL SIGNALS - Low Battery: - check tension lower than 22 Vdc...
  • Page 4 RETE F3 F4 F5 PICT. 1 Fig. 1 PICT. 2 Via del Lavoro, 10-30030 Salzano (VE) Tel. (+39) 041 5740374 – Fax (+39) 041 5740388 Sito Web www.venitem.com E-mail info@venitem.com MA-AL-T272-01-01 Manual TUL272 eng rev1 Rev.1 Page 4 of 4...

Table of Contents