Download Print this page

VERIS INDUSTRIES, INC. V102 Installation Manual page 2

10a spst enclosed relay with resistive hoa switch

Advertisement

TM
WIRING COLOR CODES
CONTROL SYSTEM INPUT
HI
wht/black
120VAC
LOW
wht/blue
10-30VAC/DC
COMM
wht/yellow
Common
Resistive HOA Position Monitor
CONTACT AND COIL SPECIFICATIONS
TYPICAL COIL PERFORMANCE
Pull in Voltage
10-30V.....................................
120V........................................ 78
Drop Out Voltage
10-30V.....................................
120V........................................ 18
Voltage
10V.......................................... 25mA
24V.......................................... 31mA
30V.......................................... 39mA
120V........................................ 22mA
CONTACT RATINGS
Resistive.............. 10A@277VAC
Motor.................... 1/3HP@120VAC
Gold Flash............. Yes
Z203392-0C
PAGE 2
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
V102
CONTACT OUTPUT
AC
DC
8
9
AC
DC
2
3
Coil
Current
AC
DC
14mA
16mA
18mA
-
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
INSTALLATION GUIDE
WIRING EXAMPLE
Nipple mount directly to a panel
To Load
COIL
To Controls
HOA POSITIONS
Up position: contacts are closed.
HAND
OFF
Middle position: contacts are open.
AUTO
Down position: control system actuates the contacts.
PROGRAMMING THE RESISTIVE
MONITOR
The resistive monitor is a 0-10 kΩ analog output for monitoring the HOA switch
position. Please use the following ranges for the DDC scaling.
Condition
Range* (Ω)
Line Open
Greater than 8630
HOA Off
5290 to 8630
HOA Auto
2880 to 5289
HOA On
1200 to 2879
Line Shorted
Less than 1200
* Ranges based on the presence of 0-1000Ω of resistance due to wire. Average # of feet for 1000 Ω
by wire AWG listed below.
Wire Type (AWG)
Distance Allowed (ft.)
26
12,189
22
30,864
18
78,296
† All 2-wire runs
Nipple mount to a 2x or 4x electri-
cal box
CONTACTS
To Load
Wire
Nut
To Controls
Nominal Values without Wire
Resistance* (Ω)
n/a
6190
3391
1406
n/a
05121