VERIS INDUSTRIES, INC. V101 Installation Manual

10a spst enclosed relay with hoa switch

Advertisement

Quick Links

TM
V101
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
DIMENSIONS
4.0"
(103 mm)
3.8"
(97 mm)
3/4" NPT Nipple
Z203391-0D
PAGE 1
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
RELAYS
2.0"
(52 mm)
2.3"
(64 mm)
(59 mm)
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
10A SPST Enclosed Relay With HOA Switch
Installer's Specifications
Operating Temperature
Operating Humidity
Expected Relay Life
Relay Status
Wire Specifications:
Lead Length
Gauge
Insulation Class
Agency Approvals
INSTALLATION
Disconnect and lock out all power sources before beginning the
installation.
1. Using the threaded nipple, connect the relay to the desired enclosure through a
knock out hole.
2. Secure with the conduit nut provided.
3. Connect coil wires:
• Choose the coil common lead (white with yellow stripe) and connect it to
the common (-) source termination point.
• Choose either the low voltage (10-30VAC/DC, white with blue stripe) or
high voltage (120VAC, white with black stripe) lead, depending on the
application requirements, and connect it to the (+) source termination
point.*
NOTE: When connecting the control side of this device (#18 wires) to power
line circuits, provide current limiting at 7 amps max.
4. Connect relay contacts:
• Choose the two orange wires (N.O. contact) and connect to the switched
load.
5. Secure the enclosure and reconnect power.
* Isolate or insulate all non-terminated wires according to local electrical code requirements, i.e.
wire nut.
2.5"
INSTALLATION GUIDE
V101
-40° to 55°C (-40° to 131°F)
10-90% RH, non-condensing
Electrical (@ rated current) 100,000 cycles;
Mechanical (unpowered) 10,000,000 cycles
LED ON=energized
14" (356mm) min.
UL1015; Coil: 18AWG; Contacts: 16AWG
UL508 enclosed device listing, pollution degree 2
600VAC RMS
05121

Advertisement

loading

Summary of Contents for VERIS INDUSTRIES, INC. V101

  • Page 1 INSTALLATION GUIDE RELAYS V101 V101 10A SPST Enclosed Relay With HOA Switch Installer’s Specifications Operating Temperature -40° to 55°C (-40° to 131°F) Operating Humidity 10-90% RH, non-condensing Expected Relay Life Electrical (@ rated current) 100,000 cycles; Mechanical (unpowered) 10,000,000 cycles...