Honeywell EVCS-CMPT9 Installation, Commissioning And Maintenance Manual page 12

Compact master and slave exchange
Table of Contents

Advertisement

EVCS-CMPT9 Programming
Honeywell
Status Screen Menu
Compact M9
-Healthy- Calls
0
10:24:01 07|01|11
On power up, or by pressing the * key, the Status Screen Menu can be accessed.
The top line can be changed from the Set Site Name Menu. The second line can be changed from Set Panel Name Menu. The
third line contains the status of the unit. The fourth line shows the current time and date.
The padlock in the top right of the display shows the state of the write protect jumper on the rear of the display PCB. This should be
UNLOCKED to commission the system, and then LOCKED to prevent any unauthorised changes to the commissioned system.
Menu Structure
There are 3 levels of accessibility: User, Manager, and Engineer.
User level is accessible to all.
Manager level is accessible to those who log in as Manager or Engineer.
Engineer level is accessible to those who log in as Engineer.
To access the menus from the Status Screen Menu, press the TICK button.
Note: If panel is installed in a public area, then all operations will be restricted to Manager or Engineer only, except for user menus
only. This includes receiving and initiating calls.
>Log in
User Menu
Accept faults
View current faults
View fault log
View event log
View call log
View panel version
Back
Items marked * can be configured to display or not at user level (see later).
>Log out
Manager Menu
Accept faults
View current faults
View fault log
View event log
View call log
View panel version
Set time+date
Change manager PIN
www.acornfiresecurity.com
*
*
*
*
*
11
www.acornfiresecurity.com