2gig Technologies 2GIG-SMKT2-345 Installation Instructions Manual

Wireless photoelectric smoke and temperature
Table of Contents

Advertisement

Available languages

Available languages

Quick Links

2GIG-SMKT2-345
WIRELESS PHOTOELECTRIC
SMOKE AND TEMPERATURE
ALARM
388 West Center Street
Technical Support 866-670-1591
www.2gig.com
Installation Instructions
DESCRIPTION
The 2GIG-SMKT2-345 is a photoelectric smoke alarm with a built-in transmitter
designed for use with the 2GIG-CNTRL-345 security system. When smoke is
detected, the alarm sounds a loud local alarm. Twenty seconds after the local
alarm sounds, the built-in transmitter sends a digitally coded wireless signal to
the Control Panel. The wireless signal will be repeated every 20 seconds as
long as smoke is still present.
In addition to the photoelectric detector, the unit contains an integrated fi xed
135° temperature and rate-of-rise heat sensor that will send an alarm signal
based on temperature detected.
BUILT-IN WIRELESS TRANSMITTER
The smoke alarm can send three different wireless signals to the alarm Control
Panel: alarm, low battery, and status.
Every hour, the smoke alarm sends a status transmission to the Control Panel.
The hourly signal updates the Control Panel with the smoke alarm's condition.
By monitoring status transmissions, the Control Panel can determine that the
smoke alarm is still operational in the installation and if it has a low battery.
The Control Panel must be programmed to the transmitter's serial
number before system testing and operation. Refer to the Control Panel's
instructions for details on programming.
INSTALLATION
1. Slide the battery compartment cover away from the unit to unsnap it and
lift it off. See Figure 2.
2. Observing proper polarity, insert the two 3V lithium batteries supplied into
the alarm battery compartment and replace the battery cover.
3. Remove the red plastic dust cover from the unit.
4. Refer to Page 3 for selecting a proper location for the smoke alarm.
5. Using the two screws and anchors provided, mount the base.
6. Attach the unit to the base as follows:
• Line up the raised alignment tab on the lip of the unit with the alignment
arrow on the base. See Figure 3.
• Insert the unit into the base and turn clockwise approximately 15
degrees. It should snap fi rmly into place.
• IMPORTANT: The unit cannot be attached to the base if no batteries
are installed.
PROGRAM SMOKE ALARM INTO THE CONTROL PANEL
Before testing the smoke alarm, the internal wireless transmitter must be
programmed into the Control Panel.
1. Refer to the Control Panel's instructions to prepare the receiver to accept
the smoke alarm's serial number.
2. Press the smoke alarm's TEST/SILENCE button for 4 seconds. The
smoke alarm will perform a sounder test, a sensitivity test, and send a
test signal to the Control Panel.
3. Verify that the signal was received by the Control Panel and that the
sensor was entered into the system.
4. Exit Control Panel programming before testing the smoke alarm.
Orem, UT 84057
R
CM
Temperature
Sensor
Test/Silence
button
Figure 3. Smoke Alarm-to-Base Alignment
SMOKE TEST
Units should be tested in place annually using one of the following methods:
A. Use Smoke! in a can
B. Hold a smoldering punk or cotton wick close to the unit and gently direct
the smoke into the smoke entry openings for 20 seconds or until an alarm
is indicated.
The smoke alarm LED should stay on and the sounder should emit a temporal
three pattern, and an alarm should be indicated at the Control Panel. Disarm
the system to reset the Control Panel alarm. Be sure to extinguish the
smoke source after testing!
SILENCE THE ALARM
Press the TEST/SILENCE button to silence the sounder during an alarm. After
a few minutes, the sounder and alarm resume if smoke is still present.
LED
Figure 1. Smoke Alarm Features
Figure 2. Battery Compartment
Alignment arrow
Alignment tab
and follow directions on the can.
®
Sounder vent
Temperature
sensor
Battery
compartment
1

Advertisement

Table of Contents
loading

Summary of Contents for 2gig Technologies 2GIG-SMKT2-345

  • Page 1 Installation Instructions DESCRIPTION The 2GIG-SMKT2-345 is a photoelectric smoke alarm with a built-in transmitter designed for use with the 2GIG-CNTRL-345 security system. When smoke is detected, the alarm sounds a loud local alarm. Twenty seconds after the local alarm sounds, the built-in transmitter sends a digitally coded wireless signal to the Control Panel.
  • Page 2: Sensitivity Test

    8. Observing proper polarity, replace the batteries and the battery SENSITIVITY TEST compartment cover. 1. Press and hold the TEST/SILENCE button for 4 seconds. Once the test starts, the smoke alarm LED fl ashes 1 to 9 times. 9. Reattach the unit to its mounting base. See Installation , Step 6. 10.
  • Page 3: Selecting A Location

    Since regulations pertaining to smoke alarm/detector installation vary from SELECTING A LOCATION state to state, contact the authority having jurisdiction (AHJ). Where public Selecting a suitable location is critical to the operation of smoke alarms. This safety is primary, the AHJ may be federal, state, local, or other regional equipment should be installed in accordance with National Fire Protection department or individual such as a fi...
  • Page 4 There evacuating the area unassisted. are no obligations or liabilities on the part of 2GIG Technologies for FIRE PREVENTION AND ESCAPE consequential damages arising out of or in connection with use or The purpose of an early warning smoke alarm is to detect the presence of fi...
  • Page 5: Installation

    Instructions pour l’installation DESCRIPTION Le 2GIG-SMKT2-345 est un détecteur de fumée photoélectrique comportant un émetteur intégré destiné à être utilisé avec les systèmes de sécurité 2GIG-CNTRL-345. Quand de la fumée est détectée, l’alarme du dispositif déclenche une sonnerie locale retentissante.
  • Page 6: Remplacement Des Piles

    Remettre le couvercle de l’alarme en place de la façon suivante : TEST DE SENSIBILITÉ • Aligner le couvercle de l’alarme sur l’appareil. Appuyer sur le bouton TEST/ARRÊT et le maintenir enfoncé pendant 4 secondes. Une fois que le test a débuté, le voyant DEL clignote de une à neuf fois. •...
  • Page 7 Puisque les réglementations relatives à l’installation de détecteurs de fumée varient CHOIX D’UN EMPLACEMENT d’une province à l’autre, communiquer avec les autorités compétentes. Lorsque la Le choix d’un emplacement approprié est essentiel au fonctionnement des détecteurs sécurité publique est primordiale, ces autorités peuvent être un ministère fédéral, de fumée.
  • Page 8: Détecteurs De Fumée

    GARANTIE LIMITÉE avertir qu’il ne faut jamais penser que vous pourrez toujours éviter d’être victime de Ce produit 2GIG Technologies est garanti contre tous les vices de fabrication, matériaux dommages matériels ou corporels. et main d’œuvre, pendant deux (2) ans. Cette garantie est accordée exclusivement Les études actuelles montrent que les détecteurs de fumée peuvent manquer de réveiller...

Table of Contents