1-port ilink tx, long distant display transmitter, rj45 (2 pages)
Summary of Contents for Advantech WISE-4220 Series
Page 1
User Manual WISE-4220 Series Model on: WISE 4220...
Page 2
No part of this manual may be reproduced, copied, translated or transmitted in any form or by any means without the prior written permission of Advantech Co., Ltd. Information provided in this manual is intended to be accurate and reliable. How- ever, Advantech Co., Ltd.
Page 3
Technical Support and Assistance Visit the Advantech web site at www.advantech.com/support where you can find the latest information about the product. Contact your distributor, sales representative, or Advantech's customer service center for technical support if you need additional assistance.
Page 4
Before setting up the system, check that the items listed below are included and in good condition. If any item does not accord with the table, please contact your dealer immediately. Please go to Section 1.6 for package list. WISE-4220 Series User Manual...
Page 5
The sound pressure level at the operator's position according to IEC 704-1:1982 is no more than 70 dB (A). DISCLAIMER: This set of instructions is given according to IEC 704-1. Advantech disclaims all responsibility for the accuracy of any statements contained herein.
Page 6
FCC Caution: Any changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate this equipment. This transmitter must not be co-located or operating in conjunction with any other antenna or transmitter. WISE-4220 Series User Manual...
Page 7
RF peut être augmentée si l'appareil peut être conservé aussi loin que possible du corps de l'utilisateur ou que le dispositif est réglé sur la puissance de sor- tie la plus faible si une telle fonction est disponible. WISE-4220 Series User Manual...
Page 8
Cet équipement est conforme aux limites d'exposition aux rayonnements ISED établies pour un environnement non contrôlé. Cet équipement doit être installé et utilisé avec un minimum de 20 cm de distance entre la source de rayonnement et votre corps. Dipole WISE-4220 Series User Manual viii...
........1 Series Family and Specifications .............. 2 Mechanical Design and Dimensions ............2 1.2.1 WISE-4220 Series Dimension ............2 Figure 1.1 ME Dimension Front & Side ........2 Switch......................3 LED Definition ................... 4 Certification and Safety Standard ............. 4 Package Information .................
Page 10
....43 Modbus Function Code Introduction ............44 WISE-4220-S231 Modbus Mapping Table ..........44 Appendix B REST for WISE-4220 Series ..... 47 Introduction ..................... 48 REST Resources for WISE-4220 Series ..........48 B.2.1 Sensor Input ................48 WISE-4220 Series User Manual...
Series Family and Specifications Function Model Description IoT Wireless Sensor Node with Temperature/ Wireless Sensor Node WISE-4220-S231 Humidity Sensors Mechanical Design and Dimensions 1.2.1 WISE-4220 Series Dimension Figure 1.1 ME Dimension Front & Side WISE-4220 Series User Manual...
Switch Open the housing behide the WISE-4220 module, you can see a switch inside. The battery socket is no function for WISE-4220 series. It is reserved for WISE-4220 series. Switch Description Position ON (Default) Normal Mode Initial Mode Operation Mode...
– EN 61000-4-5:2014 – EN 61000-4-6:2014 – EN 61000-4-8:2010 – EN 61000-6-1:2017 – EN 61000-6-2:2017 – EN 61000-6-3:2007 +A1:2011 +AC:2012 – EN 61000-6-4:2007 +A1:2011 – EN 301 489-1 V2.1.1 (2017-02) – EN 301 489-17 V3.1.1 (2017-02) WISE-4220 Series User Manual...
Consider using ground straps, anti-static floor coverings, etc. if you use the equipment in low humidity environments. Note! Measuring temperature and humidity will depend on sensor type. Whether the device is measuring temperature or humidity depends on the settings of the sensors. WISE-4220 Series User Manual...
Accuracy: ±4% for 0%~50% RH ±6% for 50%~60% RH ±10% for 60%~90% RH Update Rate: Minimum 1 seconds Response Time: 10 seconds (Achieving 63% of a step function) Long Term Drift: 0.5% RH/Year WISE-4220 Series User Manual...
DIN rail adapter to WISE-4220 module with flathead screw driver as below. When the module is mounted on a rail, you may also consider using end brackets at each end of the rail to keep the module from sliding horizontally along the rail. WISE-4220 Series User Manual...
Page 23
Figure 3.1 DIN Mounting Kit Figure 3.2 DIN Mounting Install WISE-4220 Series User Manual...
Page 24
Figure 3.3 DIN Mounting Front Figure 3.4 DIN Mounting Back WISE-4220 Series User Manual...
Each WISE-4220 module is packed with a plastic wall mounting bracket. Users can refer to the bracket dimensions and assembly steps to configure an optimal place- ment in a wall, panel, or cabinet. Figure 3.5 Wall Mounting Kit Dimension Figure 3.6 Wall Mounting Install 1 WISE-4220 Series User Manual...
Page 26
Figure 3.7 Wall Mounting Install 2 WISE-4220 Series User Manual...
Then mount the WISE-4220 module steadily to the pole by locking the pole mounting ring tightly. Figure 3.8 Polar Mounting Front Figure 3.9 Polar Mounting Back WISE-4220 Series User Manual...
Use the shortest possible wire length. Use wire trays for routing where possible. Avoid running wires near high-energy wiring. Avoid running input wiring in close proximity to output wiring. Avoid creating sharp bends in the wires. WISE-4220 Series User Manual...
For PC platforms, the minimum requirements of web browsers are as below: Internet Explorer (version 11) Google Chrome (version 30) Mozilla Firefox (version 25) Mobile Browser Chrome Firefox Safari IE11 IE10 Configuration File Upload Data Log Chart Data Log Export WISE-4220 Series User Manual...
Enter IP address of module with "/con- fig", for example, the default URL is http://192.168.1.1/config Enter the account and password. Then click Login button. Login After login, you will see the configuration web page. Information WISE-4220 Series User Manual...
Page 33
Click the button on the top, and you can switch to other pages. Menu 4.2.5.2 System Information In the information page, you can see the dashboard: module detail, network setting, and module information, including the firmware version. WISE-4220 Series User Manual...
Page 34
4.2.5.4 Wireless Status For WISE-4220 series, users can refer to the WLAN RSSI indicators for the signal quality in Wireless Status section. It also shows the MAC ID of the client device. If the module is in AP Mode, the WLAN RSSI Level and Refresh button will not be shown.
Page 35
Access Point (AP) that the WISE module is going to connect, and config- ure the security type here. WISE-4220 series modules provide a “Second AP Setting” section, an optional setting for the WISE module to connect to another AP automatically.
Page 36
4.2.5.8 IO Status The IO family of WISE-4220 series is composed of various types of IO, including tem- perature and humidity sensors, DI, DO and AI. You can select the models which meet your requirements based on the applications. ...
Page 37
“Max” and “Min” tabs. By clicking “Reset,” you can reset the max- imal and minimal records in the module. You can also change the settings of channel 0 and 1 in the “configuration” tab. The fields that can be changed are shown as follows: WISE-4220 Series User Manual...
Page 38
The Communication WDT has a Host Idle time, and will be triggered when all TCP connections are closed. This includes all hosts which visit WISE and the communica- tion between remote servers like Dropbox or private servers. Once the Communica- WISE-4220 Series User Manual...
Page 39
You can see the current time, select the time zone you want to use, and calibrate the time by clicking “Click Me” to inquire time from host devices. You can enable SNTP, so that the module can act as an SNTP client to perform time synchronization from an assigned SNTP server. WISE-4220 Series User Manual...
Page 40
The “FSV by Communication WDT” determines whether to enable the FSV function triggered by communication with WDT. You can enable the FSV function for all the output channels of the module here. WISE-4220 Series User Manual...
Page 41
Go to the “Firmware” page in system configuration and click the icon to select the configuration file you want to upload from the local folder. Before uploading the configuration file to the module, select whether or not to apply the IP settings to the WISE module. WISE-4220 Series User Manual...
Page 42
Go to the “Firmware” page in system configuration and click the icon to select the configuration file you want to upload from the local folder. You can find the latest offi- cial release firmware file at the Advantech support site (http://support.advan- tech.com/support/).
Page 43
For WISE-4220 wireless modules, users can only configure access con- trol by the IP address, not the MAC address. 4.2.5.13 Data Logger The WISE-4220 series supports data log functions. I/O status can be logged in the module and queried from the module. Time & Date / SNTP Before you start the log function, please make sure that the RTC time inside the WISE module is correct.
Page 44
“Low Alarm” boxes. The “By Sensor” tab is used to decide what kinds of data will be logged. Note that the log memory will be cleared once any parameter changed in the “By Channel” and “By Sensor” tabs. WISE-4220 Series User Manual...
Page 45
Now you can click Query to query the data from local memory. Then the data will be shown in a chart and table. Click “Save” to save data from the WISE module into a *.json file, or you can click “Clear” to clear all data in local memory. WISE-4220 Series User Manual...
Page 47
You can use “Authentication” section for the private server with a User Name and Password provided by our example agent. After “Cloud Configuration” is configured as a private server, you can go back to the Logger Configuration page in Data Logger. Before switching Cloud Upload to ON, WISE-4220 Series User Manual...
Page 48
The WISE module will push a notification in JSON format to the private server. You can switch the I/O Log or System Log ON, and then the WISE module will start push- ing the latest logged data to the private server. WISE-4220 Series User Manual...
"Infrastructure Mode", and the connected AP is able to access internet Select Dropbox as the cloud server. The browser will open a new window for Dropbox. Enter your Dropbox account information including E-mail and Password, then click “Sign in.” WISE-4220 Series User Manual...
Page 50
Dropbox will then provide a code. Copy this code and return to the configuration web page of the WISE module. Click "Next" to enter the code. Paste the code provided by WISE Cloud Logger, then click "Submit." WISE-4220 Series User Manual...
Page 51
If your WISE-4220 module is correctly connected to the Internet, you will be able to set the functions successfully. Click "Close" to return to Configuration. You will then see the “Link Status” shows “Ready.” WISE-4220 Series User Manual...
40101~40102 Temperature Read Sensor Status* 40103~40104 Humidity Read 40021 Temperature Read Historical Max. Sensor Value 40022 Humidity Read 40041 Temperature Read Historical Min. Sensor Value 40042 Humidity Read 40201 Temperature Read Type Code** 40202 Humidity Read WISE-4220 Series User Manual...
Page 55
Description Built-in logging is out of memory for IO log. (No space left) Built-in memory errors. Built-in logging is out of memory for System log. (No space left) Cloud upload fail Cloud push fail 5-15 Reserved WISE-4220 Series User Manual...
Amazon and Yahoo web services. The web service is developed based on HTML5 language, if a user need to integrate this into other web services, the fol- lowing information/command list can be referenced. REST Resources for WISE-4220 Series B.2.1 Sensor Input...
Page 59
PATCH /sensor_value/slot_0 Single Channel Request: PATCH /sensor_value/slot_0/ch_num [Example] Request: PATCH /sensor_value/slot_0 Content-type: application/json " SVal": [ "Ch":0, "ClrH": 0 PATCH "Ch":1, "ClrL":0 Response: 200 OK Request: PATCH /sensor_value/slot_0/ch_1 Content-type: application/json "ClrL":0 Response: 200 OK WISE-4220 Series User Manual...
Page 60
0 : not occurred Write 0 : clear the low alarm status High alarm status High Alarm Read 1 : high alarm occurred. Number Status 0 : not occurred Write 0 : clear the high alarm status WISE-4220 Series User Manual...
Page 61
* Sensor type code table Type Code Sensor type Sensor type and unit 4096 (0x1000) Temperature (°C) 4097 (0x1001) Temperature Temperature (°F) 4098 (0x1002) Temperature (K) 4128 (0x1020) Humidity Humidity (%) WISE-4220 Series User Manual...
Need help?
Do you have a question about the WISE-4220 Series and is the answer not in the manual?
Questions and answers