Cabinet dimensions
Cabinet dimensions
Table 6. Power-Sure 700 unit cabinet sizes
kVA
rating
Bypass
Metering
10
Yes
No
10
Yes
Yes
15
Yes
No
15
Yes
Yes
25
Yes
Yes
30
Yes
Yes
45
Yes
Yes
50
Yes
Yes
75
Yes
Yes
100
Yes
Yes
125
Yes
Yes
150
Yes
Yes
225
Yes
Yes
300
Yes
Yes
500
Yes
Yes
Manual bypass switch
The manual bypass switch is a break-before-make switch
located on the Power-Sure 700. The manual bypass switch
is used to bypass all power electronics in case of failure.
Bypass is standard on 50 kVA and larger units and an option
on 45 kVA and smaller units.
N
otes:
This switch may be added in the field.
36
Instruction manual IM1002004E September 2015 www.powerquality.eaton.com
Cabinet size
H x W x D (in)
BTUs/Hr
30.2 x 22.2 x 29.0
1,025
44.2 x 22.2 x 29.0
1,205
30.2 x 22.2 x 29.0
1,540
44.2 x 22.2 x 29.0
1,540
44.2 x 22.2 x 29.0
2,560
44.2 x 22.2 x 29.0
3,090
44.3 x 45.9 x 29.0
4,600
66.0 x 29.0 x 35.5
7,332
76.0 x 34.4 x 35.5
9,514
76.0 x 34.4 x 35.5
11,833
76.0 x 34.4 x 35.5
14,748
76.0 x 34.4 x 35.5
17,698
77.4 x 56.0 x 41.5
23,000
77.4 x 56.0 x 41.5
30,750
77.0 x 72.4 x 48.4
51,250
Weight (Lb)
440
520
465
700
700
720
950
1,176
1,575
2,014
2,137
2,240
3,300
4,000
5,500
Normal mode
With the switch in the normal position, the Power-Sure 700
will provide clean and regulated power to the critical loads.
The Power-Sure 700 should have the switch in the normal
position unless a failure has occurred.
These units are sold in accordance to Eaton
Selling Policy 25-000.