Control Board Measurements; Adjustment Procedure; Parts Kits; Replacement Parts - Eaton Power-Sure 700 Instruction Manual

Hide thumbs Also See for Power-Sure 700:
Table of Contents

Advertisement

Control board measurements

Control board measurements
WARNING
All service to this piece of equipment must be
performed by qualified personnel.
CAUTION
The control board (#49120/407415) is electrically referenced
to high voltage, not earth or chassis ground. Extreme care
must be used when taking measurements on the control
board. Any AC powered instruments must be ground
isolated prior to taking measurements. A ground isolated
instrument case will be at the high voltage line potential.
Measurement procedure
Verify the L–N for each phase is ±3% of the nominal
voltage. If the voltage measurement is out of range,
consult factory.
22
Instruction manual IM1002004E September 2015 www.powerquality.eaton.com

Parts kits

Table 5. 50 and 60 Hz, all voltages
kVA size
10 kVA
15 kVA
25–50 kVA
75 kVA
100–125 kVA
150 kVA
225 kVA
300 kVA
500 kVA
N
otes:
Each parts kit includes the following:
(7) Power modules (SCRs)
(3) Semiconductor Fuses
(1) Fusible link (for one full phase)
(2–4) Fan motors (depending on unit size)
(1) SCR snubber board
(3) Sense fuses
(1) Main control board

Replacement parts

Individual components are also available upon request.
Please contact the factory for specific part numbers
and prices. See "Unit component location diagrams"
on page 11–page 16 for component location and
description. When contacting Application Support, please
have the unit's full model number and serial or system
number. Call 1-800-809-2772, option 4, and then option 2.
Kit price (U.S. funds)
Consult factory
Consult factory
Consult factory
Consult factory
Consult factory
Consult factory
Consult factory
Consult factory
Consult factory

Advertisement

Table of Contents