AEMC JM830A User Manual page 4

Ac current probe

Advertisement

OPERATION
Please make sure that you have already read and fully understand the WARNING section on page 1.
Making Measurements with the AC Current Probe Model JM830A
Connect the black and red terminals to the Ampere AC range of your DMM or current measuring
instrument. Select the appropriate current range (2A AC). Clamp the probe around the conductor to be
tested. If the reading is less than 200 mA, select the lower range until you obtain the best resolution.
Read the value display on the DMM and multiply it by the probe ratio (3000/1 = 3000). (If reading =
0.592A AC, the current flowing through the probe is 0.592 A x 3000 = 1776 A).
For best accuracy: carefully center the conductor inside the probe jaw, avoid if possible, the proximity of
other conductors which may create noise.
Tips for Making Precise Measurements
When using a current probe with a meter, it is important to select the range that provides the best
resolution. Failure to do this may result in measurement errors.
Make sure that probe jaw mating surfaces are free of dust and contamination. Contaminants cause air
gaps between the jaws, increasing the phase shift between primary and secondary. It is very critical for
power measurement.
MAINTENANCE
Warning:
For maintenance use only original replacement parts.
To avoid electrical shock, do not attempt to perform any servicing unless you are qualified to do so.
To avoid electrical shock and/or damage to the instrument, do not get water or other foreign agents into
the probe.
Cleaning:
To ensure optimum performance, it is important to keep the probe jaw mating surfaces clean at all times.
Failure to do so may result in error in readings. To clean the probe jaws, use very fine sand paper (fine
600) to avoid scratching the jaw, then gently clean with a soft, oil cloth.
REPAIR AND CALIBRATION
You must contact our Service Center for a Customer Service Authorization number (CSA#). This will
ensure that when your instrument arrives, it will be tracked and processed promptly. Please write the CSA#
on the outside of the shipping container. If the instrument is returned for calibration, we need to know if you
want a standard calibration, or a calibration traceable to N.I.S.T. (includes calibration certificate plus
recorded calibration data).
Chauvin Arnoux
15 Faraday Drive • Dover, NH 03820 USA
Tel:
(800) 945-2362 (Ext. 360)
(603) 749-6434 (Ext. 360)
Fax:
(603) 742-2346 or (603) 749-6309
repair@aemc.com
(Or contact your authorized distributor)
Costs for repair, standard calibration, and calibration traceable to N.I.S.T. are available.
NOTE: All customers must obtain a CSA# before returning any instrument.
TECHNICAL AND SALES ASSISTANCE
If you are experiencing any technical problems, or require any assistance with the proper use or
application of this instrument, please call our technical hotline:
(800) 343-1391 • (508) 698-2115 • Fax (508) 698-2118
Chauvin Arnoux
techsupport@aemc.com
www.aemc.com
Shop for AEMC products online at:
®
, Inc. d.b.a. AEMC
®
®
, Inc. d.b.a. AEMC
ShopAEMC
www.
®
Instruments
Instruments
.com
1.877.766.5412
99-MAN 100113.v5 06/07

Advertisement

loading