Waeco ECL-76 Installation And Operating Manual page 104

Charging current distributor
Table of Contents

Advertisement

Available languages

Available languages

Connection
Air conditioner
Dometic
FreshLight1600
Dometic
FreshLight2200
Dometic
FreshLight2200
Dometic
FreshLight2200
Dometic
FreshWell3000
Dometic
FreshWell3000
➤ Mount the ECL-76/ECL-102 charging current distributor and the corresponding relay in
such a way that they remain fixed, dry and well-ventilated, ideally in direct proximity to
the inverter.
➤ Connect the positive terminal of the starter battery to relay connection 30 (Batt. 1) and
the positive terminal of the additional battery to relay connection 87 (Batt. 2).
I
NOTE
Use cables with the correct cable cross section – see circuit diagrams, fig. 1,
page 3 to fig. o, page 27.
➤ Insert an electrical fuse in direct proximity to the starter battery and an electrical fuse
(value see associate circuit diagram) in direct proximity to the supply battery into the
positive lead.
I
NOTE
 The fuse in the positive lead from the charging current distributor to the
battery can only be omitted if the lead is very short and will not come into
contact with metal.
 To connect the inverters in the scope of delivery of the DC kits, please refer
to the documentation accompanying the equipment.
104
Charging current
distributor
ECL-103
ECL-102
ECL-102
ECL-103
ECL-102
ECL-103
ECL-76, ECL-102, ECL-103
Inverter
SinePower MSI1824T
PerfectPower PP2002
SinePower MSI1812T
SinePower MSI1824T
SinePower MSI1812T
SinePower MSI1824T
Cable cross
section
35 mm
minimum
2
25 mm
minimum
2
35 mm
minimum
2
35 mm
minimum
2
35 mm
minimum
2
35 mm
minimum
2
EN

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecl-102Ecl-103

Table of Contents