ASME Code, Section IV C.S.A Design-Certified Complies with ANSI Z21.13/CSA 4.9 Gas-Fired Low Pressure Steam & Hot Water Boilers Installation Date: _______________________ TRIAD Boiler Systems, Inc. 1099 Atlantic Drive, Unit 2 West Chicago, IL 60185 Phone: 630.562.2700 Fax: 630.562.2800 www.triadboiler.com...
Page 2
ATTENTION!!! WATER: ÿ The pH of the system must be between 6.0 and 8.5. Periodically check the pH! ÿ If Glycol is used it must be approved by the chemical manufacturer for aluminum boilers! VENTING: ÿ This boiler is Category IV (condensing positive pressure) and is NOT certified for use with Type B vent! HEAT EXCHANGER: ÿ...
This manual covers installation of the TRIAD Note: Each safety device must be maintained TRIUMPH Series Boilers. The model numbers and checked per the recommended schedule;...
∑ Burn hazard! Pipes, vents, and boiler ∑ Shock hazard! Do not spray water directly on components could be hot. Do not touch piping any electrical components. Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 3...
Do not attempt to adjust firing rate of regulations. the boiler. The firing rate must be adjusted only by factory trained personnel. 2.5.3 Crush Hazards Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 4...
Slip and fall hazard! Do not locate intake or operate boiler with faulty relief valve. exhaust terminations directly above walkway; dripping of condensation can cause icing of the walking surface. Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 5...
American National Standard/CSA Standard ANSI Z21.13/CSA 4.9, latest edition, Gas-Fired Low Pressure Steam and Hot Water Boilers. Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 6...
Boilers may be installed immediately adjacent to each other. However Triad recommends this clearance between each boiler when there is insufficient access at the rear to allow for service and adjustment. No pipes, ducts, etc.
If a horizontal duct is used, 1 These chemicals, when burned, form acids which square inch per 2,000 Btu per hour is required, Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 8...
The exhaust vent termination must be 14 feet above grade when located adjacent to a public walkway. It must Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 9...
Forced air inlet consideration such things as prevailing winds, Reference: ANSI Z223.1 - 2002 eddy zones, building configurations, etc. Triad cannot be responsible for the effects such Sidewall Installations adverse conditions may have on the operation of the boilers. Dimensions listed above or those...
"lock up" type must be provided to reduce the pressure to less than 14" W.C. The roof intake termination must be an unrestrictive type, as shown above. Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 13...
Page 17
1,000 Btu per hour input, i.e., 500,000 Btu per hour requires about 500 cubic feet per hour. (See "Typical Boiler Operating Conditions," Shutoff Section 4.3, for more information.) (on boiler) Meter (not supplied) Gas Piping Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 14...
Some leak test solutions, including soap and water, may cause corrosion. These solutions Contact Triad for minimum flow at other than should be rinsed-off with water after testing. maximum firing rate. Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler...
* Note: Condensate Trap must be piped to drain during the cooling cycle. in accordance with all state and local codes. Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 16...
Installation of external limit controls may be based cleaning or sealing compounds be used in required certain codes certain the boiler system. installations. Review applicable local codes for details. Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 17...
Never flush the hydronic system while the boiler is attached to the system since the debris or corrosion products could accumulate in the boiler and plug the boiler heat exchanger. Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 18...
The red light indicator for Low Water Cut Off will NOT be illuminated. When the water level is normal, the red light stays illuminated. Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 19...
E 12 indicator will remain on as indicated under display . until the display panel is manually reset. Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 20...
Page 24
Setpoint or Checking the airflow switch max boiler temp outdoor Burner off - An internal setpoint has been air mode 68° 182° reached. System is still calling for heat. Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 21...
Page 25
DHW temperature controller specifically mentioned. (supplied by others) closes (Terminal 5 to 8 TB 1, refer to Section 6.1.1), indicating a call for heat from the DHW system. Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 22...
Page 26
The set point of the boiler is controlled by an outdoor temperature sensor. As the outdoor temperature falls the setpoint of the boiler is increased. The boiler modulates to maintain this setpoint. Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 23...
Page 27
1.8 VDC is reached. The firing rate table: increases linearly with voltage until high fire is reached at 10 VDC. The boiler setpoint Parameter 4 remains active to shut down the Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 24...
Combustion measurement instrumentation must be used to adjust the boiler for local conditions Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 25...
Page 29
Remove the flat, round, blue plastic cap from the cover. Using a 3mm (7/64 ) hex wrench, turn the adjustment screw counterclockwise to increase or Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 26...
Page 30
(from lowest to highest fan speed). High fire adjustment Low fire adjustment T-750/T-900/T-1000 Adjusting Low and High Fire Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 27...
T-1000 1,050,000 1,019* 987,000 420** 987,000 8 amps or less Note: The heat exchanger is constructed and stamped for 80 psig maximum operating pressure and/or 200º F maximum temperature. Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 29...
Triad boiler. lockouts on the display panel. Observe any unusual noises or operating conditions and make the necessary corrections. Notify responsible individuals for required corrective action or repair. Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 30...
2. Check gas pressure. (Section 3.12.2.) those listed below. 3. Perform combustion check. Adjust gas flow if a. Check all joints and pipe connections for necessary. (Section 3.12.4.). tightness. Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 31...
E 04 when the a flame stabilization period of 5 seconds at Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 32...
Page 36
High Water Temperature replaced. When the boiler water has exceeded both the operating and high-limit temperature the high limit Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 33...
Note: When an Internal Control Failure occurs, as identified by E-Codes listed above, the failure is internal to the MCBA and replacement of the MCBA is required. A Triad qualified service technician must be called to replace the MCBA device.
The fan is being directed to a higher speed than it is achieving. WARNING If any Manual Reset limit device trips, DO NOT reset without determining and correcting the cause. Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 35...
Technical information is also available at the above number. When ordering replacement parts please have the model number and serial number of your boiler available. Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 36...
Regulated 10V output. COM 1 RS-485 port A. COM 2 RS-485 port B. OUTSIDE TEMP W/ FILTER Thermistor - factory option. OUTSIDE TEMP W/ FILTER Thermistor - factory option. SPARE SPARE Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 38...
& & 6.2 B OILER ARTS 6.2.1 Main Assembly TRIUMPH Series T-750/T-900/T-1000 Mark Description Heat Exchanger Boiler Gas Train Control Pad Location Control Panel Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 40...
& & 6.2.2 Control Panel Mark Description AM-3 Relay Module TRIUMPH Boiler Control Series - MCBA Transformer Low Water Cutoff Control Mounting Plate Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 41...
Low Gas Pressure Switch High Gas Pressure Switch Gas Safety Shut-off/Control Valve Gas Manifold Shut-off Valve Flex Hose with Gas Valve Adaptor Venturi Premix Combustion Blower Burner Hood Burner Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 44...
Subject to the terms and conditions herein and erosion, corrosion, deterioration, abnormal except as provided below with respect to temperatures or the influence of foreign products or parts not manufactured by Triad, matter or energy. Seller warrants to the original owner at the original...
Page 49
Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 46...
8.0 APPENDIX Date Hi/Low- Stack Temp Action Fire Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 47...
Page 51
72 F 31 Difference T1-T2 for modulating back -1 = RMCI Off 32 RMCI address (194- par 1) F or 54 F 33 Setvalue addition for DHW, Parameter 1 Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 48...
Page 52
1X = CH: pump off DHW:normal pump function 2X = CH: normal pump function DHW : 5 second pump delay 3X = CH: pump off DHW : 5 second pump delay Triad Boiler Systems, Inc TRIUMPH Series Hot Water Boiler Page 49...