4.2 Remote Terminal Unit Function

The IPS2 unit includes a Remote Terminal Unite (RTU) function that can be employed to share Start and
Trip information as well as other binary and analogue objects.
Binary objects
There are nine objects for internal signals and the two binary inputs of the IPS2 unit that can be transmitted
on the RS485 System Interface (Single Point) using the IEC 60870-5-101 protocol.
I
> Start
0
I
> Trip
0
I> Start
I> Trip
I
> Arcing
0
Phase break
Binary Input 1
Binary Input 2
High residual current
Analogue objects
Five analogue objects, three phase currents, residual current and fault detected phase, can be transmitted
for supervision/ information purposes. See the Table 1 Explanation of the Protrol IPS2 24 VDC Configuration
settings for more information.
Protocol
The available protocol is:
IEC 60870-5-101
Supported selection of ASDUs:
No
Type ID
<1>
M_SP_NA_1
<2>
M_SP_TA_1
<9>
M_ME_NA_1
<11>
M_ME_NB_1
<13>
M_ME_NC_1
<100>
C_IC_NA_1
<103>
C_CS_NA_1
3
M_ME_NC_1
Protrol AB
Ullevigatan 19
411 40 Göteborg
Standard range
Description
Single-point information
Single-point information with time tag
Measured value, normalized value
Measured value, scaled value
3
Measured value, short floating point number
Interrogation command
Clock synchronization command
R32-IEEE STD 754
7
Ver 1710 Rev 1
Tel: 031- 45 82 00
internet: www.protrol.se
e-mail: info@protrol.se