Protrol IPC4020 User Manual

Fault detector and rtu
Hide thumbs Also See for IPC4020:
Table of Contents

Advertisement

Quick Links

IPC4020/IPC4022
IPC4020 and IPC4022 are fault detectors for over current and earth fault, both with
integrated remote terminal unit functionality.
This user's manual describes the interfaces and management of the devices. This
includes:
▪ Overview
▪ Connection using the service port
▪ Configuration, reset and upgrade
▪ System interface
▪ Detector functions
▪ Event list, Site manager and transient fault recorder
▪ Commissioning and testing
M A N U A L
Fault Detector and RTU

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the IPC4020 and is the answer not in the manual?

Questions and answers

Summary of Contents for Protrol IPC4020

  • Page 1 IPC4020/IPC4022 Fault Detector and RTU IPC4020 and IPC4022 are fault detectors for over current and earth fault, both with integrated remote terminal unit functionality. This user’s manual describes the interfaces and management of the devices. This includes: ▪ Overview ▪ Connection using the service port ▪...
  • Page 2: Table Of Contents

    Binary Outputs – Output 1-8/13/22 ______________________________________________________ 34 7.4.2 Binary Outputs – Detector m ___________________________________________________________ 35 7.4.3 Binary Outputs – PDCIO and PBO ________________________________________________________ 35 Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se 431 49 Mölndal, SWEDEN...
  • Page 3 Detector Settings – Detector n ____________________________________________________ 46 8.5.1 Overcurrent _________________________________________________________________________ 46 8.5.2 Earth Fault, General __________________________________________________________________ 47 8.5.3 Earth Fault Protrol ____________________________________________________________________ 47 8.5.4 Non-Directional Earth Fault ____________________________________________________________ 48 Phase Break ___________________________________________________________________ 49 8.6.1 Auto reclosing – OPTION ______________________________________________________________ 50 Event log and Site Manager ___________________________________________________ 51 Event log –...
  • Page 4: Safety Information

    ESD, by proper earthing of both the device and the personnel performing maintenance. The device should be connected to protective earth at terminal X4.2. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se...
  • Page 5: Abbreviations

    IPC402x-UM-2209-1-2.x.x (en) Abbreviations IPC401x Previous generation fault detectors – IPC4010, -11 and -12 IPC402x IPC4020, IPC4020exp3, IPC4020exp6 or IPC4022 ASDU Application Service Data Unit COMTRADE Common Transient Data Exchange DHCP Dynamic Host Configuration Protocol Earth Fault Electro Static Discharge Overcurrent...
  • Page 6: Overview

    TERM Ethernet Link RJ45 Act. Figure 1. Overview IPC4020 with expansion for two extra detector functions (to the left). The outputs of contacts X8 and X10 are routed to more powerful relays. Binary outputs Binary inputs Option W IPC4022 RS485...
  • Page 7: Front Panel - Hmi

    There are various LED indicators on the front panel for inputs, outputs, communication ports and status purposes. Figure 4. Front panel of IPC4020. Each binary input and output have a LED above its screw terminal and reflects the position of the input/output. Voltage on an input activates the LED. Closed relay output activates the LED.
  • Page 8: Push-Button For Local Acknowledge

    Any outputs that were activated before the restart, return to inactive position unless the conditions for activation are valid. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se...
  • Page 9: Internal Supervision

    There is built-in protection for surge voltages. However, cables for communication that may be subjected to overvoltage must have a primary protection, for example Protrol OVP. As a rule of thumb, one can say that cables that leave the building / station must be supplemented with a primary protection.
  • Page 10: Rs485-Port För Iec 60870-5-101 Master (Option)

    There is built-in protection for surge voltages. However, cables for communication that may be subjected to overvoltage must have a primary protection, for example Protrol OVP. As a rule of thumb, one can say that cables that leave the building / station must be supplemented with a primary protection.
  • Page 11: Service Interface

    Service Interface The built-in web server in IPC402x gives authorized access to all settings, status information, file transfer and event lists, either via Ethernet RJ45 or USB type B. Protrol recommends using Chrome or Firefox web browsers. Connecting using Ethernet The prerequisite for connecting via Ethernet is that the service computer has IP settings that match, i.e.,...
  • Page 12: Connecting Using Usb

    Connecting using USB It is also possible to connect using USB type B. to do so, a separate software, Protrol USB Bridge for Windows 7/10, is needed. This is available on Ensto Protrol's website, together with a link to download necessary drivers.
  • Page 13: Login

    IPC402x-UM-2209-1-2.x.x (en) Login After connecting to the IPC402x device, a login screen is displayed. This includes information about the connected Protrol device and the input field for logging in. Figure 6. The login field of the web server. The following standard users can be selected:...
  • Page 14: Configuration And Settings

    Configuration and Settings Configuration is done using the web interface. See chapter 4 for details on connection to the device and its web interface. The majority of the PDCIO parameters are configured in IPC4020. All settings can be found on the...
  • Page 15 IPC402x-UM-2209-1-2.x.x (en) Reset settings: • IPC402x is delivered either with Protrol's factory defaults or with specific customer settings (delivery defaults) according to agreement between Ensto Protrol and the customer. • Reset to factory / customer settings is made on the System tab.
  • Page 16 - Avoid a reset by pressing the ACN button until the device is in normal operation. ▪ The unit now resets the settings and then restarts. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se 431 49 Mölndal, SWEDEN...
  • Page 17 The administrator can activate/deactivate all accounts except for the admin account. Please observe that the passwords can only to consist of capital letters, lower case letters and the numbers 0-9. Special characters and other national characters are not allowed. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se...
  • Page 18: Device Settings - Unit

    Figure 7. Configuration of NTP. If the disturbance recording files shall be visualized using Protrol-Tool, the station name is not allowed to have spaces. Alternatively, the files must be edited before they can be loaded by the tool. PDCIO is described in details in its own user’s manual [4].
  • Page 19 IPC402x time is used for time stamping of indications, events, and disturbance recordings. The time resolution is 1 ms. When NTP is activated, time synchronisation using IEC 60870-101/-104 is disabled. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se...
  • Page 20: Remote Control Interface

    IPC402x supports the communication protocols IEC 60870-5-101 and IEC 60870-5-104. In addition, there is an option which makes it possible to use IPC4020 as a local -101 Master. With this option it is possible to connect several -101 slaves to IPC4020 and access them in the remote control center.
  • Page 21: Events, Queues And Interrogation

    If the IPC device is acting master for other slaves, it will collect events from all active slaves. Due to speed limitations in the master-slave transmission there will be a delay until all status updates are retransmitted to the control center. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se...
  • Page 22: General Settings - Communication

    Each tab and its settings are described in the following chapter. Range according to common notation (4 bytes in decimal form, 0..255). Observe that the address 0.0.0.0 is not allowed. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se...
  • Page 23 IEC -101 master is an option that needs to be specified upon order. This option is not available if the device is configured for IEC -101 slave and connected to PDCIO. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se...
  • Page 24 2..1 000 This is for information only and cannot be changed by the user. The port is set to 8-E-1, i.e., 8 data bits, even parity and 1 stop bit. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se...
  • Page 25: Iec 60870-5-101 Master - Optional

    (COT) size 7.2.3 IEC 60870-5-101 master - OPTIONAL IPC4020 can be obtained with the option IEC -101-master for IPC402x. With this option, IPC4020 can act local IEC-101 master, which enables the user to connect an additional number of local -101 slaves.
  • Page 26 All objects of all slaves must have unique object addresses. The SCADA system interpretes it as all objects are from the same RTU, i.e., the IPC4020 that acts -101 master. o For the -101 master to be able to resend commands from the remote control center, each upper octet of every object address must be identical to the Common address of the slave.
  • Page 27 This is for information only and cannot be changed by the user. Address 0 means that no slave is expected to be connected. The port is set to 8-E-1, i.e., 8 data bits, even parity and 1 stop bit. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se...
  • Page 28: Binary Inputs - I/O-Addressing - Binary Inputs

    If Double point is used, this means for indication <OFF> that input n is high and input n+1 is low. Input n low and input n+1 high results correspondingly in indication <ON>. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se...
  • Page 29: Binary Inputs - Input 1-16/22/37

    Can only have the type single indication. If the device is an IPC4020exp4 or IPC4020exp6, there are additional physical binary inputs available. Övre oktetten är alltid 0 som fabriksvärde. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se...
  • Page 30: Binary Inputs - Detector M

    - No ▪ Delay - 0 ms For more information regarding detector functions and their specific signals, refer to chapter 8. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se 431 49 Mölndal, SWEDEN e-mail: info@protrol.se...
  • Page 31 0 (Not activated) m = 1, 2 or 3 depending on the detector. Factory settings for the upper octet are always 0. Option: RECL OFF/ON, Auto reclosure inactive / activated. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se...
  • Page 32: Binary Inputs - Iec 60870-5-101/-104 Master

    7.3.3 Binary Inputs – IEC 60870-5-101/-104 Master If the IPC4020 device is configured to be master, see section 7.2.3, an additional subtab is displayed which lists binary inputs that mirror the status of the slaves. Configuration of these supervision objects is made in the same way as for other logical inputs.
  • Page 33: Binary Outputs - I/O-Addressing - Binary Outputs

    For Double command <OFF> this means that output relay n is closed and output relay n+1 is opened. The command <ON> opens output relay n and closes output relay n+1. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se...
  • Page 34: Binary Outputs - Output 1-8/13/22

    Can only have the type single command. If the device is an IPC4020exp4 or IPC4020exp6, there are additional physical binary outputs available. The upper octet has always factory setting 0. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se...
  • Page 35: Binary Outputs - Detector M

    PDC2/PDCIO manual [4] and the settings template for IPC402x [5]. m = 1, 2 or 3 depending on detector number. Logical output 1: RECL OFF/ON, Auto reclosing deactivate / activate (option). Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se 431 49 Mölndal, SWEDEN...
  • Page 36: Analog Inputs (I/O-Addressing - Analog Inputs)

    Lower octets of the address. Decimal. For a detailed description of what the different types provide regarding format, scaling and how the deadband is defined, see descriptions in the following text. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se...
  • Page 37: Analog Inputs - Internal

    Integers corresponding to 0.1 Celsius degrees Scaled [SI*100] Integers corresponding to 0.01 Celsius degrees. Unit temperature Deadband [%] Set as a percentage of 100 degrees Celsius. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se 431 49 Mölndal, SWEDEN e-mail: info@protrol.se...
  • Page 38: Analog Inputs - Detector M

    - 0,1,2,3,12,13,23,123 Can only be of the types: - "Float [SI]" or "Scaled [SI * 1]" m = 1, 2 or 3 depending on the detector. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se 431 49 Mölndal, SWEDEN...
  • Page 39 Faulty phase, as floating point. Fault Phase Scaled [SI*1] Faulty phase, as integer. Deadband Not used. Sent upon detected fault (OC/EF). Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se 431 49 Mölndal, SWEDEN e-mail: info@protrol.se...
  • Page 40: Analog Inputs - Pdcio And Pai

    PT100 High level 2 Alarm level high temperature level 2 1..1 000 °C PT100 Low level Alarm level low temperature -40..+20 °C Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se 431 49 Mölndal, SWEDEN e-mail: info@protrol.se...
  • Page 41: Detector Functions

    IPC402x contains the following detector functions: ▪ Overcurrent - detects short circuit or overload ▪ Earth fault Protrol - patented method for sensitive detection of solid and intermittent earth faults ▪ Earth fault non-directional – residual current based detection ▪...
  • Page 42: Evaluation Of Earth Faults

    See the example below showing a solid earth fault and the corresponding state changes during the evaluation process. Earth Fault -0,5 -1,5 State Time delay Figure 8. States during the evaluation of a solid earth fault. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se 431 49 Mölndal, SWEDEN e-mail: info@protrol.se...
  • Page 43: Evaluation Of Transient And Arcing Faults

    State Reignition time Figure 9. Earth fault with arcing characteristics – after the second ”START” the detector progresses immediately to state TRIP. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se 431 49 Mölndal, SWEDEN e-mail: info@protrol.se...
  • Page 44: Settings - Common

    Test qualifier Parameter for test 0..4294967295 The unit can be seconds, minutes, or hours. Maximum time is 48 h. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se 431 49 Mölndal, SWEDEN e-mail: info@protrol.se...
  • Page 45: Settings - I/O Settings

    Dx Fault phase See section 7.5.2 Does not affect the amplitude of the input signal. Ratio Primary/Secondary current. Also applies to display of other currents. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se 431 49 Mölndal, SWEDEN...
  • Page 46: Detector Settings - Detector N

    Where TMS is a parameter of own choice and k and α are defined by the choice of inverse curve according to the following table. �� Curve type Standard inverse 0,14 0,02 Very inverse 13,5 Extremely inverse Long inverse Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se 431 49 Mölndal, SWEDEN e-mail: info@protrol.se...
  • Page 47: Earth Fault, General

    IEC 60870-5-101/-104 8.5.2 Earth Fault, General The IPC402x devices have two types of earth fault detectors; Protrol's patented method, and a complementary non-directional earth fault function that can be employed when switching onto faults. The non-directional function can also be used to detect fault connection, that a phase is missing or that one phase is connected with the wrong polarity.
  • Page 48: Non-Directional Earth Fault

    IPC402x-UM-2209-1-2.x.x (en) Settings – Earth Fault Protrol: Parameter Description Range Factory value Unit Enable Protrol earth fault function activated Yes or No Level Earth fault current level 0.1..100.0 Delay Time delay between START and TRIP 0..10 000 Event delay Time delay for TRIP interlocked with input 0..25 000...
  • Page 49: Phase Break

    Phase breaks do not result in a start signal. Note that if a phase is missing but the two remaining have a phase difference of 120 degrees, there will be no phase break. Such a fault is indicated by a non- directional earth fault. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se...
  • Page 50: Auto Reclosing - Option

    Auto reclosing (AR - RECL) means that a delayed switch-on is ordered after an initial TRIP has been issued by any of the Overcurrent or Earth fault Protrol protection functions. This option can be acquired for one bay only, or for all three bays.
  • Page 51: Event Log And Site Manager

    12, 13, 23 or 123, which show which phases are involved. Figure 11. Event log. At the bottom there is a button to generate a dummy event for test purposes. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se 431 49 Mölndal, SWEDEN...
  • Page 52: Site Manager

    Status tab. Figure 12. Site manager for IPC4020. Please note that Site manager will adjust to the type of IPC402x device that is used and on what options that are activated. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se...
  • Page 53 Description Status Green/Red indicator which indicates battery fault. Test in progress Yellow indicator which indicates that battery test is in progress. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se 431 49 Mölndal, SWEDEN e-mail: info@protrol.se...
  • Page 54 There is a checkbox that enables activation of the outputs via the web interface. It is checked as long as you are logged in. To activate an output, simply click on the LED symbol. It then lights up and closes the relay output for 3 seconds. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se...
  • Page 55: Transient Fault Recorders - Tfr

    IPC402x is always ready to register a new disturbance record. The disturbance records are stored in non-volatile memory. It is possible to erase individual or all disturbance records manually, i. e., after commissioning and/or testing. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se...
  • Page 56 TFR data is saved in the same basic format as for IPC401x. Data can thus be displayed by the same tool, see [3]. In addition, there is a modern tool for viewing Protrols disturbance recordings, Protrol TFR Plotter. For conversion to COMTRADE there is a special tool, available on Protrols web page. Also, files from IPC401x can be converted.
  • Page 57 IPC402x-UM-2209-1-2.x.x (en) Figure 15. TFR log file – data at the end of the file. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se 431 49 Mölndal, SWEDEN e-mail: info@protrol.se...
  • Page 58 When the file is selected, the configuration file and data file are displayed to the right. Change any input, scaling, labels, etc., if necessary. • Convert by clicking Create COMTRADE files. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se 431 49 Mölndal, SWEDEN...
  • Page 59: Upgrade Of Firmware

    Start PDC SW upgrade. Please observe that updating of PDCIO firmware using IPC402x takes longer time than if it is done locally on the PDCIO device. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se 431 49 Mölndal, SWEDEN...
  • Page 60: Checklist For Commissioning And Testing

    0 is safe, the connection is correct. c. Create a disturbance file and check that the phase sequence is the expected one. d. Measurement values are displayed correctly in the remote control center. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se...
  • Page 61 A new column, Remote signal test, is then added to the object settings for binary inputs on the tabs Binary Inputs/Input 1-16 Binary Inputs/Detector Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se 431 49 Mölndal, SWEDEN...
  • Page 62 Deactivate remote signal test. The device spontaneously returns to normal state 30 minutes after activation. Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se...
  • Page 63: References

    IPC402x-UM-2209-1-2.x.x (en) 13 References IPC4020-datablad-xxyy-en.pdf IPC4022-datablad-xxyy-en.pdf IPC4010-12_manual_xxyy_en.pdf PDC2/PDCIO_manual_xxyy_se.pdf IPC4020-LIST-01_IPC402x_IEC -101-104_Settings_Template_Rev._x.xlsx Ensto Protrol AB, Alfagatan 3, SE-431 49 Mölndal, SWEDEN Phone: +46 31 45 82 00. E-mail: info@protrol.se www.protrol.se Ensto Protrol AB Phone: +46 31 45 82 00 Alfagatan 3 internet: www.protrol.se 431 49 Mölndal, SWEDEN...

This manual is also suitable for:

Ipc4022

Table of Contents