Specifications - BAPI H200 Installation And Operating Instructions

Duct and outside air humidity 4 to 20ma or 0 to 5v humidity output with optional temperature sensor
Table of Contents

Advertisement

4 to 20mA or 0 to 5V Humidity Output with Optional Temperature Sensor
9938_ins_hum_temp_duct_out_5_20

Specifications

Power:
10 to 35 VDC
12 to 27 VAC
Power Consumption:
22 mA max. DC
0.53 VA max. AC
Sensor:
Humidity
RH Accuracy
Drift
Response time
RH Linearity
RH Hysteresis
Opt. Temp.
Filter:
Calibrated Accuracy:
RH 2%
RH 3%
Thermistor
RTD
Output:
Humidity
Opt. Temp.
Humidity Output Impedance:
Current
Voltage
Probe Length:
Duct
Outside Air
Dimensions:
Weatherproof (WP)
Weather Tight (EU)
BAPI-Box (BB)
BAPI-Box 2 (BB2)
Termination:
Crimp
Wire Nut
Enclosure Material:
Weatherproof (WP)
Weather Tight (EU)
BAPI-Boxes (BB, BB2) Polycarbonate, UV resistant
Enclosures Ratings:
Weatherproof (WP)
Weather Tight (EU)
BAPI-Boxes (BB, BB2) NEMA-4, IP66, UL94V-0
Environmental Operation Range: -40º to 158ºF (-40º to 70ºC) • 0% to 100% RH
Approvals:
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:sales@bapihvac.com • Web:www.bapihvac.com
For 0 to 5 VDC or 4 to 20 mA Humidity Outputs
For 0 to 5 VDC Humidity Output
For 0 to 5 VDC or 4 to 20 mA Humidity Outputs
For 0 to 5 VDC Humidity Output
Factory corrected @17 RH points (10 to 90% RH)
Capacitive Polymer
±2% @ 73°F (23°C) from 10 to 90%
0.5% per year
< 5 seconds in moving air
Negligible, factory corrected linear from 10 to 90%
Factory corrected to <1%
Passive RTD or Thermistor
80 micron sintered stainless steel filter
Calibration @17 RH points, (10% to 90%)
2% from 10 to 90% @ 73°F (23°C), Non-condensing
3% from 10 to 95% @ 73°F (23°C), Non-condensing
±0.36ºF (0.2ºC) from 32 to 158ºF (0 to 70ºC) - High accuracy units are available
±0.55ºF (0.31ºC) @ 32ºF (0ºC) - High accuracy units are available
Selectable via wiring detail
0 to 5VDC or 4 to 20mA at 0 to 100% RH
Resistance RTD or Thermistor
700W@ 24VDC, Voltage drop is 10VDC
(Supply Voltage DC – Transmitter voltage drop 10VDC) / 0.02 Amps = Max load Impedance
10KW
5.3" (13.5cm) Duct Insertion, 1" diameter
2.4" (6.1cm) Below Enclosure, 1" diameter
W x H x D
2.75" x 4.5" x 2.2", (70 x 114 x 55 mm)
4.1"x 3.8" x 2.1", (105 x 97 x 54 mm)
4.15" x 5" x 2.5", (105.4 x 127 x 63.5mm)
4.9" x 2.8" x 2.35", (124.8 x 71.6 x 59.7mm)
Open wire
18 to 26 AWG with Sealant Filled Crimp Connector (BA/SFC1000-x00)
26 to 16 AWG with Sealant Filled Wire Nut (BA/SFC2000-x00)
Cast Aluminum
ABS plastic, UV resistant
NEMA-3R
IP66, UL94V-0
RoHs
Specifications subject to change without notice.
Duct and Outside Air Humidity (H200-H300)
Installation and Operating Instructions
rev. 02/15/18
3 of 4