3.1 SHOUTDOWNS AND LOCK-OUTS

Blockage
If a blockage condition continues to exist after several start up attempts, the boiler will switch into lock-out (fault) mode. The boiler
can only start operating again once the causes of the lock-out have been rectified and after pressing the
Lock-out Mode
A temporary lock-out caused by an unusual occurrence in the boiler's
operation. e.g. The display gives a code of a blocked flue (code St9). The
boiler control will try to re-start several times. The boiler will start up again
after the blocking conditions have been eliminated. The shutdown codes can
be read out as follows:
• Press the two buttons
• Confirm by pressing
shutdown code "9".
• Press the (+) button. "Su" appears on the display.
NOTICE
The boiler starts up again automatically when the reason for the blocking has been removed.
Shutdown
Description
code
Su:0
Parameter error
Maximum supply temperature
Su:1
exceeded
Maximum increase of the
Su:2
flow temperature has been
exceeded
Max difference between
Su:7
Tsupply / return exceeded
Su:8
No release signal
Line and neutral of
Su:9
power supply are mixed
up
Su:10
Shutdown input is open
Shutdown input active or frost
Su:11
protection active
Communication error with the
Su:13
SCU PCB
Su:15
Gas pressure too low
7703476.01 (1-03/18)
simultaneously.
button. "St" is displayed, alternating with the
Probable causes
Parameter error on the PSU PCB
Non-existent or insufficient circulation
Non-existent or insufficient circulation
Sensor error
Non-existent or insufficient circulation
/ sensor error
External cause
Parameter error
Bad connection
Power supply incorrectly wired
Floating or 2 phase network
External cause
Parameter error
Bad connection
External cause
Parameter error
Bad connection
Bad connection with BUS
SCU PCB not installed in the boiler
Non-existent or insufficient gas
pressure.
Incorrect setting of the Gps gas
pressure switch on the SCU PCB
Solution
Reset of and dU
Restore parameters with Recom
Check the water pressure
Contact a qualified Service Technician
Check the water pressure
Contact a qualified Service Technician
Contact a qualified Service Technician
Contact a qualified Service Technician
Contact a qualified Service Technician
Contact a qualified Service Technician