Honeywell Hydronic Panels are capable of managing boilers with DHW priority. The panel features two isolated end
switches labeled Boiler and End Switch for TT outputs to the boiler. Two slide switches are available to provide simple
programing of the end switches to meet the desired application. See the operational matrix below detailing functionality
of the switches.
Additionally, this panel features a LOW LIMIT input which must be closed for pumps to be activated. This input comes
with a factory installed jumper for cold start boiler operation when the controlling Aquastat has a HIGH LIMIT only. If the
installed boiler requires warm up time then this jumper should be removed and wired to the boiler.
NO PRIORITY ZONE OR PRIORITY END SWITCH
T-STAT
CALL
PRIORITY ZONE, NO PRIORITY END SWITCH
DEACTIVATE ALL
OTHER ZONES
YES
IS THIS THE
T-STAT
PRIORITY ZONE?
CALL
NO
WAIT FOR
IS PRIORITY
PRIORITY ZONE
ACTIVE?
YES
TO SATISFY
PRIORITY ZONE, PRIORITY END SWITCH
DEACTIVATE ALL
OTHER ZONES
YES
IS THIS THE
T-STAT
CALL
PRIORITY ZONE?
NO
WAIT FOR
IS PRIORITY
PRIORITY ZONE
ACTIVE?
TO SATISFY
YES
BOILER RELAY=ON
CLOSED
END SWITCH=ON
ZONE PUMP=ON
STATUS OF
ZR/ZC
BOILER RELAY=ON
OPEN
END SWITCH=ON
ZONE PUMP=OFF
Fig. 11.
CLOSED
STATUS OF
ZR/ZC
OPEN
NO
Fig. 12.
CLOSED
STATUS OF
ZR/ZC
BOILER RELAY = ON
END SWITCH = ON
OPEN
ZONE PUMP = OFF
CLOSED
STATUS OF
ZR/ZC
NO
BOILER RELAY = ON
OPEN
END SWITCH = OFF
ZONE PUMP = OFF
Fig. 13.
5
M37144
BOILER RELAY = ON
END SWITCH = ON
ZONE PUMP = ON
BOILER RELAY = ON
END SWITCH = ON
ZONE PUMP = OFF
M37145
BOILER RELAY = ON
END SWITCH = ON
ZONE PUMP = ON
BOILER RELAY = ON
END SWITCH = OFF
ZONE PUMP = ON
M37146
HPSR10*
33-00331EF—05