LG LB-H1860 Series Installation Instructions Manual page 23

Ceiling duct type air conditioners
Table of Contents

Advertisement

[Table. 1]
Static Pressure(mmAq)
Model Name Step(Hi/Med/Lo)
16.5 CMM
LB-H1860
14.5 CMM
**
13 CMM
18 CMM
LB-H2460
16.5 CMM
**
14 CMM
32 CMM
LB-G3660
**
29 CMM
LB-G3680
**
26.5 CMM
Note: 1. Be sure to set the value refering table 1. Unexpected set value will cause
mal-function.
2. Table 1 is based at 230V. According to the fluctuation of voltage, air flow rate
varies.
[Table. 2]
Static Pressure(mm Aq)
Model Name
LB-E4880
**
LB-E6080
**
(Standard)
LB-E6080
**
(Low Static)
1) The above table shows the correlation of External Static Pressure & AIR FLOW.
2) Duct work must be designed within the range of
3) Change the wiring diagram referring to page 20 of manual on condition fo High/Low Static
Pressure.
4) If duct work is designed under
Pressure applying air damper.
0
2
235
230
245
238
254
252
230
215
240
235
255
252
235
230
247
245
254
253
0
2
Step
CMM
CMM
High
48.5
46.5
Med
43
41.5
Low
39
37.5
High
58.5
57
Med
54
52.5
Low
49
47.5
High
54
52.5
Med
49
47.5
Low
44
42.5
External Static Pressure, adjust the External Static
23
4
6
Setting Value
225
215
235
230
248
245
210
50
230
210
250
245
230
150
245
235
253
250
4
6
8
CMM
CMM
CMM
45
43.5
42
39.5
38
36.5
36
34.5
33
55
53
51
51
49
47
46
44
42
51
49
47
46
44
42
41
39
37
on installing the unit.
8
10
180
215
240
-
-
-
1
230
248
10
15
CMM
CMM
40
40
35
35
31
30
49
44
45
39
40
34
45
40
35