WARNINGS AND CAUTIONS:
• TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER AT CIRCUIT BREAKER OR FUSE AND TEST THAT THE POWER IS OFF BEFORE WIRING!
• To be installed and/or used in accordance with electrical codes and regulations.
• To avoid overheating and possible damage to this device and other equipment, DO NOT install to control a receptacle.
• Use only one IPS15 or IPV15 sensor in a multi-location circuit with up to 9 VP0SR-10 coordinating Vizia+™ switch remotes without LEDs or up to
4 IPV0R-1L sensor remotes or 4 VP0SR-1L Vizia+™ matching remotes with LEDs.
TOOLS NEEDED TO INSTALL YOUR DEVICE
Slotted/Phillips Screwdriver
Electrical Tape
Pencil
Cutters
CHANGING THE COLOR OF YOUR DEVICE
Your device may include color options. To change color of the face
proceed as follows:
Push down
tabs per
diagram,
one at a time
and rotate
forward to
release
INSTALLING YOUR REMOTE
√
NOTE: Use check boxes
when Steps are completed.
WARNING:
Step 1
TO AVOID FIRE, SHOCK, OR DEATH;
TURN OFF POWER at circuit breaker or fuse and test
that power is off before wiring!
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Identifying your wiring application
Step 2
(most common) -
NOTE: If the wiring in the wall box
does not resemble any of these configurations, consult an
electrician.
2
1
3
1
2
3
4
5
4
5
6
3-Way
4-Way
1. Line or Load (See important
1. First Traveler – note color
instruction below)
2. Second Traveler – tagged
2. Neutral
3. Neutral
3. Ground
4. Ground
4. First Traveler – note color
5. Third Traveler – note color
5. Second Traveler – note color
6. Fourth Traveler – tagged
NOTE: For matching remote
NOTE: For matching remote
w/LEDs installation, the First
w/LEDs installation, the First
Traveler becomes Line Hot.
Traveler becomes Line Hot.
Decora
IMPORTANT:
For 3-Way applications, note that one of the screw terminals from
the old switch being removed will usually be a different color (Black) or
Pliers
labeled Common. Tag that wire with electrical tape and identify as the
Ruler
common (Line or Load) in both the sensor wall box and remote wall box.
For 4-Way applications, note that the old switch being removed will
have 4 screws plus a ground screw. Tag the two same color insulated
wires with electrical tape.
Preparing and connecting wires:
Step 3
This remote can be wired using side wire terminal
Attach new
screws or through backwire openings. Choose
face by
appropriate wire stripping specifications accordingly.
inserting
bottom hinge
tabs, then
pivot and
5/8"
snap the
(1.6 cm)
color kit to
attach
Cut
(if necessary)
Side Wire
Back Wire
Side wire terminals
Back wire openings
accept #14-12 AWG
use #14-12 AWG solid
solid copper wire only.
copper wire only.
• Make sure that the ends of the wires from the wall box are
straight (cut if necessary).
• Remove insulation from each wire in the wall box as shown.
3-Way Wiring of Sensor Remote with
Step 4a
IPS15/IPV15 Sensor:
IPV0R Remote
IPS15, IPV15 Sensor
Additional
Terminal
Neutral Wire
Screw marked
Terminal
Terminal
White (WH)
Screw
Screw
marked
marked
Black (BK)
2
Black (BK)
BK
WH
BK
1
Ground
Ground
Terminal
Terminal
4
Screw
Screw
(Green)
(Green)
3
Terminal
5
Terminal
Screw
Screw
marked
marked
3-Way
3-Way
IPV0R Remote
IPS15, IPV15 Sensor
WH
BK
WH
BK
Hot (Black)
Green
Green
Ground
Ground
Line
3-Way
RD
3-Way
120VAC, 60Hz
Neutral (White)
3-Way or More Applications (Multi-Location)
®
Manual-ON Occupancy Sensor Remote
California Title 24 2008 Compliant
Cat. No. IPV0R - 120VAC, 60Hz
For use with Cat. No. IPS15 and IPV15 Sensors
INSTALLATION INSTRUCTIONS
WARNINGS AND CAUTIONS:
• If you are not sure about any part of these instructions, consult an electrician.
• The Manual-On Occupancy Sensor Remote is intended to replace additional 3-Way and 4-Way switches when used with the IPS15 and
IPV15 Occupancy Sensors.
• Do not touch the surface of the lens. Clean outer surface gently with damp cloth only. DO NOT use soaps or cleaning liquids.
• Use this device WITH COPPER OR COPPER CLAD WIRE ONLY.
NOTE: The Occupancy Sensor must be installed in a wall box that has a Load
connection. The sensor remote must be installed in a wall box with a Line Hot
connection and a Neutral connection. A Neutral wire to the sensor remote needs
to be added as shown. If you are unsure about any part of these instructions,
consult an electrician. NOTE: Maximum wire length from sensor to all installed
remotes cannot exceed 300 ft (90 m).
WIRING SENSOR REMOTE OR VIZIA MATCHING SWITCH
REMOTE (3-Way wall box with Line Hot connection):
Connect wires per WIRING DIAGRAM as follows:
NOTE: Use backwire connection when connecting two wires to one screw terminal.
• Green or bare copper wire in wall box to Green terminal screw on Sensor
Remote or Vizia Matching Switch Remote.
• Line Hot (common) wall box wire identified (tagged) when removing old
switch and First Traveler wall box wire to Sensor Remote terminal screw or
Strip Gage
Vizia Matching Switch Remote terminal screw marked "BK".
(measure bare wire
• Second Traveler wall box wire from other 3-Way wall box to Sensor Remote
here or use gage on
terminal screw marked "3-Way" or Vizia Matching Switch Remote terminal
back of the remote)
screw marked "YL/RD" (note wire colors). This traveler from the remotes
must go to the terminal screw marked "3-Way" on the sensor.
• Neutral wall box wire to remote terminal screw marked "WH".
WIRING SENSOR (3-Way wall box with Load connection):
Connect wires per WIRING DIAGRAM as follows:
NOTE: Use backwire connection when connecting two wires to one screw terminal.
• Green or bare copper wire in wall box to Green terminal screw on sensor.
BK
• Load wall box wire identified (tagged) when removing old switch to terminal
screw marked "RD" on sensor.
• First Traveler Line Hot to terminal screw marked "BK" on sensor.
• Remove Red insulating label from terminal screw marked "3-Way" on sensor.
• Second Traveler wall box wire (note color as above) to terminal screw
marked "3-Way" on sensor. This traveler must go to the terminal screw on
the Sensor Remote marked "3-Way" or to the terminal screw on the Vizia
matching switch remote marked "YL/RD".
• Neutral wall box wire to terminal screw marked "WH" on sensor.
Terminal
Screw marked
4-Way Wiring of Sensor Remote with IPS15/
Step 4b
White (WH)
4
IPV15 Sensor:
WH
2
3
IPV0R Remote
VP0SR-1L Remote
1
(3-Way Wall box from Step 2)
(4-Way Box from Step 2)
5
Additional
Terminal
Neutral Wire
Screw marked
White (WH)
Terminal
Terminal
Terminal
Screw marked
Screw
Screw
2
Red (RD)
marked
marked
Black (BK)
WH
Black (BK)
BK
1
Ground
Ground
Terminal
Terminal
4
Screw
Screw
(Green)
(Green)
3
Terminal
Terminal
5
Screw
Screw
marked
marked
Yellow/Red
3-Way
(YL/RD)
Black
LOAD
White
Hot (Black)
Line
120VAC, 60Hz
Neutral (White)
NOTE: The Occupancy Sensor must be installed in a wall box that has a Load
connection. The sensor remote must be installed in a wall box with a Line Hot
connection and a Neutral connection. A Neutral wire to the sensor remote needs to
be added as shown. If you are unsure about any part of these instructions, consult
an electrician. NOTE: Maximum wire length from sensor to all installed remotes
cannot exceed 300 ft (90 m).
WIRING SENSOR REMOTE OR VIZIA MATCHING SWITCH REMOTE
(3-Way wall box with Line Hot connection):
Connect wires per WIRING DIAGRAM as follows:
NOTE: Use backwire connection when connecting two wires to one screw terminal.
• Green or bare copper wire in wall box to Green terminal screw on Sensor
Remote or Vizia Matching Switch Remote.
• Line Hot (common) wall box wire identified (tagged) when removing old switch
and First Traveler wall box wire to Sensor Remote terminal screw or Vizia
Matching Switch Remote terminal screw marked "BK".
• Second Traveler wall box wire from 4-way wall box to Sensor Remote terminal
screw marked "3-Way" or Vizia Matching Switch Remote terminal screw marked
"YL/RD" (note wire colors). This traveler from the remotes must go to the
terminal screw marked "3-Way" on the sensor.
• Neutral wall box wire to remote terminal screw marked "WH".
WIRING SENSOR REMOTE OR VIZIA MATCHING SWITCH REMOTE
(4-Way wall box):
Connect wires per WIRING DIAGRAM as follows:
NOTE: Use backwire connection when connecting two wires to one screw terminal.
• Green or bare copper wire in wall box to Green terminal screw on Sensor
Remote or Vizia Matching Switch Remote.
• First Traveler and Third Traveler wall box wires to Sensor Remote or Vizia
Matching Switch Remote terminal screw marked "BK".
• Second Traveler (tagged) and Fourth Traveler (tagged) wall box wires to Sensor
Remote terminal screw marked "3-Way" or Vizia Matching Switch Remote
IPS15, IPV15 Sensor
terminal screw marked "YL/RD" (note wire colors). This traveler from the
(3-Way Wall Box from Step 2)
remotes must go to the terminal screw marked "3-Way" on the sensor.
Terminal
Terminal
Additional
Screw marked
Screw marked
Neutral Wire
• Neutral wall box wire to remote terminal screw marked "WH".
White (WH)
White (WH)
Terminal
4
Screw
WIRING SENSOR (3-Way wall box with Load connection):
marked
3
Black (BK)
WH
1
BK
Connect wires per WIRING DIAGRAM as follows:
2
Ground
5
Terminal
NOTE: Use backwire connection when connecting two wires to one screw terminal.
Screw
4
(Green)
3
• Green or bare copper wire in wall box to Green terminal screw on sensor.
1
Terminal
• Load wall box wire identified (tagged) when removing old switch to terminal
Screw
5
6
marked
screw marked "RD" on sensor.
3-Way
Terminal
• First Traveler Line Hot to terminal screw marked "BK" on sensor.
Screw marked
Red (RD)
• Remove Red insulating label from terminal screw marked "3-Way" on sensor.
• Second Traveler wall box wire (note color as above) to terminal screw marked
"3-Way" on sensor. This traveler must go to the terminal screw on the Sensor
Remote marked "3-Way" or to the terminal screw on the Vizia matching switch
remote marked "YL/RD".
• Neutral wall box wire to terminal screw marked "WH" on sensor.
DI-000-IPV0R-02B
IPV0R Remote
VP0SR-1L Remote
IPS15, IPV15 Sensor
BK
BK
WH
BK
WH
WH
Green
Green
Green
Ground
Ground
Ground
Black
RD
3-Way
3-Way
YL/RD
LOAD
White