5. Shipping

5.1 Check condition upon delivery

1. Check the contents of each package for damage upon delivery.
2. In the case of transport damage estimate the extent, document the
damage and notify Honeywell immediately in writing.

5.2 Transportation

Danger
The system falls off of the pallet
Danger of being crushed by system!
Position the system vertically during transport
Never get the system tangled in electrical lines.
Observe the local safety regulations.
Observe the weight and mass centre.
Only use appropriate and authorised means of transportation,
for example fork lift or hand lift.
Warning
Installation on non-level and non-structural installation sites
Personal and property damage!
Ensure sufficient compressive strength according to class C12/
15 for concrete in the exposition class X0 according to EN 206-
1.
The installation site has to be solid, level and horizontal.
Observe the weight information.
The compact booster unit is attached to wooden rails and wrapped in
foil for transport and temporary storage. All connection interfaces have
protective lids.
The system is on a small wooden pallet under the telescope box. Accesso-
ries are packed in the same box - see the box label. Two carrier handles for
transport are in the box.
1. To unpack, cut the packaging straps.
2. Take the accessories and the extra padding out of the box.
3. Lift the box upwards.
- The system stands alone on the wooden pallet.
4. Check the contents of the package for completeness.
5. Check the system for transport damage.
6. Select the appropriate means of transport.
7. Transporting the system to the installation site.
EN1H-1377GE23 R1114 - Translation of original
GB

6. Assembly

6.1 General safety instructions

Danger
Danger of injury from electric voltage.
High shock currents and burns from direct and indirect contact with
live parts.
Turn off the power supply before assembling the compact
booster unit and secure it from being turned on.
Faulty mains connection
Damage to the electricity network, short circuit!
The electrical system must conform with the installation regula-
tions according to VDE 100 (i.e. grounded electrical sockets).
The electrical network must be equipped with a residual current
device for max. 30mA.
Non- or erroneously-connected cables
Malfunctions, which endanger the safety of operating personnel.
Work on electrical equipment may only be performed by specia-
list electric technicians.
Improperly connected wiring and lines (e.g. too small bend radius)
Smouldering and fires from cables.
Work on electrical equipment may only be performed by specia-
list electric technicians.
Live cable ends and components
Make sure the protective earth system is connected throughout.
Warning
The compact booster unit is not designed for operation outside.
Temperature, light and moisture influences can lead to
malfunctions and damage to devices.
Do not use the compact booster unit outside.
Danger through improper installation
Personal and property damage!
Performance of tasks only by qualified personnel (see section
1.10.1.1).
Caution
Damaged or improperly installed compact booster unit.
Malfunctions
Do not damage the compact booster unit and only install it if it
is clean and fully functional.
Install the compact booster unit according to the described
instructions.
Install free of voltage and of bending moments.
Connecting cable overly bent
Defective system due to improper load on the system
Reduction of service life!
Install connecting cable with zero potential. No load is allowed
to be put on either the connections or the system.
Drinking water backfeed of max. 4bar exceeded
Defective system due to improper load
Install pressure reducing valve ahead of the system to ensure
that not more than 4bar prepressure is fed from the drinking
water network.

6.2 Installation according to EN1717

Accomodate the compact booster unit in a technical centre or in a frost-free,
well ventilated, lockable room that is not used for anything else. Hazardous
gases should never enter the installation room. A sufficiently dimensioned
dewatering connection (drain connection or similar) is required (observe
EN 12056).
Usable volume tank
13 l
Table 6: Usable volume/dewatering capacity
Do not operate the compact booster unit near living rooms and
bedrooms.
9
Dewatering capacity
5,4 m
3
/h