MTS-3000 SERIES MODULAR TEST SYSTEM OPERATION AND REFERENCE MANUAL First Edition March 2001 Manta Test Systems Incorporated 4060B Sladeview Crescent, Unit #1 Mississauga, Ontario, L5L 5Y5, Canada Tel: +1(905) 828-6469 Fax: +1(905) 828-6850 e-mail: support@mantatest.com Internet: http://www.mantatest.com...
Page 2
MTS-3000 Modular Test System Operation and Reference Manual All rights reserved by Manta Test Systems Incorporated. No part of this publication may be reproduced or distributed in any form or by any means without the permission of Manta Test Systems Incorporated.
DC Current: Current Source option ............2-2 2.2.9 MTS-3010 Digital I/O Module (Optional) ..........2-2 METERING....................2-3 2.3.1 Time measurement...................2-3 2.3.2 Frequency measurement ................2-3 STATIC/DYNAMIC TESTING CAPABILITIES........2-3 OPTIONS.......................2-3 2.5.1 System Options ..................2-3 2.5.2 AC Voltage Module Options ..............2-3 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
Page 4
3.3.9.2 OPERATE TIME TEST..............3-23 3.3.9.3 HARMONIC RESTRAINT TEST..........3-23 3.3.9.4 INSTANTANEOUS TEST.............3-24 3.3.9.5 TARGET TEST................3-24 3.3.10 Differential Relay - Independent Coil Type ..........3-25 3.3.10.1 SLOPE TEST...................3-25 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
Page 5
Section 4 Detailed Operation FAULT STATES ...................4-1 4.1.1 Prefault State....................4-1 4.1.2 Fault State ....................4-1 4.1.3 Postfault State ..................4-1 CHARACTERISTICS OF FAULT STATES ..........4-1 OPERATION MODE - STATIC VS. DYNAMIC ........4-2 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
Page 6
AC Current Range (ACI Range) ..............5-9 5.2.9 Reclose.....................5-9 5.2.10 Fault Incidence Angle (FIA) ..............5-10 5.2.11 Maximum Fault Duration (Max Flt Dur) ..........5-10 5.2.12 Display Options ..................5-10 Φ 5.2.12.1 DEFAULT DISPLAY (Hz & ) ...........5-10 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
Page 7
Breaker Open (BKR OPEN: 52B)...........5-21 5.7.5.4 PERMISSIVE..................5-22 5.7.5.5 UNBLOCK..................5-22 5.7.5.6 Off....................5-22 5.7.6 Output Delay (O/P Delay) ..............5-22 5.7.7 Version .....................5-22 Section 6 QuickTest ADVANTAGES OF QUICKTEST...............6-1 QUICKTEST ALGORITHMS ..............6-1 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
Page 8
Fault State Control ...................7-3 7.2.3 External Data Mode .................7-5 7.2.4 Voltage Programming................7-5 7.2.4.1 COMMANDS.................7-5 7.2.4.2 EXAMPLES...................7-6 7.2.5 Current Control ..................7-6 7.2.6 Phase Control ...................7-7 7.2.6.1 COMMANDS.................7-7 viii MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
Page 9
Defining & Displaying Theoretical Relay Characteristics ......B-9 POWER WINDOW ..................B-10 SPECIAL NOTES ..................B-10 APPENDIX C ALPHABETICAL RS-232 COMMAND SUMMARY USER ERRORS - INAPPROPRIATE BUTTON PRESSING .....C-1 HARDWARE ALARMS................C-2 SOFTWARE ALARMS ................C-4 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
Page 10
TABLE OF CONTENTS GLOSSARY ....................... D-1 INDEX .........................E-1 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
Page 11
TEST CONNECTIONS FOR SCR OUTPUT TYPE RELAY .....4-6 DIFFERENTIAL RELAY HARMONIC RESTRAINT TESTING .....4-7 ROOT MENU....................5-1 MENU TREE SETTINGS................5-4 PARALLEL MENU ..................5-7 PARALLEL CONNECTION ................5-7 MENU TREE: PREFERENCES ..............5-14 MENU TREE: INDEX/OTHER..............5-17 MENU TREE: DIGITAL I/O ................5-19 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
Page 12
TABLE OF CONTENTS MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
• Compact and rugged. 1.2 GENERAL DESCRIPTION The Manta MTS-3000 is a flexible modular test system, geared particularly towards protective relay testing, but configurable for numerous other applications requiring AC and/or DC voltage and/or current sources. Systems can be as simple as a single phase AC current source, or as complex as a full three phase AC voltage and current source with DC voltage and current, multi-channel digital input operation sensing and digital output control, and accurate timing measurement capability.
INTRODUCTION - Section 1 An MTS-3000 System consists of a Control Module (CM), and one or more AC output modules. These modules connect together to form a stack, with the control module at the top. An AC Current Module (ACI), an AC Voltage Module (ACV), or an AC Voltage/Current Module (ACV/ I) may be easily added or removed from a stack to configure the system to your needs.
INTRODUCTION - Section 1 1.4.6 Dynamic Relay Testing Dynamic relay testing refers to testing of relays using instantaneous steps and/or ramping of voltage and current inputs. To closely simulate the conditions the device sees in service, the voltages and currents are typically stepped from a nominal, prefault level, to a predetermined fault level.
INTRODUCTION - Section 1 The instrument case must always be effectively grounded. The rear panel grounding stud of the Control Module, CM, must be connected by a minimum 12-gauge wire to a known secure ground. This ground is in addition to the power cord ground. All leads and connectors must be in good condition and rated for the voltage and current carrying requirements.
SPECIFICATIONS - Section 2 SPECIFICATIONS NOTE: All specifications are subject to change. All AC quantities are RMS values, except as otherwise noted. Power outputs are specified for nominal 120VAC/60Hz or 240VAC/50Hz power input, and 25°C ambient operating temperature. For some configurations, the 15A / 7.5A rating may be exceeded if all outputs are at full power.
SPECIFICATIONS - Section 2 2.2.3 AC Voltage and Current: MTS-3030 AC Voltage/Current Module One or two outputs, depending on configuration, connected common neutral 0-150V rms phase to neutral, direct coupled, specifications as for MTS-3040 module above 0-25A rms, 120 VA maximum per channel, specifications as for MTS-3060 module above Can be configured for any voltage and/or current combination of two output channels Fully open and short circuit proof and thermal overload-protected 2.2.4 Output frequency...
SPECIFICATIONS - Section 2 2.5.3 AC Current Module Options Option 61 240V, 50/60 Hz line input Option 62 2nd AC Current Channel Option 63 3rd AC Current Channel Option 64 AC Current Test Lead Kit Maximum configuration: three Channels per ACI Module, two Modules per stack. 2.5.4 AC Voltage/Current Module Options Option 31 240V, 50/60 Hz line input...
This pushbutton selects the Prefault state for off-line programming (ENABLE off) or toggles the Prefault mode on or off (ENABLE on, Test mode). Current status is indicated by the PREFAULT LED. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL ###################################0$17$#7(67#6<67(06 CU M004 01A...
Page 22
These keys are used to enter numeric data, and to modify the currently selected parameter, such as amplitude, phase, or frequency. 7. ENTER KEY This key is used to signal the end of a numerical entry sequence, and to restore operation of the MODIFY knob. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL #0$17$#7(67#6<67(06########################################### CU M004 01A...
Page 23
This pushbutton turns on or off the mains power to the Control Module and to any AC output modules connected to the Control Module. 14. ALPHANUMERIC DISPLAY This Liquid Crystal Display (LCD) provides information on current equipment status, and displays numerous menu options. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL ###################################0$17$#7(67#6<67(06 CU M004 01A...
1. When DCI is enabled by this switch, whenever an external relay contact (in series with a DC current operated target) closes, the programmed DC current will flow through the external circuit. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL #0$17$#7(67#6<67(06########################################### CU M004 01A...
1. OUTPUT TERMINALS Up to 300VDC at 100 W is available here. 2. DC VOLTAGE DISPLAY The present setting of the DC voltage module is displayed on this LED display. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL ###################################0$17$#7(67#6<67(06 CU M004 01A...
These keys are used to select a parameter prior to modifying it. The first press selects amplitude of a given output, while the second selects its phase angle. 3. COOLING INTAKE/FILTER The filter on this cooling intake may be removed for cleaning if necessary. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL #0$17$#7(67#6<67(06########################################### CU M004 01A...
4. COM 1 RS232C PORT Female DB-9 serial port wired as a DCE (Data Communications Equipment) for external PC or DUT. 5. IRIG B CONNECTORS (OPTIONAL) Connect to IRIG B datastream from GPS receiver. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL ###################################0$17$#7(67#6<67(06 CU M004 01A...
Page 28
External I/O connector to run one or more systems in a master-slave configuration. 9. PRINTER PORT Connects to external printer to print Quick-Test reports. 10. GROUNDING STUD Connect to a secure external ground during testing. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL #0$17$#7(67#6<67(06########################################### CU M004 01A...
3.3 BASIC APPLICATIONS 3.3.1 Getting Started Because of its modularity, the MTS-3000 series system can be configured in many different ways. It’s not feasible to provide a detailed operation description for every possible configuration. Except where noted, the assumption is the equipment is configured as a three phase protective relay test system equipped with three AC voltage sources, three AC current sources, a digital I/O module with DC current sourcing, and a DC voltage module, as illustrated below.
Page 30
MTS-3000 system, operating at approximately 50 volts and seven amps, with a phase shift between voltage and current of 75°. FIGURE 3.8 TEST CONNECTIONS 3-10 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL #0$17$#7(67#6<67(06########################################### CU M004 01A...
Page 31
INPUT 1 at the appropriate times to simulate relay operation. It will be necessary to provide a current path by shorting terminals A and N of the current module with a second jumper cord. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 3-11 ###################################0$17$#7(67#6<67(06...
Once the FAULT button is released, the AC outputs return to zero, the relay being tested drops out, and the indicator LED and tone turn off. 3-12 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL #0$17$#7(67#6<67(06########################################### CU M004 01A...
Page 33
RESET. This resets the timer and V/I readings, and extinguishes the TRIP LED. Note the important difference in this ‘dynamic fault’ mode compared to the ‘static fault’ mode described in steps 1-12. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 3-13 ###################################0$17$#7(67#6<67(06...
(flashing) channels to Frequency 1, disables the MODIFY input, turns off the F2 LED, and returns the display to normal. FIGURE 3.10 FREQUENCY ADJUST 3-14 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL #0$17$#7(67#6<67(06########################################### CU M004 01A...
3. Enter the desired DC voltage level on the MODIFY keyboard. For 250.0VDC, for example, press 2, 5, 0, ENTER. This setting will appear on line 1 of the CM display, as well as the LED output display of the DC VOLTS module. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 3-15 ###################################0$17$#7(67#6<67(06...
The DC current output only should be used when the protective relays trip output circuit is properly isolated. FIGURE 3.12 DC CURRENT ADJUST 3-16 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL #0$17$#7(67#6<67(06########################################### CU M004 01A...
B voltage from its default 240.0 to 180.0 . The resultant voltage will then be the mathematical sum of the amplitudes of the two voltages. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 3-17 ###################################0$17$#7(67#6<67(06 CU M004 01A...
See Parallel Current Mode in the Advanced Operation section. 3.3.8 Overcurrent Relay Test FIGURE 3.15 OVERCURRENT RELAY TEST 3-18 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL #0$17$#7(67#6<67(06########################################### CU M004 01A...
FAULT pushbutton. See the Advanced Operation section for information on configuring the input. Any commercial normally open foot switch will work. A heavy duty one is available from Manta Test Systems. 3.3.8.3 INVERSE-TIME CHARACTERISTIC TEST.
The TRIP LED will light, the output current will trip off, and the timer and all current, voltage, and phase readings will be frozen. Record the current and timer readings, and press RESET to restore the system to Prefault mode. 3-20 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL #0$17$#7(67#6<67(06########################################### CU M004 01A...
5. Press the ON pushbutton of the DIGITAL I/O module to turn off the DC current. This will drop out the seal-in relay, as indicated by the INPUT 1 LED and tone turning off. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 3-21 ###################################0$17$#7(67#6<67(06...
5. Select the B phase of the current output module by pressing the F2 key on the module, and enter the desired restraint current via the MODIFY keyboard or rotary knob. 6. Enable the outputs by pressing ENABLE. Press and hold FAULT. 3-22 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL #0$17$#7(67#6<67(06########################################### CU M004 01A...
MODIFY to directly adjust the percentage of harmonic content of the fundamental current whose amplitude is displayed on the AC current module. Note the display for IA changes from IA to IAh as a reminder that IA is in harmonic mode. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 3-23 ###################################0$17$#7(67#6<67(06...
The most common levels are 0.2A and 2.0A. 3. Press the ON button on the DIGITAL I/O module, which enables the DC current output and turns on its LED. 3-24 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL #0$17$#7(67#6<67(06########################################### CU M004 01A...
1. Select slope display mode by entering the following key sequence: MENU | Settings | Display Optns | Slope | 2wdg 87T style, followed by MENU again. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 3-25 ###################################0$17$#7(67#6<67(06...
POSTFAULT causing the TRIP LED to be lit, the timer and AC readings to be frozen, and the AC outputs to be disabled. 3. Record the timer reading from the first line on the Control Module display. Press RESET to restore the system operation. 3-26 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL #0$17$#7(67#6<67(06########################################### CU M004 01A...
(See Parallel Current Mode in the Advanced Operation section). 3. Select the output channel(s) amplitude adjust mode and, with MODIFY keypad or rotary knob, set a current to be within 5%, but lower than the expected operate point. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 3-27 ###################################0$17$#7(67#6<67(06...
If three voltage modules are not fitted, it will be necessary to move the Va output to the other phases in turn to verify them. 3-28 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL #0$17$#7(67#6<67(06########################################### CU M004 01A...
FAULT pushbutton. See the Advanced Operation section for information on configuring the input. Any commercial normally open foot switch will work. A heavy duty one is available from Manta Test Systems. 3.3.11.3 TIMING TEST.
3.3.12.2 PICKUP TEST. 1. Disable the outputs, if necessary, by pressing ENABLE until its LED is out, and press FAULT. Its LED should come on. 3-30 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL #0$17$#7(67#6<67(06########################################### CU M004 01A...
If the relay under test has a DC current-operated target, the sensing leads from INPUT 1 must be connected to the contact output terminals of the relay which contain the target element. Note that the DC current is an optional feature of the DIGITAL I/O module. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 3-31 ###################################0$17$#7(67#6<67(06...
4. Select A phase voltage again via the voltage module F1 key, and begin increasing the voltage level with the MODIFY knob. The relay should trip when the voltage reaches the inhibit level. 3-32 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL #0$17$#7(67#6<67(06########################################### CU M004 01A...
2. Select the voltage adjust mode for voltage A by pressing F1 until the flashing cursor lies beneath the ‘V’ on the VA voltage line of the display. Determine the voltage limit window by raising and lowering the voltage with the MODIFY knob until the relay drops out. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 3-33 ###################################0$17$#7(67#6<67(06...
F3 and enter the desired frequency 2 value. This is typically used if the frequency of the power source for the MTS is unstable, as is often the case when being driven from a portable generator. 3-34 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL #0$17$#7(67#6<67(06########################################### CU M004 01A...
‘V’ representing Volts in the F1 line of the module’s display. 3. Enter the desired test voltage value via the MODIFY keyboard or rotary knob. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 3-35 ###################################0$17$#7(67#6<67(06...
Depress the FAULT button and raise the current (or lower the voltage for an impedance relay) until the relay is picked up at the desired point for timing testing. 2. Release the FAULT button to reset the relay. 3-36 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL #0$17$#7(67#6<67(06########################################### CU M004 01A...
Φ-N, Φ-Φ, or 3Φ). In many cases there will be detailed written test procedures available that outline specific voltage and current amplitudes, as well as phase angles to test the relay. These procedures may be followed using the basic vector mode of the MTS-3000. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 3-37 ###################################0$17$#7(67#6<67(06...
‘indirect’ phase values such as phase-to-phase voltage angles. The impedance for the selected fault type is displayed on the second line of the CM display. 3-38 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL #0$17$#7(67#6<67(06########################################### CU M004 01A...
3. To check the reach of other phase elements of the relay, select the desired phase by pressing F4 on the Control Module. This transfers the preset fault values to the selected phase. Repeat Steps 1 and 2, as required. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 3-39 ###################################0$17$#7(67#6<67(06...
Control Module, tripping off the AC outputs, and bringing on the TRIP LED. 4. Press RESET to clear the timer and restore prefault conditions. 3-40 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL #0$17$#7(67#6<67(06########################################### CU M004 01A...
MODIFY keypad. While the CMs F2 LED is illuminated, press F1 on the voltage module to select the VA channel to output at frequency 1. Press F2 again to disable the frequency adjust mode. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 3-41 ###################################0$17$#7(67#6<67(06...
2. Set the DC voltage to below the expected operate point. Press SET on the DC Voltage module and adjust the DC voltage level, as required, with the MODIFY knob or keypad. 3-42 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL #0$17$#7(67#6<67(06########################################### CU M004 01A...
DC voltage to the relay under test, as well as INPUT #2 on the DIGITAL I/O module. The presence of voltage on INPUT #2 will start the timer. The Timer will stop when the relay operates. Record the timer reading. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 3-43 ###################################0$17$#7(67#6<67(06...
Page 64
OPERATION SUMMARY - Section 3 3-44 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL #0$17$#7(67#6<67(06########################################### CU M004 01A...
DETAILED OPERATION - Section 4 DETAILED OPERATION 4.1 FAULT STATES The MTS operates in one of three unique fault states: Prefault, Fault and Postfault, as indicated by the FAULT and TRIP (POSTFAULT) LEDs. A flashing LED indicates that the AC outputs are enabled. FAULT LED TRIP LED Fault state...
DETAILED OPERATION - Section 4 *NOTE: It’s possible to change the function and logic of the auxiliary output contact (see section 5.16). P R E FA U LT FA U LT P O S T FA U LT FIGURE 4.1 EXAMPLE OUTPUT SEQUENCE (PREFAULT OFF) PREFAULT FAULT POSTFAULT...
DETAILED OPERATION - Section 4 [F A U L T ] L E D o ff [F A U L T ] L E D on F A U L T P R E F A U L T FIGURE 4.3 FAULT STATE DIAGRAM FOR STATIC MODE 4.3.2 Dynamic Fault Mode Dynamic Fault Mode refers to the operation mode used to perform operate time tests.
However, this low threshold level may cause false triggering when working in very noisy environments. Threshold levels may be raised, if required. Please contact Manta Test Systems for details. 4.4.3 Start Trigger (FLT) A “start”...
DETAILED OPERATION - Section 4 4.4.4 Stop Trigger (TRIP) A “stop” trigger will initiate a transition from DYNAMIC FAULT state to POSTFAULT state. This transition can be initiated by a voltage or contact change on INPUT 1 of the Digital I/O modules. The stop trigger action is disabled in static operation mode.
DETAILED OPERATION - Section 4 FIGURE 4.5 TEST CONNECTIONS FOR SCR OUTPUT TYPE RELAY 4.5 CURRENT MODES 4.5.1 Current Range The MTS-3000 has two current ranges which determine how the internal current amplifiers are configured to perform different types of testing. Most testing can be done in the default 0-25A, Low Voltage range. However, some applications, especially older high burden electromechanical ground protection relays, may require the 0-12A, High Voltage mode.
DETAILED OPERATION - Section 4 FIGURE 4.6 DIFFERENTIAL RELAY HARMONIC RESTRAINT TESTING 4.5.2 HARMONIC Current Mode This current mode generates a current output which is the sum of a fundamental frequency current, and a harmonic current. The harmonic may be from 2nd through to 10th harmonic. The fundamental current, percentage harmonic, and phase relationship are adjustable.
DETAILED OPERATION - Section 4 4.5.2.1 DEFINITION OF PERCENTAGE HARMONIC. The total RMS current is defined as: × Itrms fundamental current % nth harmonic) fundamental current The percentage of harmonic is defined as: nth harmonic amps x 100 % nth harmonic = fundamental amps In the case of 2nd harmonic of 60Hz, which is most often used, this becomes: % 2nd harmonic = 120 Hz amps x 100...
5.1.1.3 MENU NAVIGATION. Working down the menu tree – (Selecting a sub-menu ) Menu items with three trailing dots lead to sub-menus. In this example, pressing F1 yields the SETTINGS sub-menu. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
Page 74
5 D W H # 4 3 1 3 3 # 9 2 V Blinking cursor Exiting the menu: The MENU button may be pressed again at any time to exit from the menu. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
Page 75
For example, Voltage Ramp: Start n.nV (0.0-150.0) means that, if this option is selected, the user is expected to input a value between 0.0 and 150.0 volts. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
Page 76
ADVANCED OPERATION - Section 5 FIGURE 5.2 MENU TREE SETTINGS MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
Complex adjustments, such as the four parameters which must be adjusted simultaneously to simulate a phase-to-phase voltage collapse in a 3Φ system, can be controlled by a single MODIFY knob adjustment or keypad input. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
0.0 to 25.00 @ 0 to 500 A/second Note that, as an advanced feature, ramping isn’t available in the simplified Vector mode. Φ-N, Φ-Φ, or 3Φ fault mode must be selected first. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
F2 (as described in 3.3.13) is known as Frequency 1. It’s possible to program Frequency 1 for different values in prefault and fault modes for cases where it’s desired to generate a step change in frequency. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06...
This feature allows a variety of reclosure scenarios to be programmed. Shots determines the number of times a reclosure will be initiated before locking out from further operation when using the "internal" reclose option. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
However, they’re supplied with φ-N voltage and phase current, plus a determined proportion of the residual current. This proportion of the residual current is the zero sequence compensation factor, K. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 5-11 0$17$#7(67#6<67(06...
Page 84
Three Phase faults (3 This mode displays the positive sequence impedance (Z ) for three phase faults. V = φ-N voltage Z = V / I Where: I = φ-N current 5-12 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
5.3 QUICK TEST As noted above, because of the unique nature of Quick Test, an entire separate section of this manual is devoted to it. Refer to Section 6. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 5-13 0$17$#7(67#6<67(06 CU M004 01A...
Page 86
ADVANCED OPERATION - Section 5 FIGURE 5.5 MENU TREE: PREFERENCES 5-14 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
5.4.6 Assign Ports This allows the reports generated by Quick Test to be output via COM 1, COM 2, or the Printer port (LPT1). The default assignment is LPT1. ####### MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 5-15 0$17$#7(67#6<67(06 CU M004 01A...
ADVANCED OPERATION - Section 5 5.4.7 LCD Contrast This allows the contrast on each of the LCD main displays in the system to be adjusted for optimum legibility. 5-16 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
Page 89
ADVANCED OPERATION - Section 5 FIGURE 5.6 MENU TREE: INDEX/OTHER MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 5-17 0$17$#7(67#6<67(06 CU M004 01A...
Quick Test. 5.6.4 Diagnostics A variety of diagnostic codes and information may be displayed here. This feature is provided to assist in remote diagnosis by a factory support person. 5-18 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
Page 91
ADVANCED OPERATION - Section 5 FIGURE 5.7 MENU TREE: DIGITAL I/O MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 5-19 0$17$#7(67#6<67(06 CU M004 01A...
This selection programs the input to accept an external foot switch as a fault initiate trigger in Static mode, (i.e. the outputs will be maintained as long as the input signal is sustained). See Section 4.3 for further information about operation modes. 5-20 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
In this mode, the contacts simulate a 52B circuit breaker auxiliary contact. The contacts are as shown on the front panel during PREFAULT and FAULT. They change state upon entering POSTFAULT state. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 5-21 0$17$#7(67#6<67(06...
This selection reports the installed software and hardware versions, and module identity number, of the Digital I/O module. This information may be required by a factory support person to help resolve an operational problem. 5-22 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
QuickTest descriptions for hardware requirements. When using the MTS-3030 (convertible voltage / current module), the output mode (i.e. voltage vs. current) may be changed automatically by Quicktest to meet the necessary hardware requirements for the Quicktest algorithm. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
QUICKTEST - Section 6 6.3 QUICKTEST TERMINOLOGY AND ABBREVIATIONS CM – control module Hook-up – the wiring connections required between the MTS and the relay under test MTS – modular test system Relay ID – a unique, five digit identification number used to identify a particular relay Stack - the optional modules that are combined to make up a particular MTS WFG –...
Page 97
Timed overcurrent (51) test to test the operate time of the relay with an input voltage of 100 Volts. The user would simply set the voltage channel to 100V prior to test execution, and then execute the test in a normal fashion. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
Page 98
QUICKTEST - Section 6 6.5 TIMED 1Φ Φ Φ Φ OVERCURRENT TEST ANSI#: Hardware requirements: MTS-3010 (DIGITAL I/O module) MTS-3030 MTS-3060 (AC CURRENT module) or (CONVERTIBLE V/I module) 6.5.1 Test Description Tests performed: Minimum Pickup: determines the minimum pickup threshold of a time overcurrent element. Operate time: determines the operate time vs.
Page 99
24.0 A: 3.56 s (printer required) These two steps repeat for the # of test points 36.0 A: 1.14 s 48.0 A: 0.71 s ø Scroll down to see 60.0A: 0.54s MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
QUICKTEST - Section 6 6.6 INSTANTANEOUS 1Φ Φ Φ Φ OVERCURRENT TEST ANSI# Hardware requirements: MTS-3010 (DIGITAL I/O module) MTS-3030 MTS-3060 (AC CURRENT module) or (CONVERTIBLE V/I module) 6.6.1 Test Description Tests performed: 1. Operate current: determines the pick up threshold of a definite time overcurrent element. 2.
Page 101
= 0.029 s Press F3 to repeat either test Next test Press F4 to print the test report (printer required) Print result * Output current is displayed on the ACI module MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
Page 102
QUICKTEST - Section 6 6.7 TIMED 1Φ Φ Φ Φ UNDER VOLTAGE TEST ANSI#: Hardware requirements: MTS-3010 (DIGITAL I/O module), MTS-3030 MTS-3040 (AC VOLTAGE module) or (CONVERTIBLE V/I module) 6.7.1 Test Description Tests performed: Operate level: determines the maximum pickup threshold of a time under voltage element. Time vs.
Page 103
! 90.0 V: 4.25 s 80.0 V: 3.61 s Time value increases until relay operates 70.0 V: 1.92 s These two steps repeat for the # of test points MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
QUICKTEST - Section 6 6.8 INSTANTANEOUS 1Φ Φ Φ Φ UNDER VOLTAGE ANSI#: Hardware requirements: MTS-3010 (DIGITAL I/O module), MTS-3030 MTS-3040 (AC VOLTAGE module) or (CONVERTIBLE V/I module) 6.8.1 Test Description Tests performed: Operate voltage: determines the pick up threshold of a definite time under voltage element. Operate time: determines the operate time with 85% of nominal operate voltage.
Page 105
Next test … Press F3 to repeat either test Print Result … Press F4 to print the test report (printer required) BACK Press BACK to return to previous menu MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 6-11 0$17$#7(67#6<67(06 CU M004 01A...
QUICKTEST - Section 6 6.9 TIMED 1Φ Φ Φ Φ OVER VOLTAGE TEST ANSI#: Hardware requirements: MTS-3010 (DIGITAL I/O module), MTS-3030 MTS-3040 (AC VOLTAGE module) or (CONVERTIBLE V/I module) 6.9.1 Test Description Tests performed: 1. Operate level: determines the minimum pickup threshold of a time over voltage element. 2.
Page 107
! 135.0 V: 4.25 s 140.0 V: 3.61 s Time value increases until relay operates 145.0 V: 1.92 s These two steps repeat for the # of test points MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 6-13 0$17$#7(67#6<67(06 CU M004 01A...
Page 108
QUICKTEST - Section 6 6.10 INSTANTANEOUS 1Φ Φ Φ Φ OVER VOLTAGE TEST ANSI#: Hardware requirements: MTS-3010 (DIGITAL I/O module), MTS-3030 MTS-3040 (AC VOLTAGE module) or (CONVERTIBLE V/I module) 6.10.1 Test Description Tests performed: 1. Operate voltage: determines the pick up threshold of a definite time over voltage element. 2.
Page 109
Next test … Press F3 to repeat either test Print Result … Press F4 to print the test report (printer required) BACK Press BACK to return to previous menu MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 6-15 0$17$#7(67#6<67(06 CU M004 01A...
QUICKTEST - Section 6 6.11 TRANSFORMER DIFFERENTIAL TEST. ANSI#: Hardware requirements: MTS-3010 (Digital I/O module), MTS-3060 (AC CURRENT) or MTS-3030 (CONVERTIBLE V/I module) Version: 6.11.1 Test Description 1. Slope: Determines the slope of a restrained differential element for up to three points. 2.
“Step I1” and “Step I2". MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 6-17 0$17$#7(67#6<67(06...
Page 112
QUICKTEST - Section 6 Example Transformer Differential (87) MENU 4φ#2YHU&XUUHQW 3 terminal Settings QuickTest 1φ UnderVoltage 2 coil indep. … Preference 1φ OverVoltage Index Differential … Enter up to 5 numbers for unique relay identity#1 Relay ID: 00000 Relay Settings Enter the relay tap setting for winding 1.
Page 113
Time result … 5th H/R = 34.5 scroll ø trip @ 80% x P/U ramp on Ix ramp on Ix UnRes H/R = 18.0 P/U=29.8A The unrestrained element operated at 29.8A MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 6-19 0$17$#7(67#6<67(06 CU M004 01A...
Page 114
QUICKTEST - Section 6 6-20 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 ######## ############################################### # CU M004 01A...
Signal (DTE view) Direction Receive Data From MTS-3000 Transmit Data To MTS-3000 Signal Ground Request to Send To MTS-3000 Clear to Send From MTS-3000 Recommended cable for connection to PC: MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 ########### CU M004 01A...
Baud Rate, and then select the desired baud rate from the list. After selecting the baud rate, this value is retained in non-volatile memory and need not be re-selected as long as the same baud rate is desired. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 ############################################...
For experimentation or learning purposes, the RS-232C interface operates in an easy-to-use, conversational or ‘terminal’ mode. When using a computer, the computer should be running terminal ® ® emulation software such as Manta Test Systems’ Powerterm, PROCOMM or Windows ‘98 Hyper Terminal.
Page 118
Example: >STR <-begin test sequence >MFD2500 <-wait for relay closure up to 2.5 sec. later >PFS <- interrogate fault state POSTFAULT <-MTS-3000 returns “POSTFAULT” indicating operation MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 ############################################ CU M004 01A...
• Valid values are 0 - 150.00 (volts) AVC# Amplitude Vc • Sets the amplitude of Vc for the currently selected fault state • Valid values are 0 - 150.00 (volts) MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 ########### CU M004 01A...
• Valid values are 0 - 25.00 (amps). AIB# Amplitude Ib • Sets the amplitude of Ib for the currently selected fault state. • Valid values are 0 - 25.00 (amps). MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 ############################################ CU M004 01A...
• Where x = value of bit patern of channels to be changed, Va=1, Vb=2, Vc=4 • Where y = phase angle: -360 to 360.0 (degrees) • Where z = fault state: 0 = present, 1 = prefault, 2 = fault MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 ###########...
• Assigns the specified channels to frequency 2 • Where x is output type: V for voltage channels, or I for current channels • Where y = channel: A, B, or C MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 ############################################...
<- assign Va, Vb, and Vc, variable frequency 1 RFR 60 58.2 0.3 <- ramp from 60Hz to 58.2Hz with a ramp rate of 0.3Hz PRF1 <- prefault V&I on <- start ramp MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 ########### CU M004 01A...
In this mode, characters sent to the MTS-3000 are not echoed back to the terminal or computer. Communication on the interface is effectively limited to one direction at a time. 7-10 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 ############################################ CU M004 01A...
Page 125
• Where: y = 3 for ODD parity (x = 17 or 25) • Where: y = 1 for 1 STOP BIT (x = 18 or 26) • Where: y = 2 for 2 STOP BITS (x = 18 or 26) MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 7-11 0$17$#7(67#6<67(06...
• This is used to sense the presence of a closed contact or voltage on the trigger inputs. • “1” is returned if a closed contact or voltage is sensed. • “0” is returned if neither of the above is sensed. 7-12 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 ############################################ CU M004 01A...
Page 127
• d for ACV, ACI, and VI modules as follows: • LSB 0: Channel A clipping • 1: Channel B clipping • 2: Channel C clipping • 3: Channel A overload MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 7-13 0$17$#7(67#6<67(06 ########### CU M004 01A...
Channel A clipping for the ACV module. 7.2.10 Other Commands Command Description VER# Version • Prints the version control information for the specified module as follows: • MTS-3000, 1.5 > Module, firmware version 7-14 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 ############################################ CU M004 01A...
• y = 120 for output enable / disable, z = 0 to disable, z = 1 to enable VDC# DC Voltage • Sets the DC voltage amplitude for the present fault state • Valid values are 0 - 300. (volts) MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 7-15 0$17$#7(67#6<67(06 ########### CU M004 01A...
• z = 16 for output contact type OFF, (y = 110) • z = 32 for output contact type FAULT-NC, (y = 110) • z = 64 for output contact type RESET, (y = 110) 7-16 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 ############################################ CU M004 01A...
<- change to remote control 3. A 0.3 second delay should be added before the execution of a STR command to ensure all MTS-3000 internal operations have been completed before entering the FAULT state. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 7-17 0$17$#7(67#6<67(06...
Page 132
RS-232C INTERFACE - Section 7 7-18 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 ############################################ CU M004 01A...
Page 133
Print Digital Input Trigger Status 7.2.9 Print Fault State 7.2.9 Program mode 7.2.8 Print phasor table 7.2.9 PIS x y z Phase angle of specified current channel 7.2.9 PRF # Set Prefault on/off 7.2.2 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
Page 134
Start trigger (Enter Dynamic fault state) 7.2.1 Terminal mode 7.2.8 VDC# Sets the DC voltage 7.2.11 VER# Version 7.2.10 VIC x y z Sets the amplifer mode for the MTS-3030 7.2.3 Repeat Last Command 7.2.10 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06######################################## CU M004 01A...
Delta or wye display modes • Displays quantities as primary or secondary values • Calculates and plots symmetrical components, positive sequence impedance and power from user- entered phasor values in “demo” mode. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
Figure B.2 B.1.4 Configuring the Comm Port Select View|Comm Port from the main menu to configure the PC communications port. The following dialog box should appear: Figure B.3 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06################################## CU M004 01A...
B.1.6.2 DEMO MODE. This mode is for demonstration purposes or when equipment is not available or connected. Choose this mode by selecting View|Demo Mode in the menu.The following window should appear: MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
Once either the real-time or demo operating mode is chosen, the phasor and impedance displays can be activated. These displays can be selected using the View submenu or the buttons on the button bar. Figure B.6 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06################################## CU M004 01A...
Note that this display is drawn based on settings and not on the true measured values, and currents are displayed at 10 times the scale of the voltages. B.3 SYMMETRICAL COMPONENTS B.3.1 Current Components Window Figure B.8 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
It is usually better to display the symmetrical components in delta mode since the positive and negative sequence components each consist of three phasors which often overlap one another. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06################################## CU M004 01A...
Select Φ-N mode and start with a balanced 3Φ system. Rotate the phase of one output Phase Unbalance and note that this causes the gradual appearance of negative and zero sequence components. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
(i.e. the angle of the zero sequence compensation factor is 0°). This can be entered by selecting Edit|Properties in the menu with the impedance window active. The following dialog window should appear: MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06################################## CU M004 01A...
Theoretical mho and quadrilaterial characteristics can be defined in the dialog window which appears when Edit|Properties is selected (with the impedance window active). Multiple mho characteristics can be defined using the “Add” button. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
B.6 SPECIAL NOTES Powerscope displays are only valid when the MTS-3000 is in the default “LINE” frequency mode. B-10 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06################################## CU M004 01A...
Page 145
Press ENABLE 1st: The user tried to perform some action while the AC outputs were inappropriately enabled or disabled. To avoid this alarm, first change the status of the AC outputs (by pressing ENABLE), and then try again. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL #######0$17$#7(67#6<67(06 CU M004 01A...
AC line (i.e. more than 15 ms of no zero crossings), and, as a result, iniates the power down sequence. If this alarm occurs, power the system off and then on to restore the system to normal operation. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06######################################## CU M004 01A...
Page 147
Pwr Supply Fail: This alarm typically occurs when the power supply fuse fails. Contact Manta Test Systems if replacing the fuse doesn’t remedy the problem. x: Overld Shtdwn (x=A,B,C): This alarm is obtained when the indicated amplifier shut itself down because it was dissipating too much power for too long at the present temperature.
If these alarms or any other alarms not mentioned above should occur, and you can reproduce the error, please make a note of the particulars and inform Manta Test Systems Research & Development so that the problem can be corrected.
Page 149
Dynamic Fault Mode This mode is used to timing events using two wires to a start trigger perform timing tests. (4.3.2) signal, and two wires to a stop trigger signal. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
Page 150
Postfault State The postfault state simulates the varied between 8Hz and 1000 Hz. (3.3.3, 5.2.6) inputs to the relay after the fault condition and relay operation. (4.1.3) MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06############################# CU M004 01A...
Page 151
Voltage Mode The MTS-3030 module uses convertible amplifiers that can operate in either current mode or voltage mode. (5.4.2) WFG Module WFG refers to waveform generation modules, such as the MTS-3030, MTS-3040, and MTS-3060. MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
Page 152
GLOSSARY MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06############################# CU M004 01A...
Page 153
3-34 5-15, 7-7, A-1, D-1 to D-3 frequency ramping 5-8 current modes 4-6 frequency relay 3-30 current ramping 2-3, 5-8 fuses 1-4 current range 2-4, 4-6, 5-5, 5-9, 7-7 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
Page 154
6-7, 6-9, 6-11, 6-13, 6-15, 6-18, A-2, B- prefault state 3-1, 3-2, 3-30, 3-31, 4-1 to 4-5, 1 to B-3, B-5, B-10, C-1, C-2, D-2 5-20, 7-4, 7-9, 7-10, 7-13, D-2 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
Page 155
3-5, 3-12, 3-19, 3-21, 3-23, 3-25, 3-26, 3- 29 to 3-32, 3-36, 3-39, 4-5, 7-16 transformer differential relay - see differential relay 3-22, 3-24, 3-25, 3-28, 4-7, 5-11, 6-17, B-1, B-9, B-10 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...
Page 156
INDEX MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 0$17$#7(67#6<67(06 CU M004 01A...