MTS-1700 SERIES
ADVANCED UNIVERSAL PROTECTIVE
RELAY TEST SYSTEM
OPERATION AND REFERENCE MANUAL
Fifteenth Edition
February 2003
Manta Test Systems Incorporated
4060B Sladeview Crescent, Unit #1
Mississauga, Ontario, L5L 5Y5, Canada
Tel: +1(905) 828-6469 Fax: +1(905) 828-6850
e-mail: support@mantatest.com Internet: http://www.mantatest.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MTS-1700 SERIES and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Manta MTS-1700 SERIES

  • Page 1 MTS-1700 SERIES ADVANCED UNIVERSAL PROTECTIVE RELAY TEST SYSTEM OPERATION AND REFERENCE MANUAL Fifteenth Edition February 2003 Manta Test Systems Incorporated 4060B Sladeview Crescent, Unit #1 Mississauga, Ontario, L5L 5Y5, Canada Tel: +1(905) 828-6469 Fax: +1(905) 828-6850 e-mail: support@mantatest.com Internet: http://www.mantatest.com...
  • Page 2 MTS-1700 SERIES Advanced Univeral Protective Relay Test System™, Operation and and Reference Manual All rights reserved by Manta Test Systems Incorporated. No part of this publication may be reproduced or distributed in any form or by any means without the permission of Manta Test Systems Incorporated.
  • Page 3: Table Of Contents

    Getting Started ..................3-7 3.3.2 Safety & other precautions ..............3-8 3.3.2.1 SAFETY....................3-8 3.3.2.2 ISOLATION ..................3-8 3.3.2.3 PROTECTION...................3-8 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 4 HARMONIC RESTRAINT TEST............3-32 3.3.11.5 INSTANTANEOUS TEST..............3-32 3.3.11.6 TARGET TEST.................3-32 3.3.12 Synchronizing/Reclosing or Synchrocheck Relay........3-32 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 5 Timing in Cycles..................4-10 4.5.9 Testing SCR Output Type Relays............4-11 CURRENT MODES..................4-12 4.6.1 I1-LOW Current Mode ................4-13 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 6 4.7.4 -N) Fault Type ................4-34 Φ 4.7.5 -N Fault Type ..................4-34 4.7.6 Fault Simulation Examples..............4-35 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 7 5.2.3.1 CURRENT DURATION..............5-8 5.2.3.2 REMOTE-END-TRIP-SIMULATION..........5-8 5.2.4 Frequency Ramping .................5-8 5.2.5 Phase Ramping ..................5-9 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 8 PHASE ADJUSTMENT MODE..............5-30 5.12.1 Normal Phase Adjustment Mode .............5-30 5.12.2 Individual Phase Adjustment Modes ............5-31 viii MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 9 CURRENT CONTROL COMMANDS..........6-9 6.2.6.2 COMMANDS USED IN I3-WYE CURRENT MODE....6-12 6.2.6.3 EXAMPLES..................6-13 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 10 DC Voltage Control Commands..............6-39 6.5.16 COM2 Interface Commands ..............6-39 6.5.17 Other Commands ..................6-39 PROGRAMMING HINTS ................6-40 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 11 PLAYBACK OF DIGITAL CHANNELS ............7-10 EXTERNAL DATA MODE USAGE ............7-11 7.8.1 Connections .....................7-11 7.8.2 General Procedure..................7-11 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 12 ENABLING MTS-1720 OUTPUT............9-6 9.3.3.3 SPECIAL NOTES................9-9 9.3.3.4 PRECAUTIONS................9-10 THREE-PHASE CURRENT OPERATION (I3-WYE CURRENT MODE) ......................9-11 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 13 OPERATION WITH THE MTS-1710 + MTS-1750 CONFIGURATION................10-6 10.4.1.3.1 Current Adjustment and Display ..........10-6 10.4.1.3.2 RS-232 Programming ..............10-6 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL xiii M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 14 OPERATION WITH THE MTS-1710 + MTS-1720 + MTS-1753 CONFIGURATION................11-6 11.4.1.3.1 Current Adjustment and Display ..........11-6 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 15 Input Threshold Voltage Selection ............B-11 EXAMPLE APPLICATION .................B-11 APPENDIX C ALPHABETICAL RS-232 COMMAND SUMMARY ........................ C-1 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 16 DETERMINING OPERATION TIMES ............J-6 TESTING DYNAMIC AND VARIABLE CHARACTERISTICS ....J-8 FAULT PLAYBACK ..................J-9 OTHER CONSIDERATIONS ...............J-9 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 17 TRIGGERING AN OSCILLOSCOPE FOR RECORDING TESTS WITH THE MTS-1710 INTRODUCTION ..................O-1 PROCEDURE....................O-1 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL xvii M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 18 EXAMPLE: BLOCKING THE Z2GT & Z3 ELEMENTS PRIOR TO RUNNING THE 51NT TEST (SEL-121F RELAY)........T-3 xviii MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 19 INTRODUCTION ..................Y-1 METHOD ..................... Y-1 OPERATION TIME TEST ................Y-1 NON-OPERATION TEST ................Y-2 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 20 UNBALANCED THREE-PHASE TEST METHOD ....CC-6 NEGATIVE SEQUENCE ELEMENTS ........... CC-7 1.2.1 Definition ....................CC-7 1.2.2 Applications ..................CC-7 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 21 UNBALANCED THREE-PHASE TEST METHOD ....CC-13 SYMMETRICAL COMPONENTS AND HARMONICS....... CC-14 AN23 - APPLICATION NOTE HARMONIC RESTRAINT ELEMENT TESTING OF GE BDD15/16 AND ABB HU RELAYS USING THE MANTA TEST SYSTEMS MTS-1710 INTRODUCTION ..................DD-1 KEY POINTS OF THE FACTORY RECOMMENDED CALIBRATION ..................DD-1 HARMONIC ANALYSIS OF THE HALF-WAVE RECTIFIED AC ..
  • Page 22 TESTING THE THREE-PHASE ELEMENT MTA........II-6 TARGET (CURRENT OPERATED) ............II-6 OPERATING SPEED................. II-7 xxii MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 23 THREE-PHASE ELEMENT ..............II-9 HELPFUL HINTS AND EQUATIONS............. II-9 TESTING WITH THE MTS-1710 AND MTS-1720......... II-9 AN29 - APPLICATION NOTE CO RELAY TEST PROCEDURE USING THE MANTA TEST SYSTEMS MTS-1710 TEST EQUIPMENT INTRODUCTION ..................JJ-1 DESCRIPTION OF RELAY ..............JJ-1 EQUIPMENT REQUIRED AND CONNECTIONS .........
  • Page 24 TWO 3-PHASE CURRENT SOURCES FROM ONLY ONE 3-PHASE CURRENT SOURCE ..............LL-4 REFERENCES ................... LL-4 INDEX ......................MM-1 xxiv MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 25 EXAMPLE OUTPUT SEQUENCE (PREFAULT OFF & POSTFAULT ON) ........................4-7 FOUR-WIRE TIMING MEASUREMENT ..........4-9 TWO-WIRE PULSE TIMING CONNECTIONS .........4-10 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 26: Figure Title Page

    TWO-SHOT AUTO RECLOSE TEST ............5-27 5.11 POSTFAULT SEQUENCE EXAMPLE 1 ............5-29 5.12 POSTFAULT SEQUENCE EXAMPLE 2 ............5-30 xxvi MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 27 MTS-1710 + MTS-1720 + (3)MTS-1750 CONTROL CONNECTIONS..10-7 10.7 MTS-1710 + MTS-1720 + (3)MTS-1750 SINGLE PHASE CURRENT CONNECTIONS ...................10-8 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL xxvii M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 28 OVERCURRENT/POWER/IMPEDANCE RELAYS......... X-6 CONNECTIONS FOR DYNAMIC TEST OF 1-PHASE OVERCURRENT/POWER/IMPEDANCE RELAYS USING ONLY THE MTS-1710..............X-8 xxviii MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 29 SIX PHASE VOLTAGE VECTORS SHOWING LOSS OF ONE POTENTIAL ....................LL-2 TEST CONNECTIONS................LL-3 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL xxix M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 30 TABLE OF CONTENTS MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 31: Introduction

    Built-in front panel menu for advanced features. 1.2 GENERAL DESCRIPTION The MTS-1700 Series Universal Protective Relay Test System is a comprehensive relay test system designed for standard testing of polyphase and single-phase protection relays. It can perform steady-state and complex dynamic testing of relays, as well as fault playback (regeneration of digitized fault waveforms).
  • Page 32: Mts-1700 System

    It allows engineers to subject relays to predicted characteristic faults (based upon computer simulation models), or abnormal faults, and analyze their performance before implementation. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 33: Applications

    Testing of pilot wire relaying systems. • Power system modelling. • Relay qualification and acceptance testing. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 34: Terminology

    INTRODUCTION - Section 1 1.4 TERMINOLOGY The following section clarifies terminology defining various approaches to relay testing. The MTS-1700 Series Universal Protective Relay Test System is very versatile, and may be used in all these types of relay testing. 1.4.1 Static Relay Testing Static relay testing refers to testing of relays using very slowly varying inputs to accurately locate pickup points and to perform repeatable measurements.
  • Page 35: Technical Support

    INTRODUCTION - Section 1 1.5 TECHNICAL SUPPORT The design of this instrument reflects decades of experience in the electric power industry. Manta Test Systems recognizes, however, that there will be testing situations encountered which were not considered during product design, and we want it to be the product which best serves your specific needs.
  • Page 36: Limited Product Warranties

    Manta Test Systems. Provided Manta Test Systems receives notice of such defects within the warranty period, it shall, at its option, either repair or replace the software or firmware media, if proven to be defective.
  • Page 37: Exclusion Of Other Warranties

    1.7.5 Extension of Warranty At the discretion of Manta Test Systems, the warranty may be extended for a product which has been returned for service shortly after its warranty period has expired. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL...
  • Page 38 INTRODUCTION - Section 1 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 39: Specifications

    Dual AC current mode for slope tests (I1: 60A maximum, 50A @3V, I2: see above for single phase current) MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 40: Metering

    Accuracy: ±0.5° for input levels >5% of range 0 -359.9° or 0 - ±180° display modes Selectable V-leads-I or I-leads-V measurement reference MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 41: Computed Measurements

    14 bit: 14 bit dynamic + 16 bit scaling • Peak output levels: ±230.5V for voltage channels ±42.4A for current channels MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 42: Rs-232C Interface

    Protective Relay Test Environment for the Manta Test Systems MTS-1700 Series • MWave Fault Waveform Playback Software • MTS-1900 Utility Suite - utility programs enhance the use of various features of the MTS-1700 series. 2.9 OPTIONS • Option -03: Programmable digital I/O and trigger channels •...
  • Page 43: Additional Standard Features

    Weight: 60.0 lbs (27.2 kg) without front/rear protective covers 63.4 lbs (28.7 kg) with front/rear protective covers • Built-in carry handle/tilt stand MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 44 SPECIFICATIONS - Section 2 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 45: Operation Summary

    [EXTERNAL STOP] trigger inputs. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 46 This pushbutton toggles between the mode and menu displays. When lit, this indicates that the menu is active and that the non-menu controls will be inoperable. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 47 Auxuliary contact 1 can be used to test premissive and unblocked transfer schemes. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 48 31. [I1 OUTPUT] TERMINALS These output terminals provide output current in the I1-LOW and I1-HIGH current modes. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 49: Rear Panel Layout

    COM 2 RS-232C F15A COM 1 RS-232C SIGNAL INPUT 10 11 FIGURE 3.2 REAR PANEL LAYOUT MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 50 Spare communications port which may be used to control auxiliary devices. 11. [COM1 RS-232C] PORT Main MTS-1710 RS-232C serial interface port. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 51: Basic Applications

    FAULT MODE PHASE is the current path from the I3 current output. FIGURE 3.3 MODE/MENU DISPLAY MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 52: Safety & Other Precautions

    Turning the knob at a moderate speed--and very fast--makes medium and coarse adjustments respectively. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 53: Generalized Setup Procedure

    Turn the [MODIFY] knob to adjust the phase angle. The phase angle between the current and all three voltages changes when this adjustment is performed. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 54: References

    The operate time can be displayed by pressing the [TIME] button. • Press [STOP/RESET] to reset the MTS-1710 to the PREFAULT state. 3-10 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 55: Overcurrent Relay Test

    Select I1-HIGH current mode for instantaneous tests requiring over 30 amps. FIGURE 3.4 OVERCURRENT RELAY TEST SETUP MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 3-11 M A N T A T E S T S Y S T E M S...
  • Page 56: Minimum Pickup Test

    2. Press [STATIC/DYNAMIC], as required, to select STATIC operation mode. 3. Press [CURRENT] to display current. 3-12 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 57: Overcurrent Relay Target/Seal-In Test Setup

    TARGET Manually rotate disk and hold main contacts closed FIGURE 3.5 OVERCURRENT RELAY TARGET/SEAL-IN TEST SETUP MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 3-13 M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 58: Target/Seal-In Test

    DC voltage drops to near zero, and the [TONE] LED is off. 3-14 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 59: Voltage Relay Test

    1. Make test connections, as shown in Figure 3.6. Select Φ-N/A-N fault mode. If more than 150V is required, connect the relay across A-B, and select 2Φ-N/A-B fault mode. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 3-15 M A N T A T E S T S Y S T E M S...
  • Page 60: Timing Test

    8. Turn [POSTFAULT] off to remove the DC current, and to release the seal-in unit. 3-16 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 61: 1-Φ Impedance Relay/Directional Overcurrent Relay Test

    Make connections as shown on the next page. The MTS-2100 program provided with your MTS-1710 is useful for demonstrating the standard tests described in this section. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 3-17 M A N T A T E S T S Y S T E M S...
  • Page 62: Reach/Minimum Pickup Test

    3. Select I1-LOW current mode and static operation mode. Turn [PREFAULT] on, press [CURRENT], and adjust current to 0A. 4. Press [VOLTAGE], and set the nominal voltage. 3-18 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 63: Mta Test

    The following procedure tests voltage restrained or voltage controlled overcurrent elements. The element may or may not be directional (phase angle sensitive). MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 3-19 M A N T A T E S T S Y S T E M S...
  • Page 64: Minimum Pickup Test

    3-20 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 65: Preparation

    [SELECT]. Press [MODE/MENU] to exit the menu. If the DC voltage output option isn’t installed, an external DC source may be used. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 3-21 M A N T A T E S T S Y S T E M S...
  • Page 66: Reach Test

    Record this value. When using Φ-Φ and 3Φ(Φ-Φ) fault types, it’s not necessary to account for any 30° offset. 3-22 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 67: Operate Time Test

    6. To test other elements (A-N, B-N, C-N, A-B, B-C, C-A), simply change the fault mode, and repeat at step 2. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 3-23 M A N T A T E S T S Y S T E M S...
  • Page 68: Permissive Trip Test

    FAULT MODE controls. FIGURE 3.10 3-Φ IMPEDANCE RELAY PERMISSIVE TRIP TEST SETUP 3-24 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 69: Testing Signal Send/Carrier Send Output

    7. Verify that the signal send contact closes only works for faults in the specified zone(s) in the table above. 8. Set the fault voltage and current to within the operating zone. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 3-25 M A N T A T E S T S Y S T E M S...
  • Page 70: Differential Relay - Three-Terminal Type

    4. Slowly increase the operate current (I2) until the relay operates. Record this reading as the minimum pickup current. Release the [FAULT] button. 3-26 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 71: Slope Test

    AC, such as the GE BDD 15/16 and ABB HO, see important additional information in Application Note 23. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 3-27 M A N T A T E S T S Y S T E M S...
  • Page 72: Instantaneous Test

    Select I1-HIGH current mode DIFFERENTIAL RELAY FIGURE 3.12 INSTANTANEOUS TEST FOR THREE-TERMINAL CURRENT DIFFERENTIAL RELAYS 3-28 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 73: Target/Seal-In Test

    7. If a seal-in unit is included, turn [PREFAULT] off and observe the seal-in unit dropout. The DC current will drop to zero and the [TONE] button LED will turn on. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 3-29 M A N T A T E S T S Y S T E M S...
  • Page 74: Differential Relay - Independent Coil Type

    Many solid state current differential relays have independent coils for the two current inputs. This section describes how to perform the standard tests on this type of relay: 3-30 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 75: Minimum Pickup Test

    2. Press [CURRENT] to display/adjust the I1 current. “I1-AMPS” should be indicated in the [MODE/ MENU DISPLAY]. Press and hold [FAULT], and increase the current to the desired nominal value. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 3-31 M A N T A T E S T S Y S T E M S...
  • Page 76: Operate Time Test

    MTS-1710 is useful (but not a necessity) for demonstrating these tests. 3-32 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 77: Phase Angle Limit Test

    4. Turn [PREFAULT] on and, if required, check the A-N and C-N voltages by pressing [VOLTAGE], and selecting A-N and C-N fault phase. Adjust if necessary. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 3-33 M A N T A T E S T S Y S T E M S...
  • Page 78: Voltage Limit Test

    3-34 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 79: Ground Fault Overvoltage Relay

    This means that two voltages--one 3rd-harmonic, and one at the fundamental frequency, are required. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 3-35 M A N T A T E S T S Y S T E M S...
  • Page 80: Setup

    4. Press [VOLTAGE], and set the inhibit voltage for the 27S element above the inhibit level. 3-36 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 81: Overvoltage Pickup Test

    3.3.13.5 UNDERVOLTAGE INHIBIT TEST. To check the inhibit of the 3rd-harmonic undervoltage element by the supervising undervoltage element: MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 3-37 M A N T A T E S T S Y S T E M S...
  • Page 82: Frequency Relay Test

    Press [TIME] again to toggle between time in seconds/cycles. Press [STOP/RESET] to return to the prefault state, and to prepare for the next test. 3-38 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 83: Target/Seal-In Test

    See Section 5.1.2 for a description of this feature). MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 3-39 M A N T A T E S T S Y S T E M S...
  • Page 84: Dc Auxiliary/Time-Delay Relay Test

    When the relay contacts close, the [TONE] button will light. 6. Press [MODE/MENU] again to exit the menu. 3-40 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 85: Pickup Timing Test

    4. Press [MODE/MENU] again to exit the menu. 5. Press [STATIC/DYNAMIC], as required, to select DYNAMIC operation mode. Press [FAULT] to initiate the test. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 3-41 M A N T A T E S T S Y S T E M S...
  • Page 86: Dropout Timing Test

    This may be used to record the settings required for testing a particular device or relay. Each of these settings is explained in detail in Section 4. 3-42 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 87 The map on the next page gives an example of the settings map testing of the Φ-Φ Example: element of a 3 Φ impedance relay. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 3-43 M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 88: General Hints On Manual Use

    Lower voltage until relay operates. 3.5 GENERAL HINTS ON MANUAL USE The Manta Test Systems MTS-1710 differs in usage from conventional relay test systems in many areas. The following hints will help new users become familiar with the MTS-1710:...
  • Page 89 A user will also find it easier to learn operation with the MTS-1720, in which prefault and fault current settings and operation is slightly different from operation with the MTS-1710 alone. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 3-45 M A N T A T E S T S Y S T E M S...
  • Page 90 The MTS-2100 computer program provided with your MTS-1710 is also very helpful as a learning and demonstration aid. Please refer to the documentation provided with MTS-2100 for use. 3-46 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 91: Detailed Operation

    Note that the trigger action (closed contact, voltage, or depressing [FAULT]) must be maintained to hold the MTS-1710 in the fault state. Transitions between the two states is depicted in the following diagram: MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 92: Dynamic Operation Mode

    The state transition diagram is shown below: PREFAULT STOP TRIGGER FAULT POSTFAULT FIGURE 4.2 FAULT STATE DIAGRAM FOR DYNAMIC OPERATION MODE MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 93: Blinking Indicators In Dynamic Mode

    (Dynamic operation mode only) * occurred AUX contacts open** AUX contacts closed** AUX contacts open** MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 94 In the dynamic operation mode, the dynamic test may be run with four combinations of prefault/postfault V&I set on/off. This is shown in the chart on the next page: MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 95: Output Levels

    The postfault current and voltage, if enabled, are the same as the prefault settings. PREFAULT FAULT POSTFAULT FIGURE 4.3 EXAMPLE OUTPUT SEQUENCE (PREFAULT OFF & POSTFAULT ON) MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 96: Example Output Sequence (Prefault On & Postfault Off)

    FIGURE 4.4 EXAMPLE OUTPUT SEQUENCE (PREFAULT ON & POSTFAULT OFF) PREFAULT FAULT POSTFAULT FIGURE 4.5 EXAMPLE OUTPUT SEQUENCE (PREFAULT ON & POSTFAULT ON) MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 97: Trigger/Timer Operation

    In static operation mode, only the tone LED and tone (if enabled) turn on when a closed contact or voltage is sensed on the [EXTERNAL STOP] trigger inputs. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 98: Reset

    The sensing action, impedance characteristics, and isolation of these inputs are the same as those of the [EXTERNAL START] trigger inputs (see Section 4.5.4). MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 99: Trigger Threshold Levels

    However, this low threshold level may cause false triggering when working in very noisy environments. The threshold levels may be raised if required. Please contact Manta Test Systems for details. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 100: Two-Wire Pulse Timing

    (time in cycles doesn’t actually count power cycles--it’s a calculated value). 4-10 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 101: Testing Scr Output Type Relays

    52A (See Section 5.15.2). This will ensure the voltage is available to the SCR before the fault is applied. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 4-11 M A N T A T E S T S Y S T E M S...
  • Page 102: Current Modes

    Each of the current modes is detailed in the following sections: 4-12 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 103: I1-Low Current Mode

    Note there are prefault, fault, and postfault current settings (see Section 3.4), and the setting which is adjusted depends upon the present fault state. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 4-13 M A N T A T E S T S Y S T E M S...
  • Page 104: Il-High Current Mode

    I3-WYE current mode provides full 3Φ current, and requires the MTS-1720. Use of this current mode is described in Section 9.4. 4-14 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 105: I1 & I2 Current Mode

    Press [CURRENT] until the upper left corner of the [MODE/MENU] display reads “I1-AMPS”. Turn the [MODIFY] knob, as required. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 4-15 M A N T A T E S T S Y S T E M S...
  • Page 106: Special Notes

    (i.e. don’t connect both the red terminals and the black terminals together) as a method to obtain higher currents. 4-16 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 107: Proper & Improper Current Output Connections In I1&I2 Current Mode

    Figure 4.11 shows a connection method for a three-terminal type differential relay, with I1 and I2 simulating CT currents that would actually be produced in an in-service relay. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 4-17 M A N T A T E S T S Y S T E M S...
  • Page 108: Harmonic Current Mode

    2.25A and the rectified DC current at 1.00A. Figure 3 shows the pure DC rectified signal without any fundamental current. 4-18 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 109: Sum Of Fundamental Frequency Current Of 60Hz With 50% Harmonic

    FIGURE 4.13 SUM OF FUNDAMENTAL FREQUENCY CURRENT OF 60Hz WITH 50% HARMONIC FIGURE 4.14 SUM OF FUNDAMENTAL AND THE RECTIFIED DC CURRENT MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 4-19 M A N T A T E S T S Y S T E M S...
  • Page 110: Pure Harmonic - Basic Adjustment

    Press [PHASE] and turn the [MODIFY] knob, as required. This adjusts the “phase” between the harmonic and the fundamental, thereby changing the waveshape of the I2-Harmonic output. 4-20 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 111: Definition

    Note that the G.E. formula is actually the same as the Westinghouse formula if both numerator and denominator are multiplied by 2.22. Note: The DC-Amps must be zero to adjust the %HARM. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 4-21 M A N T A T E S T S Y S T E M S...
  • Page 112: Dc Amps - Basic Adjustment

    Press [CURRENT] until the upper left corner of the [MODE/MENU DISPLAY] reads “I2-AMPS”. Turn the [MODIFY] knob as required. This adjusts the fundamental current. 4-22 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 113: Special Notes

    VC channel provides the harmonic content component of the current. This means that, in these two current modes, you will not be allowed to adjust voltage in these fault modes: MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 4-23...
  • Page 114: Fault Current Preset Feature

    Maximum voltage = 44 Vrms For one MTS-1710 + MTS-1720, three current channels are available. 4-24 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 115: Selecting I3-Parallel Current Mode

    I1-HIGH current mode, except for the fact that the current is obtained by a parallel connection to three output terminals. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 4-25 M A N T A T E S T S Y S T E M S...
  • Page 116: Paralleling Of Two Mts-1710S

    The current through the load will be the vectorial sum of the two currents. 4-26 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 117: Three Phase Connection

    The current through each phase of the load will be the vectorial sum of the paralleled currents. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 4-27 M A N T A T E S T S Y S T E M S...
  • Page 118: Paralleling Of Two (Mts-1710 + Mts-1720) Systems

    The current through the load will be the vectorial sum of the six paralleled currents. 4-28 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 119: Three Phase High Current

    The current through each phase of the load will be the vectorial sum of the paralleled currents. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 4-29 M A N T A T E S T S Y S T E M S...
  • Page 120: Paralleling More Than Two (Mts-1710 + Mts-1720) Systems

    Higher currents and higher VA output can be obtained by simply connecting more MTS-1710 + MTS-1720 systems together. The MTS-1720 systems are optional. NOTE: External transient protection is required when paralleling together more than three MTS-1700 systems. Please contact Manta Test Systems Technical Support for more details. 4.6.10.6.1 Single phase high current I3- P ARALLEL...
  • Page 121: Three Phase High Current

    The current through each phase of the load will be the vectorial sum of the paralleled currents. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 4-31 M A N T A T E S T S Y S T E M S...
  • Page 122: Setting And Displaying Current In The I3-Parallel Current Mode

    The IA+IB+IC summed current is treated as a single high current. This is displayed accordingly as a single current in the MTS-2100 program. 4-32 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 123: Disabled Functions In I3-Parallel Current Mode

    Three-Phase (0-0) Two-Phase Three-Phase to-Neutral (0-N) FIGURE 4.24 VOLTAGE ADJUSTMENT IN VARIOUS FAULT MODES MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 4-33 M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 124: Φ-N Fault Type

    The 2Φ-N fault type simulates 2Φ-N faults by allowing adjustment of any two Φ-N voltages simultaneously. 4-34 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 125: Fault Simulation Examples

    Prefault Φ-N B-N Prefault Φ-N C-N Prefault Φ-Φ B-C Prefault 120V Φ-Φ B-C Fault MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 4-35 M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 126: Three-Phase-To-Ground Fault Example

    Similarly, for 3Φ fault types, 3Φ voltage adjust will be performed to keep the percentage voltage collapse on all three phases equal, even if the prefault Φ-N voltages are unbalanced. 4-36 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 127: Phase Angle Control

    This section assumes that V-leads-I phase angle measurement reference is selected. If I-leads-V phase angle measurement is selected, then the display values will be 360, minus the value shown. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 4-37 M A N T A T E S T S Y S T E M S...
  • Page 128: In I1-Low, I1-High & I3 Current Modes

    Similarly, if the [FAULT PHASE] is changed to C-A/Φ-Φ, the current is rotated to maintain the phase angle between VCA and the current at 70°. 4-38 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 129: I3-Wye Current Mode

    The fault phase angle can be checked before or after a dynamic test by selecting static operation mode, selecting [PHASE], and pressing [FAULT]. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 4-39 M A N T A T E S T S Y S T E M S...
  • Page 130: Monitor Voltage

    This means that the voltage output must be a few volts to read a frequency value in Hz. 4-40 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 131: Variable Frequency Reference Mode

    The change from prefault to fault state may have occurred up to one cycle before this moment due to the synchronization to the zero crossing of the voltage. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 4-41 M A N T A T E S T S Y S T E M S...
  • Page 132: Multi-System Synchronization

    Connect the multi-system synchronization cable at the rear, as shown in Figure 4.27 or 4.28. 4-42 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 133: Control Of Frequency And Phase Angle When Using Multi-System Synchronization

    (see Sections 5.12.2.1 and 6.7). MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 4-43 M A N T A T E S T S Y S T E M S...
  • Page 134: Use Of The Multi-System Sync Capability For Testing Pilot-Wire Relay Systems

    For example, to simulate a 10ms channel delay, the following commands should be sent to the MTS-1730: DIO,OCD1,1,10,1,1 DIO,OCD0,1,10,0,1 4-44 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 135: External Frequency Reference

    A unipolar or bipolar signal may be used. Set frequency reference mode to “LINE”. The use of this feature can be combined to be used with the multi-system sync feature. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 4-45 M A N T A T E S T S Y S T E M S...
  • Page 136: Audible Tone

    When enabled, and when the MTS-1710 enters the postfault state, a short beep occurs to indicate completion of a dynamic test. Of course, this only occurs in dynamic operation mode. 4-46 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 137: Adjusting Postfault Values

    When any of these conditions are present, the display will alternate between the normal display and the warning display. All warnings will continue to flash until the causing condition has been removed. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 4-47 M A N T A T E S T S Y S T E M S...
  • Page 138 “RES” command). However, all amplitude settings will be forced to zero. This will prevent immediate re- entry into an overload condition, if remedial action wasn’t taken. 4-48 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 139: Dc Voltage Control

    Fine adjustment of the level can be performed by turning the [MODIFY] knob. Press [MODE/MENU] when done. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 4-49 M A N T A T E S T S Y S T E M S...
  • Page 140 The default setting on power-up also can be set via the RS-232 interface using the DDF# command. See Section 6.2.15. 4-50 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 141: Advanced Operation

    If a menu item isn’t available, an appropriate error message will be displayed. Press [SELECT] or [PREVIOUS] to return to the previous menu display. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL CU A002 15A M A N T A T E S T S Y S T E M S...
  • Page 142: Mts-1710 Menu Tree

    ADVANCED OPERATION - Section 5 FIGURE 5.1 MTS-1710 MENU TREE MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 143: Mts-1710 Settings Sub-Menu Tree

    ADVANCED OPERATION - Section 5 FIGURE 5.2 MTS-1710 SETTINGS SUB-MENU TREE MTS-1700 SERIES OPERATION AND REFERENCE MANUAL CU A002 15A M A N T A T E S T S Y S T E M S...
  • Page 144: Special Notes

    To set ramp (initial, rate, and final) values, the MTS-1710 must be in static operation mode. Only the initial fault levels can be modified in dynamic mode--if and only if--the ramp rate has been set off. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 145: Programming Ramp/Duration Settings

    If the fault final value is less than the fault initial value, the parameter will be ramped down. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL CU A002 15A M A N T A T E S T S Y S T E M S...
  • Page 146: Basic Ramp/Duration Sequences

    - fault initial level (d) Programmed ramp + duration FIGURE 5.3 BASIC RAMP/DURATION SEQUENCES MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 147: Other Ramp/Duration Sequences

    FIGURE 5.4 OTHER RAMP/DURATION SEQUENCES MTS-1700 SERIES OPERATION AND REFERENCE MANUAL CU A002 15A M A N T A T E S T S Y S T E M S...
  • Page 148: Voltage Ramp & Fault Duration

    The only limitation is the prefault, fault initial, fault final and postfault frequency must all be in the same harmonic range. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 149: Phase Ramping

    The initial fault value is used as the value in the fault state. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL CU A002 15A M A N T A T E S T S Y S T E M S...
  • Page 150: Programming Durations

    120.0 20%/sec 10.0 I1 or I3[A] 3A/sec 12.0 Phase [deg] 12.0 75.0 Freq. [Hz] 5-10 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 151 The fault values are applied for 10 cycles (assuming 60Hz output), then return to prefault levels. The return to prefault is programmed by setting postfault on, and programming the postfault settings to be equal to the prefault settings. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 5-11 CU A002 15A...
  • Page 152: Timer Control

    The above factors, which determine the type of internal start trigger, are in order of priority. If two or more conditions are true, the higher one will determine the mode of operation. 5-12 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 153: External Start Timer Mode

    DC voltage is sensed across the relay coil. The timer is stopped when the relay contacts change state (open/close). MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 5-13 CU A002 15A...
  • Page 154: Dc Auxiliary Relay Timing Test

    An example of this is shown in Figure 5.7. 5-14 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 155: Special Application Of The External Start Timer Mode

    Purpose: To measure the operate time of the time delay relay, TD on the auxiliary trip bus. FIGURE 5.7 SPECIAL APPLICATION OF THE EXTERNAL START TIMER MODE MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 5-15 CU A002 15A M A N T A T E S T S Y S T E M S...
  • Page 156: Fault Incidence Angle Control

    120° apart). If this isn’t the case, a correction may be required to program the fault incidence angle properly. 5-16 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 157: Synchronizing Mode

    B R E A K E R A D V A N C E Φ = + 1 5 . 4 ° T I M E : 1 0 3 m s MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 5-17 CU A002 15A...
  • Page 158: Phase Sequence

    Use RMS measurement in PREFAULT state, and high-speed peak responding measurement in FAULT state. 5-18 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 159: Default Settings

    Auto-reclose delay If in manual control mode, the current mode, fault mode, fault type, fault phase and current mode selected will be the one selected on the front panel. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 5-19 CU A002 15A M A N T A T E S T S Y S T E M S...
  • Page 160: Other Default Settings

    This is the default data displayed in the [MODE/MENU DISPLAY] when the menu is not active. This is described in Figure 3.3. 5-20 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 161: Multiple Readings Display

    Φ - Φ A - B 5.10.3.1.1 Z1 gnd display This display mode shows the positive sequence impedance (Z1) for phase-ground faults directly. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 5-21 CU A002 15A M A N T A T E S T S Y S T E M S...
  • Page 162 5. Exit the menu. Z1gnd is now displayed. Adjust the fault voltage, current, and phase angle for relay pickup. 5-22 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 163: Automatic Impedance Display Selection

    This feature is similar to the automatic impedance display selection mode described in 5.10.3.1.2 above, except that the reactive component of the positive sequence impedance is displayed. To use this feature, select DISP RATIOS IMPEDANCE AUTO X1 in the menu. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 5-23 CU A002 15A...
  • Page 164: Current Ratio Display

    The ratio is calculated using the present values of the I1 and I2 current readings, and is only available in I1& I2 current mode. 5-24 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 165: I1 & I2 Ct Taps For Current Ratio Displays

    While the breaker time is shown on the [MODE/MENU DISPLAY], pressing the [TIME] button toggles between display in seconds and cycles. 5.11.2 Auto-Reclose Simulation 5.11.2.3 AUTO-RECLOSE TIME DELAY. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 5-25 CU A002 15A M A N T A T E S T S Y S T E M S...
  • Page 166: Reclose Into Fault

    This feature is only applicable in dynamic operation mode. The number of reclose-into-fault events is programmed under the SETTINGS POSTFAULT RECLOSE RECLOSE-INTO-FAULT selection in the menu. 5-26 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 167: Trip Type

    T I M E D E L A Y T O A U T O - R E C L O S E : 2 0 . 0 C Y C MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 5-27 CU A002 15A...
  • Page 168: Pt Location

    Note that, if individual amplitude adjustment mode is set, all outputs will be zero during the reclose delay interval, regardless of the PT location setting. 5-28 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 169: Examples

    4 cycles Trip type: 3-Φ Auto-reclose time delay: 11 cycles PT location: bus side MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 5-29 CU A002 15A M A N T A T E S T S Y S T E M S...
  • Page 170: Phase Adjustment Mode

    The default setting is “Normal” where phase adjustment automatically adjusts the appropriate current(s) and/or voltage(s). This is dependent upon the current mode. 5-30 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 171: Individual Phase Adjustment Modes

    Example vector configurations possible using individual phase adjustment modes FIGURE 5.13 INDIVIDUAL PHASE ADJUSTMENT MODES MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 5-31 CU A002 15A M A N T A T E S T S Y S T E M S...
  • Page 172: Menu Control Of Individual Phase

    The individual phase adjustment menu tree for I1-LOW and I1-HIGH current modes is summarized in the following figure: 5-32 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 173: I2-Harmonic Current Mode Individual Phase Adjustment

    V C : 1 2 0 . 0 ° I 2 : 3 0 . 5 ° Repeat this, as desired, for all phases, and for each of the prefault, fault and postfault states. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 5-33 CU A002 15A...
  • Page 174: I1&I2 Current Mode Individual Phase Adjustment

    Repeat this, as desired, for all phases, and for each of the prefault, fault and postfault states. 5-34 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 175: I3 Current Mode Individual Phase Adjustment

    V C : 1 2 0 . 0 ° I 3 : 3 0 . 5 ° Repeat this, as desired, for all phases, and for each of the prefault, fault and postfault states. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 5-35 CU A002 15A...
  • Page 176: I3-Wye Current Mode Individual Phase Adjustment

    V O L T A G E C U R R E N T 5-36 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 177 A : 3 3 0 . 0 ° i B : 2 4 0 . 0 ° i C : 1 6 3 . 5 ° MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 5-37 CU A002 15A M A N T A T E S T S Y S T E M S...
  • Page 178: Non-Menu Control Of Individual Phase

    When the phase adjustment mode is set to “Individual-Voltage”, the output phase which is changed is determined by the table on the next page: 5-38 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 179 I2-AMPS) I2-HARMONIC * May be prefault, fault or postfault setting, depending upon present fault state. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 5-39 CU A002 15A M A N T A T E S T S Y S T E M S...
  • Page 180: Viewing Phase Settings

    SETTINGS MODES PHASE INDIVIDUAL-ADJ-MODE ADJUST PREFAULT SETTINGS MODES PHASE INDIVIDUAL-ADJ-MODE ADJUST FAULT SETTINGS MODES PHASE INDIVIDUAL-ADJ-MODE ADJUST POSTFAULT 5-40 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 181: Special Notes

    B : 2 4 0 . 0 ° v C : 0 0 0 . 0 ° I 1 : 0 0 0 . 0 ° MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 5-41 CU A002 15A M A N T A T E S T S Y S T E M S...
  • Page 182: Voltage Limit Test

    [PHASE] button which will display the reverse angle. Note that the units annunciator in the [MODE/MENU DISPLAY] reads “DEG+180”. 5-42 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 183: Phase Angle Measurement Reference

    This is annunciated by the “DEG:I-V” units indicator in the upper left corner of the [MODE/MENU DISPLAY], when phase is selected. Example: MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 5-43 CU A002 15A M A N T A T E S T S Y S T E M S...
  • Page 184: Aux Contact Output Arrangement

    However, in some situations, it may be desirable to invert this so that the [AUX CONTACT] output is normally closed, and opens during fault state. Select NC arrangement in these cases. 5-44 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 185: Breaker Simulation 52A/52B

    DC voltage supply. This is useful for testing communication-based scheme protection relays. [AUX CONTACT_2] does not support this feature. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 5-45 CU A002 15A...
  • Page 186: Auxiliary Contact Delay

    5-46 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 187: Rs-232C Interface

    Shielded cable should be used between the external device (computer), and the MTS-1710. The shield should be connected to the frame (earth) ground. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 188: Com2 Port

    The standard CONTROL-S (ASCII 19) and CONTROL-Q (ASCII 17) characters are used to pause and resume data output from the MTS-1710. These may be used manually, if desired, to pause the display. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 189: Command Descriptions

    For experimentation or learning purposes, the RS-232C interface operates in an easy-to-use, conversational or ‘terminal’ mode. When using a computer, the computer should be running terminal ® ® emulation software such as Manta Test Systems’ Powerterm, PROCOMM or Windows ‘95 Hyper Terminal.
  • Page 190 The delay value is programmed with the maximum expected relay operation time. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 191: Fault Mode Control

    • This command is disallowed when Φ-Φ fault type is selected. See example for use in Φ-Φ fault mode. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 192 • Valid values are 0 - 99.999 (seconds) • A value of 0 turns off voltage fault duration. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 193: Examples

    Example 2 Simple Φ-Φ Fault FMDO <- simulate A-N fault <- set prefault Φ-N amplitudes to 70V AVA70 AVB70 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 194 <- final fault amplitude at 15% of nominal VRR24 <- ramp rate at 24%/sec <- initiate fault and ramp MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 195: Current Control

    Valid values are 0 - 30.00 (amps). • This value is only used for I1-LOW, I1-HIGH I3, and I3-WYE current modes. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 196 − Each channel is set to one-third of the programmed value. 6-10 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 197 • Valid values are 0 - 5.000 Amps. • Note: Settable only when %HM# and %HP# are set to zero. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 6-11 M A N T A T E S T S Y S T E M S...
  • Page 198: Commands Used In I3-Wye Current Mode

    • In I3-WYE current mode, the value must be specified in Φ-N amperes, regardless of the fault mode. 6-12 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 199: Examples

    <- dynamic operation mode <- initiate fault NOTE: For examples of programming in I3-WYE current mode, see Section 9.6. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 6-13 M A N T A T E S T S Y S T E M S...
  • Page 200: Phase Control

    (The phase display mode may be set differently and read a different value). 6-14 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 201: Examples

    AVA70 <- prefault voltages at 70V AVB70 AVC70 AI12 <- 2.0A prefault current PHS0 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 6-15 M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 202: Frequency Control/Programming

    • This command only takes effect in variable frequency reference mode. 6-16 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 203: Examples

    <- select variable frequency reference mode VHM1 <- select fundamental <- dynamic operation mode for dynamic test MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 6-17 M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 204 <- fault initial freq. at 59.2 Hz FFF58 <- fault final freq. at 58 Hz 6-18 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 205: Control

    This mode is used for simple tests, demonstrations, and very simple control applications. It’s ideal for use with the terminal emulator feature of Powercomm. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 6-19 M A N T A T E S T S Y S T E M S...
  • Page 206: Timer & Tone Control

    • DCU3, DCU4 and DCU5 selects I2, %-harmonic and DC-AMPS current respectively to be displayed in I2-Harmonic current mode. 6-20 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 207 • Prints the present timer reading (in cycles) Print Voltage • Prints the present value of voltage (in volts) MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 6-21 M A N T A T E S T S Y S T E M S...
  • Page 208: Clock/Calender Control

    • Specify the numerical values of month, day, year (e.g. MDY 11,4,91 sets the date to Nov. 4, 1991) 6-22 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 209: Fault Playback Commands

    • Sets the fault playback rate. This should be set to be equal to the sample rate of the rate of the fault waveform to be played back. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 6-23 M A N T A T E S T S Y S T E M S...
  • Page 210: Programmable Waveform Commands

    VmaxRMS) for voltages or (1/127 x ImaxRMS) for current 255 = Vmax for voltages or x Imax for current 6-24 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 211: Usage

    <- second data point (use repeat last command feature) <- data point at 1 degree <- data point at 1.5 degrees MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 6-25 M A N T A T E S T S Y S T E M S...
  • Page 212: Example - 14 Bit Data

    The following is an example usage of the programmable waveform commands which redefine the sine wave output to a triangular wave. 6-26 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 213 <- remote control mode PWC0 <- programmable waveform off <- return to local control mode MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 6-27 M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 214: Dc Voltage Control

    • The new setting is retained in non-volatile memory, and takes effect until changed again. 6-28 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 215 CTRL - L CTRL - M CTRL - N CTRL - O CTRL - P MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 6-29 M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 216: Other Commands

    6.2.17 Other Commands Command Description CAL# Calibration • Calibration save enable/disable • Valid values are 0-5 6-30 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 217 4 - reserved for factory use only 5 - reserved for factory use only VER1 Version (MTS-1710) • Print Manta Test Systems MTS-1710 model number, firmware version and serial number VER2 Version (MTS-1720) • Print Manta Test Systems MTS-1720 model number, firmware version and serial number, if it’s connected and turned on.
  • Page 218 5 - Mode display with I1÷I2 ratio 6 - Mode display with I2÷I1 ratio 6-32 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 219 • Print the last settings of all AC outputs in a phasor table format. • Example: Ready>PHT VA,069.27,000.0 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 6-33 M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 220 • Note that the currents values in I3-WYE current mode, and the voltage values, are the settings, and not measured values. The phasors, which are output, will change, depending upon the current mode. • Manta Test Systems’ MTS-2100 Powerscope program uses this to produce a real-time display of the phasors. AXC#,# AUX Contacts Arrangement •...
  • Page 221: Relationship Between Manual Settings And Rs-232C Commands

    Example 1: The following command sequence polls the MTS-1710 status five times. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 6-35 M A N T A T E S T S Y S T E M S...
  • Page 222: Command Summary

    Set voltage - duration VFF# Set voltage - fault final VDF# Set voltage - default 6-36 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 223: Current Control

    25Hz frequency reference mode 6.5.9 RS-232 Control Auto line feed off Auto line feed on MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 6-37 M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 224: Timer & Tone Control

    6.5.13.1 COMMANDS FOR 8-BIT FAULT PLAYBACK. RCD#,#,#,# Playback data RCM# Playback mode RCR# Playback rate 6-38 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 225: Commands For 14-Bit Fault Playback

    Positive phase sequence FIA# Fault incidence angle Default settings DMD# Display mode data Z1K# Z1 K-factor MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 6-39 M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 226: Individual Phase And Amplitude Programming

    All settings must be set by the appropriate RS-232 commands. 6-40 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 227: Programming Individual Phase/Amplitude For The Mts-1710

    DMM# Synchronizing mode SYN0 Auto-reclose delay TDR# * I2-Harmonic and I1&I2 current modes only MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 6-41 M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 228: Individual Phase/Amplitude Settings Map

    • When individual amplitude adjust mode is set, all usual amplitude adjustments, except for prefault Φ-N settings, will be disabled. 6-42 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 229 • This command is only valid in individual amplitude adjustment mode. • This command is only valid in I1&I2 and I2-HARMONIC current modes. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 6-43 M A N T A T E S T S Y S T E M S...
  • Page 230: Examples

    PHS240,2,3 AI10,0 PHS0,0,4 AI111.75,1 PHS287.2,1,4 AI10,2 PHS0,2,4 An STR command will initiate the fault. 6-44 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 231 PHS-6,0,4 AI15,1 PHS-60,1,4 AI2.5,0 PHS84,0,5 AI25,1 PHS30,1,5 An STR command will initiate the fault. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 6-45 M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 232: Special Notes

    When the MTS-1720 is connected to the MTS-1710--and is active--(I3-WYE current mode selected), the individual phase and amplitude can be programmed for full 3Φ voltage and current. 6-46 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 233 1 - fault phase 2 - postfault phase • Third argument specifies the output. Valid values are 1 - 6. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 6-47 M A N T A T E S T S Y S T E M S...
  • Page 234: Individual Amplitude Programming Commands

    2 - postfault Ic • This command is only valid for I3-WYE current mode. 6-48 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 235: Examples

    PHS125.4,2,5 AIC1.96,0 PHS5.4,0,6 AIC2.03,1 PHS-2.2,1,6 AIC1,2 PHS5.4,2,6 An STR command will initiate the fault. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 6-49 M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 236: Special Notes

    When using individual phase and amplitude programming for the MTS-1710 + MTS-1720 Two channel current source, the same special notes apply, as described in Section 6.7.1.5. 6-50 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 237: Fault Playback

    The maximum record length (in cycles) which can be reconstructed in this mode is given by: Length [cycles] = 60,000 x line freq [Hz] sample freq [Hz] MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 238: Internal Data Repetitive Mode

    For voltage outputs: Vout = D - 128 x Vmax RMS where 1 ‹ D ‹ 255 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 239: Example For The Mts-1710+Mts-1720 - 8 Bit

    ±99.0V on Va, ±130.8V on Vb, ±101.8V on Vc, ±28.3A on Ia, ±14.7A on Ib, and ±9.76A on Ic. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 240 RCD128,45,176,201,8,107 1.56 -86.52 39.29 16.48 -13.78 -1.84 RCD130,44,177,202,9,104 2.34 -90.64 40.09 18.04 -13.55 -2.00 RCD131,40,178,209,11,102 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 241: Example For The Mts-1710+Mts-1720 - 14 Bit

    70.0V on Va, 92.5V on Vb, 72.0V on Vc, 20.0A on Ia, 10.4A on Ib, and 6.9A on Ic, the following commands specify three consecutive samples. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 242: Determining Playback Data Values - 8 Bit

    I1 (in I1-LOW current mode), or a phase or line current (in I3 current mode). MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 243: Determining Playback Data Values - 14 Bit

    I1 (in I1-LOW current mode), or a phase or line current (in I3 current mode). MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 244: Fault Playback In I3-Parallel Current Mode

    Note: The frequency mode must be set to line frquency for correct waveforms playback. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 245: Required Settings For Fault Playback

    Download fault data (Va, Vb, Vc, Ia, Ib, Ic) RCD#,#,#,#,#,# <- repeat for up to 60,000 samples RCD#,#,#,#,#,# MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 246: Operation In Various Fault Modes

    Digital outputs from the MTS-1710, and signals from the system under test, can be recorded using this function. 7-10 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 247: External Data Mode Usage

    4. Initiate analog playback from the computer. 5. Press [STOP/RESET], or send the RES command to reset the MTS-1710 fault state back to prefault. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 7-11 M A N T A T E S T S Y S T E M S...
  • Page 248 FAULT PLAYBACK - Section 7 7-12 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 249: Fuse Replacement

    To replace, remove the plastic cap, pull the ejection lever to eject the existing lamp, and insert the new lamp. 8.3 FIRMWARE UPGRADE The firmware is upgradable through a serial communication port at the back of the MTS-1710. Call Manta Test Systems to obtain the correct firmware version for your particular unit. The following procedure de- scribes the use of Hyperterminal as the terminal program.
  • Page 250: Generation Calibration

    232 interface to enable saving of the calibration factors. A 0.1% accurate external reference meter is required to perform the calibration. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 251: Ac Voltage Generation Calibration

    Select OTHER SERV CALIBRATION GENERATION IA in the menu. Turn the [MODIFY] knob to adjust the calibration factor until the reference meter reading is 10.000A ±0.025A. Press [SELECT]. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 252: Ac Current I3 Generation Calibration

    8.4.4 VDC VOLTAGE GENERATION CALIBRATION This applies only to units with the DC option installed. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 253: Measurement Calibration

    A 0.1% accurate external reference meter is required to perform the calibration. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 254: Ac Voltage Measurement Calibration

    2. Press [CURRENT], adjust the current down to 0, and then slowly up to 5.0A (as read on an external reference meter). MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 255: Ac Current (I1-High) Measurement Calibration

    (the output current doesn’t change when this is done). Press [SELECT]. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 256: Dc Current Measurement Calibration

    3. Press [CURRENT], adjust the current down to 0, and then slowly up to 6.0A (as read on an external reference meter). MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 257 10. Set the dynamic measurement mode to PEAK (see section 5.1.1), and the operation mode to DYNAMIC. Press [FAULT]. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 258: Ac Current (I3) Measurement Calibration (Φ−Φ Values)

    Press [SELECT]. 6. Exit the menu, and adjust the IAB current to 40A. 8-10 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 259: Dc Voltage Measurement Calibration

    5. When done, the CAL1 command must be sent via the RS-232C interface to enable saving of the calibration factors. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 8-11 M A N T A T E S T S Y S T E M S...
  • Page 260: Time Measurement Verification

    1. Unplug the MTS-1710. Observe proper antistatic handling procedures. Ground the MTS-1710 case by connecting the rear panel ground stud to a secure earth ground. 8-12 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 261: Led/Lamp Test Function

    To check the [TONE] pushbutton LED, short the [EXTERNAL STOP] trigger contact sense input terminals, and this button should light. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 8-13 M A N T A T E S T S Y S T E M S...
  • Page 262 SERVICING - Section 8 8-14 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 263: Mts-1720 Two Channel Current Source

    40.00 -80.00 Hz (0.001 Hz resolution, 0.01% accuracy) 80.00 - 800.00 Hz (0.01 Hz resolution, 0.02% accuracy) MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 264: Metering

    8 bit: 8 bit dynamic + 12 bit scaling 14 bit: 14 bit dynamic + 16 bit scaling • Peak output levels: ±42.4A MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 265: Physical Characteristics

    Indicates that the MTS-1720 is synchronized to the MTS-1710 and ready to provide output. [POWER] SWITCH. This switch turns on the MTS-1720. POWER LED. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 266: Rear Panel Layout

    9. SAFETY FRAME GROUND TERMINAL 10. [SLAVE CURRENT] CONNECTOR This connector carries the current outputs to the MTS-1710. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 267: Getting Started

    1710 and MTS-1720. • Connect the [COM3 SLAVE CURRRENT] port of the MTS-1710 to the MTS-1720 [COM1 TO MTS- 1710 PORT], using the provided cable. (Use only a Manta Test Systems supplied cable. This is NOT a standard RS-232 cable). •...
  • Page 268: Enabling Mts-1720 Output

    OUTPUT] terminals. This is annunciated by “I3-WYE” in the lower right hand corner of the [MODE/ MENU DISPLAY], as opposed to “I3” without the MTS-1720 connected. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 269: Typical Full Three-Phase Relay Connections

    FIGURE 9.4 TYPICAL FULL THREE-PHASE RELAY CONNECTIONS A typical three-phase relay is connected to the MTS-1710, as shown in Figure 9.4. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 270 Impedance relays with neutral or residual current coils (such as those by GEC) should be connected, as shown in Figure 9.5. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 271: Special Notes

    If the MTS-1720 is turned off, the system reverts to I3 current mode using the MTS-1710 only. The relay connections are the same for both current modes. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 272: Precautions

    Note that the current neutral terminal must always be connected as the return path for every output. 9-10 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 273: Three-Phase Current Operation (I3-Wye Current Mode)

    [FAULT PHASE] selector. For example, if a 2Φ-N fault is set up for A-B-N, the identical conditions can be applied to B-C-N and C-A-N by rotating the [FAULT PHASE] selector to these positions. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 9-11...
  • Page 274: Phase-Ground Fault

    Once the fault voltage, current and phase angle are set, they can be applied to any desired phase (A-N, B- N, or C-N) by changing the [FAULT PHASE] selector. 9-12 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 275 (Ia, Ib, Ic). In all fault states, the interphase angles on the voltages and currents are 120°. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 9-13 M A N T A T E S T S Y S T E M S...
  • Page 276: N Fault Type

    In the prefault state, the interphase angles on the voltages and currents are set to 120°. 9-14 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 277: Two-Phase-To-Ground Fault

    Once the fault voltage, current and phase angle are set, they can be applied to any desired phase (A-B-N, B- C-N, or C-A-N) by changing the [FAULT PHASE] selector. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 9-15 M A N T A T E S T S Y S T E M S...
  • Page 278: Displayed Quantities

    All possible combinations are shown in the chart on the following page: 9-16 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 279: Simultaneous Ac & Dc Currents

    Select I4-DC current mode and Φ-N/B-N fault mode. Connect the relay, as shown in Figure 9.12. (The C-N [I3 OUTPUT] is also available in case a DC current and two AC currents are required). MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 9-17...
  • Page 280 If the above is done in the FAULT state instead of prefault, and the DC current is preset (to 0.2A or 2.0A), a complete dynamic test may be performed which simulates real world operation. 9-18 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 281: Testing High Burden Current Differential Relays

    Individual phase adjust must be enabled first via SETTINGS MODES PHASE INDIVIDUAL-ADJ-MODE ENABLE INDIV-CURRENT. The phase angle can then be set by pressing previous and selecting ADJUST FAULT. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 9-19 M A N T A T E S T S Y S T E M S...
  • Page 282: Use Of Impedance Display

    Φ-G, Φ-Φ, and 3Φ elements directly. To avoid selection of the incorrect formula, select DISP RATIOS IMPEDANCE AUTO in the menu. 9-20 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 283: Application Of Advanced Capabilities

    I3 current mode. No changes to the connections to an external relay are necessary between the two modes. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 9-21 M A N T A T E S T S Y S T E M S...
  • Page 284: Current Programming

    <- fault voltage 15V VFI15 <- initial fault current 5A IFI5 <- initiate fault 9-22 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 285 <- initial fault current 6A (10.4A phase-to-phase) IFI6 <- postfault current 1A (1.73A phase-to-phase) IPO1 <- initiate fault MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 9-23 M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 286 <- final fault current 15A (21.2A phase-to-phase) IFF15 <- ramp currents at 4A/sec IRR4 9-24 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 287: Fault Playback

    The MTS-1720 firmware is upgradable through a serial communication port at the back of the MTS-1710. Call Manta Test Systems to obtain the correct firmware version for your particular unit. The procedure in section 8.1 describes the use of Hyperterminal as the terminal program to upgrade the unit.
  • Page 288 MTS-1720 TWO CHANNEL CURRENT SOURCE - Section 9 9-26 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 289: Mts-1750 High Current Source

    • 19"W x 6.25"H x 18.75"D (48.3 cm W x 15.9 cm H x 47.6 cm D) • Weight: 53.7 lbs. (24.4 kg) • Built-in carry handle/tilt stand MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 10-1 M A N T A T E S T S Y S T E M S...
  • Page 290: Accessories Included

    POW ER AUX. CURRENT INPUT HIGH CURREN T SOURCE FIGURE 10.1 MTS-1750 FRONT PANEL 10-2 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 291: Rear Panel Layout

    Connect to a solid earth ground. 4. [AC RECEPTACLE] This is the main AC input receptacle. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 10-3 M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 292: Operation

    Select I1-LOW current mode on the MTS-1710. • Turn on the MTS-1710 and MTS-1750. 10-4 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 293: Enabling Mts-1750 Output

    N O M T S - 1 7 5 0 D E T E C T E D [ i a i b i c ] MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 10-5 M A N T A T E S T S Y S T E M S...
  • Page 294: Operation With The Mts-1710 + Mts-1750 Configuration

    • Connect the [COM3 SLAVE CURRENT] port of the MTS-1710 to the MTS-1720 [COM1 TO MTS- 1710 PORT], using the RS-232 cable provided. (Use only the Manta Test Systems supplied cable). This is NOT a standard RS-232 cable). •...
  • Page 295: Mts-1750S Configuration & Single Phase Output

    • Turn on the MTS-1710, MTS-1720 and MTS-1750s. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 10-7 M A N T A T E S T S Y S T E M S...
  • Page 296: Current Adjustment And Display

    IRR, IPO commands (see Section 6.2.6.1), with the exception that the maximum value is 450A. 10-8 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 297: Mts-1750S Configuration & Three Phase Output

    10-6. FIGURE 10.8 MTS-1710 + MTS-1720 + (3)MTS-1750 THREE PHASE CURRENT CONNECTIONS MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 10-9 M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 298: Current Adjustment And Display

    (150A maximum), and the current phase angle is programmed by the PHS#,#,4 command. 10-10 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 299: Fault Playback With The Mts-1750

    Short together pin 12 (ground) to pin 8 (Amplifier enable). Pin 8 is the amplifier enable and is active low. Shorting this pin to ground forces will always enable the amplifiers. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 10-11 M A N T A T E S T S Y S T E M S...
  • Page 300 All adjustments, including amplitude, frequency and general signal shape, are controlled by the function generator. 10-12 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 301 • 19"W x 6.25"H x 18.75"D (48.3 cm W x 15.9 cm H x 47.6 cm D) • Weight: 53.25 lbs. (24.15 kg) • Built-in carry handle/tilt stand MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 11-1 M A N T A T E S T S Y S T E M S...
  • Page 302 5. ALARM LEDS Indicate overload of the respective current outputs when illuminated. 11-2 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 303 This is the main AC input receptacle. 5. SAFETY FRAME GROUND TERMINAL Connect to a solid earth ground. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 11-3 M A N T A T E S T S Y S T E M S...
  • Page 304: Mts-1710 + Mts-1720 + Mts-1753 Configuration

    The standard MTS-1710 + MTS-1720 connections are shown in gray. Additional connections required for the MTS-1753 are shown in black. 11-4 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 305 Select the I3 current mode on the MTS-1710. • Turn on the MTS-1710, MTS-1720 and MTS-1753. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 11-5 M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 306: Enabling Mts-1753 Output

    The fault current can be set without applying it to the load by using the fault current preset feature (see Section 4.6.9). 11-6 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 307: Features

    Output Low Voltage 0.4V Output High Current (sourcing) -200uA -1500uA Output Low Current (sinking) 3.2mA MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 14A...
  • Page 308: A.4 Physical Specifications

    The signal ground is the same ground as the ground of the MTS-1710 voltage and current outputs. Output isolation is provided by the MTS-1730 Input/Output Signal Conditioner (Option -03B). MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 309: Operation

    The following section describes the use of the RS-232C command set for controlling the digital I/O channels: MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 310: Interpretation Of Logic Values

    0 - hexadecimal (for example, E29B) 1 - binary (for example, 1110001010011011) 2 - decimal (for example, 58011) MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 311: Digital Input Control

    • Reads status of all 16 inputs and returns 16 bit result • Example: (assuming hex format initially selected) Ready>DIO,INP 0F29 Ready>DIO,FMT1 Ready>DIO,INP 0000111100101001 Ready> MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 312 • Valid values are 0 - 20000 ms. The default value is 100ms. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 313: Digital Output Control

    The leading zeros in this command could be eliminated, leaving the command to read as follows: DIO,OUT0,H8,HF • The comma after the command “OUT” is optional. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 314 • This command responds to changes; not to constant levels. (i.e. if the condition already has been met, the outputs won’t change) MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 315: Applications

    It’s cleared when the MTS-1710 is returned to the prefault state. • Recording is only performed in dynamic operation mode. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 316: A.6.5.2 Examples

    (b) Example 2 Channel 25 40 (c) Example 3 FIGURE A-1. DIGITAL OUTPUT EXAMPLES A-10 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 317: A.6.6 Phase Comparison Output Programming

    • 0 = disabled (AUXOUT15 becomes normal digital output) • 1 = enabled (AUXOUT15 becomes programmable square waveoutput) • The default value is 0 (disabled) MTS-1700 SERIES OPERATION AND REFERENCE MANUAL A-11 M A N T A T E S T S Y S T E M S...
  • Page 318: Examples

    <- postfault phase comparison output disabled DIO,PCP2,0 DIO,OUT2,0,H8000 <- force postfault value to zero A-12 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 319: Commands

    Sequence of events report Status DIO,STA DIO,INP Read Inputs DIO,POI Postfault inputs * Indicates multiple definitions possible. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL A-13 M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 320 PROGRAMMABLE DIGITAL I/O CHANNELS A-14 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 321: Mts-1730 Digital Input/Output Signal Conditioner

    • Sequence of events recording • Routing of currents and voltages for testing multiple elements MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 322: Ordering Information

    Hardshell shipping case • Option -14 Cordura carry case • Option -14 19” Rackmount enclosure MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 323: Front Panel

    DC/AC voltage sensing input from 10 to 300V peak at greater than 50k ohms impedance. 7. OUTPUT MODULE Four channel output module with five-way binding posts. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 324: Rear Panel

    Conditioned input channel signals. Connect to the MTS-1710 [AUX INPUTS] connector, using the appropriate cable. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 325: Channel Assignments And Special Functions

    When this feature is desired, the output module should be a high speed type (Option -03D2 or -03D3). MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 326: Four-Channel Input Module

    You can change the logic input voltage level to 5V, if required, for interfacing to 5V logic. The proper location of these jumpers is shown in the figure on the next page: MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 327: B-4 Configuration Jumpers For Input Sense Levels On Four-Channel Input Modules

    5V logic input sensing FIGURE B-4. CONFIGURATION JUMPERS FOR INPUT SENSE LEVELS ON FOUR-CHANNEL INPUT MODULES MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 328: 16-Channel Input Module

    5 V L O G I C 1 2 V L O G I C FIGURE B-5. MTS-1730 16-CHANNEL INPUT MODULE MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 329: Connector Pinout

    C14 (channel 14 contact in) V14 (channel 14 voltage in) V15 (channel 15 voltage in) COMMON MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 330: Input Bank Configuration And Numbering

    RJ1, RJ3, RJ6 Bank Bank Bank Bank (and remove U2 and U3 IC’s) 16 channel modules B-10 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 331: Active Input Bank Selection

    6 A4 contacts Direct close optocoupler input 7 A3 contacts Block trip optocoupler input MTS-1700 SERIES OPERATION AND REFERENCE MANUAL B-11 M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 332: B-6 Example Connections Of Mts-1730 To Sel-121G Distance Relay

    TRIP TRIP CLOSE SEL-121G FIGURE B-6. EXAMPLE CONNECTIONS OF MTS-1730 TO SEL-121G DISTANCE RELAY B-12 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 333: Alphabetical Rs-232 Command Summary

    Digital I/O delayed output definition A.6.5.1 DIO,ORD Digital I/O read outputs A.6.5.1 DIO,OUT#,#,# Digital I/O output definition A.6.5.1 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 334 IPR# Set prefault current 6.2.6.2 IRR# Set current ramp rate 6.2.6.1 Internal timer start 6.2.10 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 335 Remote end trip 6.2.17 RIF# Reclose into fault events 6.2.17 Real time clock reset 6.5.12 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 336 6.2.5.1 WFS# Wait on fault state 6.2.2 External timer start 6.2.10 Z1K# Z1 K-factor 6.2.17 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 337: E.1 Introduction

    3. Start the program (SYNCSCOP.EXE) from the program icon, or from Windows [Start] menu. 4. When prompted, select the MTS-1710 as the equipment type. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 338: E.3.2 Synchroscope Graph

    2. Turn the [MODIFY] knob to adjust the voltage up and down to find the voltage limit of the synchronizing element. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 339: E.3.6 Frequency Limit Test

    Vc voltage and nominal frequency. These values are used as the defaults for setting up the phase, voltage and frequency limit tests. MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S...
  • Page 340 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 341 (4.6.6) External Trigger An external start or stop trigger action. (4.5.4, 4.5.5) MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 342 All other amplitudes are automatically set by the under computer or external device control. (6.2.1) MTS-1710 to simulate standard faults (4.7) MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 343 45Hz to 650 Hz. (4.10.1.2) MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 344 GLOSSARY MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 345 COM1 6-1, 6-2, 6-20, 6-28, 6-29, E-1 18, 4-23, 4-24, 5-21, 6-12, 8-8, 9-17, 9- 18, II-6, II-7, JJ-5, JJ-6, KK-9 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL MM-1 M A N T A T E S T S Y S T E M S...
  • Page 346 5-41, 6-5 to 6-8, 6-12 to 6-14, 6-16, 6-32, 6-36, 6-40, 7-10, 7-11, 8-3, 8-4, 8- MM-2 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 347: Memory Voltage Polarization Tests

    J-1, 10 to 9-12, 9-19 to 9-24, 10-9, 10-10, see also impedance relay MTS-1700 SERIES OPERATION AND REFERENCE MANUAL MM-3 M A N T A T E S T S Y S T E M S...
  • Page 348 5-12, 5-19, 6-4, 6-5, 6-35, 6-40, 6-41, 4-46, 4-47, 5-17, 5-25 to 5-28, 5-32 to MM-4 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...
  • Page 349 Internal start mode 5-12 RS-232C interface 6-1, 6-2, 11-1 three-phase fault 4-34, 9-23, 9-24, II-1, II-9, II- MTS-1700 SERIES OPERATION AND REFERENCE MANUAL MM-5 M A N T A T E S T S Y S T E M S...
  • Page 350: Trip Duration Tests

    3-15, 3-17, 3-38 XON/XOFF 2-4, 6-1, 6-2 zero sequence compensation factor 5-22 MM-6 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL M A N T A T E S T S Y S T E M S CU A002 15A...