BG-12 Manual Pull Station
Patented, U.S. Patent No. Des. 428,351; 6,380,846; 6,314,772; Other Patents Pending
Document 50964-1
Description
The BG-12 pull station is a non-coded, dual-action manual pull station with a hex-lock reset
feature. It provides Fire•Lite control panels with one normally open (N/O) alarm initiating
input. The BG-12 meets the ADAAG controls and operating mechanisms guidelines (sec-
tion 4.1.3[13]), and the ADA requirement for a 5 lb. maximum pull force to activate the pull
station. Operating instructions are molded into the pull station handle along with Braille
text. Molded Terminal numbers are also present.
Ratings
Switch contact (N/O) is gold plated for reliability and rated at 0.25 A at 30 volts (AC or
DC).
Installation
The BG-12 pull station can be surface mounted to an SB-10 or SB-I/O surface backbox or
semi-flush mounted on a standard single-gang, double-gang or 4" (10.16 cm) square electrical
box. The optional BG-TR trim ring can be used if the BG-12 is to be semi-flush mounted.
Operation
To activate the dual-action pull station, push in and pull down on the handle. The word
'ACTIVATED' appears after the handle is pulled down. This will remain until the pull sta-
tion is reset.
The pull station includes one Single Pole, Single Throw (SPST) Normally Open (N/O)
switch which closes upon activation of the pull station.
Resetting the Pull Station
1. To reset the BG-12 hex lock pull station, insert the supplied 9/64-inch hex wrench into
the lock until firmly seated and turn counterclockwise 1/4-turn.
2. Open the door until the handle returns to normal.
3. Close and lock the door.
NOTE: Closing the door automatically resets the switch to the 'Normal' position. Open-
ing the door will not activate or deactivate the alarm switch.
Wiring
FROM
FACP +
IDC –
1
STRIP GAUGE
I56-2263-003
WARNING: DO NOT LOOP WIRING
UNDER ANY TERMINALS. BREAK WIRE
RUN TO MAINTAIN IDC SUPERVISION.
WARNING! Do not loop wiring under any
terminals. Break wire run to
maintain IDC supervision.
CAUTION! Do not detach the door of the pull station during installation. The door of
the pull station cannot be reattached to the backplate after the backplate has already been
installed onto an electrical box.
CAUTION!
Install the Fire•Lite BG-12 pull station in accordance with these instructions,
applicable NFPA standards, national and local Fire and Electrical codes and the requirements
of the AHJ (Authority Having Jurisdiction). Regular testing of the devices should be con-
ducted in accordance with the appropriate NFPA standards. Failure to follow these directions
may result in failure of the device to report an alarm condition. Fire•Lite is not responsible for
devices that have been improperly installed, tested or maintained.
ADA Compliance
For ADA compliance, if the clear floor space only allows forward approach to an object, the
maximum forward reach height allowed is 48 inches (121.92 cm). If the clear floor space
allows parallel approach by a person in a wheelchair, the maximum side reach allowed is
54 inches (137.16 cm).
TO NEXT
+
DEVICE
Document 50964-1
– IDC
2
3
4
BG-12
Manual Pull Station
I56-2263-003