Description
The BG-12LPS pull station is a non-coded, dual-action manual pull station with a key-lock reset
feature. It provides Fire•Lite control panels with two (2) normally open (N/O) alarm initiating
input signals. "Pre-signal" input is activated by pushing in, then pulling down the dual action
handle. A "General" alarm input signal can be manually activated via a momentary rocker switch
mounted inside the unit. This general alarm switch can only be accessed by opening the cover
with the supplied key/lock.
The BG-12LPS meets the ADAAG controls and operating mechanisms guidelines (section
4.1.3[13]), and the ADA requirement for a 5 lb. maximum pull force to activate the pull station.
Operating instructions are molded into the pull station handle along with Braille text. Molded
Terminal numbers are also present.
Ratings
Switch contacts (N/O) are gold plated for reliability and rated at 0.25 A at 30 volts (AC or
DC).
Installation
The BG-12LPS pull station can be surface mounted to an SB-10 or SB-I/O surface backbox
or semi-flush mounted on a standard double-gang or 4" (10.16 cm) square electrical box. The
optional BG-TR trim ring can be used if the BG-12LPS is to be semi-flush mounted.
Operation
To activate the dual-action pull station, push in and pull down on the handle. The word
'ACTIVATED' appears after the handle is pulled down. This will remain until the pull station
is reset.
The pull station includes two independently operated Single Pole, Single Throw (SPST) Normally
Open (N/O) Switches for pre-signal/ general alarm applications.
Resetting the Pull Station
1. Insert the key into the lock and rotate 1/4 turn counterclockwise.
2. Open the door until the handle returns to normal.
3. Close and lock the door.
Note: Closing the door automatically resets the switch to the 'Normal' position. Opening the
door will not activate or deactivate the pre-signal toggle switch.
Wiring
To Next Pre-Signal +
Device on IDC –
From FACP +
Pre-Signal IDC –
1
I56-2268-003
STRIP GAUGE
WARNING! Do not loop wiring under any
terminals. Break wire run to
maintain IDC supervision.
UL PRODUCT
IDENTIFICATION
Momentary
Rocker
Switch
for General
Alarm
Notification
– To Next Device on
+ General Alarm IDC
Document 51479
– From FACP
+ General Alarm IDC
2
3
4
CAUTION! Do not detach the door of the pull station
during installation. The door of the pull station cannot be
reattached to the backplate after the backplate has already
been installed onto an electrical box.
CAUTION!
I n s t a l l t h e F i r e • L i t e B G - 1 2 L P S p u l l s t a -
t i o n i n a c c o r d a n c e w i t h t h e s e i n s t r u c t i o n s ,
LABEL
applicable NFPA standards, national and local Fire
and Electrical codes and the requirements of the AHJ
Toggle
(Authority Having Jurisdiction). Regular testing of the
Switch
PUSH FOR
for
devices should be conducted in accordance with the
Pre-Signal
GENERAL
ALARM
appropriate NFPA standards. Failure to follow these
directions may result in failure of the device to report
an alarm condition. Fire•Lite is not responsible for
devices that have been improperly installed, tested or
maintained.
ADA Compliance
For ADA compliance, if the clear floor space only allows
forward approach to an object, the maximum forward
reach height allowed is 48 inches (121.92 cm). If the
clear floor space allows parallel approach by a person
in a wheelchair, the maximum side reach allowed is 54
inches (137.16 cm).
BG-12LPS
Manual Pull Station
I56-2268-003

Advertisement

loading

Summary of Contents for Fire-Lite Alarms BG-12LPS

  • Page 1 STRIP GAUGE Description The BG-12LPS pull station is a non-coded, dual-action manual pull station with a key-lock reset feature. It provides Fire•Lite control panels with two (2) normally open (N/O) alarm initiating input signals. “Pre-signal” input is activated by pushing in, then pulling down the dual action handle.
  • Page 2 IDC del alarma general Desde FACP + – Desde FACP Pre-señal IDC – + IDC del alarma general BG-12LPS Estación Pulsadora Manual Patented, U.S. Patent No. Des. 428,351; 6,380,846; 6,632,108 Documento 51479 I56-2268-003 Descripcion STRIP GAUGE La estación pulsadora BG-12LSP es una estación no códificada y de doble acción manual con la característica de reajuste de una cerradura de llave.