6.
CAPACITY TABLE
6-1.
COOLING CAPACITY
MODEL
: ASTG09KMCA
AFR
11.7
°CDB
18
°CWB
12
°CDB
TC
SHC
IP
20
2.34
1.53
0.34
25
2.22
1.47
0.39
30
2.10
1.42
0.44
35
1.98
1.37
0.49
40
1.83
1.32
0.54
46
1.68
1.30
0.62
MODEL
: ASTG12KMCA
AFR
12.0
°CDB
18
°CWB
12
°CDB
TC
SHC
IP
20
3.28
2.15
0.59
25
3.12
2.08
0.67
30
2.95
2.00
0.75
35
2.77
1.92
0.83
40
2.56
1.85
0.92
46
2.26
1.76
0.97
3
AFR: Airflow Rate (m
/min)
TC: Total Capacity (kW)
SHC: Sensible Heat Capacity (kW)
IP: Input Power (kW)
Indoor temperature
21
23
15
16
TC
SHC
IP
TC
SHC
IP
2.60
1.54
0.34
2.69
1.67
0.34
2.47
1.48
0.39
2.56
1.61
0.39
2.34
1.43
0.45
2.42
1.56
0.45
2.20
1.38
0.50
2.28
1.50
0.50
2.03
1.33
0.55
2.10
1.45
0.56
1.87
1.31
0.63
1.93
1.42
0.64
Indoor temperature
21
23
15
16
TC
SHC
IP
TC
SHC
IP
3.65
2.16
0.60
3.78
2.35
0.61
3.48
2.10
0.68
3.59
2.28
0.68
3.28
2.01
0.76
3.39
2.19
0.77
3.08
1.94
0.84
3.19
2.10
0.85
2.85
1.86
0.93
2.95
2.03
0.94
2.51
1.77
0.99
2.60
1.92
0.99
- (01 - 09) -
25
27
18
19
TC
SHC
IP
TC
SHC
IP
2.87
1.67
0.35
2.96
1.81
0.35
2.73
1.62
0.40
2.81
1.75
0.40
2.58
1.56
0.45
2.66
1.69
0.46
2.43
1.50
0.51
2.50
1.62
0.51
2.24
1.45
0.56
2.31
1.57
0.56
2.06
1.43
0.64
2.13
1.54
0.65
25
27
18
19
TC
SHC
IP
TC
SHC
IP
4.03
2.36
0.61
4.15
2.55
0.62
3.83
2.29
0.69
3.95
2.47
0.70
3.62
2.20
0.78
3.73
2.37
0.78
3.40
2.11
0.86
3.50
2.28
0.86
3.14
2.03
0.95
3.24
2.20
0.95
2.77
1.93
1.00
2.86
2.09
1.01
29
32
21
23
TC
SHC
IP
TC
SHC
IP
3.14
1.80
0.35
3.32
1.92
0.36
2.98
1.74
0.40
3.15
1.85
0.41
2.82
1.68
0.46
2.98
1.79
0.46
2.65
1.61
0.52
2.80
1.72
0.52
2.45
1.56
0.57
2.59
1.66
0.57
2.25
1.54
0.65
2.38
1.64
0.66
29
32
21
23
TC
SHC
IP
TC
SHC
IP
4.40
2.54
0.62
4.65
2.70
0.63
4.19
2.46
0.70
4.42
2.62
0.71
3.95
2.36
0.79
4.18
2.52
0.79
3.71
2.27
0.87
3.92
2.42
0.88
3.43
2.19
0.96
3.62
2.33
0.97
3.03
2.08
1.02
3.20
2.21
1.03