Conductor Cross-Section On Electronic Unit; Cable Glands; Selection Of Suited Connection Cables - ABB LME620-AI User Manual

Electronic unit for field installation for the control of contrac control actuators series pme, lme, rhd and rsd
Hide thumbs Also See for LME620-AI:
Table of Contents

Advertisement

18
LME620-AI / PME120-AI / EAN823 / EBN853 / EBN861 ELECTRONIC UNIT | OI/PME/LME/EAN823/EBN853/EBN861-EN REV. E
hange from two to one column
... 6 Electrical connections
... Conductor cross-section on universal plug
PME / LME
Separate
Cable cross-section Motor / brake / heater:
electronic unit
Contact surface
integrated
Cable cross-section Power supply:
electronic unit
Contact surface
Change from one to two columns

Conductor cross-section on electronic unit

EAN823 – screw terminals
Motor/brake
Mains
Signals
EBN853 – Screw terminals
Motor/brake
Mains
Signals
EBN861 – Screw terminals
Motor / brake
Mains
Signals
Change from two to one column
Crimp pins
Signals:
Motor / brake / signals:
Heater:
Signals:
Power supply /signals:
2
rigid: 0.2 to 6 mm
(24 to 10 AWG)
2
flexible: 0.2 to 4 mm
(24 to 12 AWG)
2
rigid: 0.5 to 6 mm
(20 to 10 AWG)
flexible: 0.5 to 4 mm
2
(20 to 12 AWG)
rigid: 0.5 to 6 mm
2
(20 to 10 AWG)
2
flexible: 0.5 to 4 mm
(20 to 12 AWG)
rigid: 0.2 to 6 mm
2
(24 to 10 AWG)
flexible: 0.2 to 4 mm
2
(24 to 12 AWG)
2
rigid: 0.5 to 6 mm
(20 to 10 AWG)
2
flexible: 0.5 to 4 mm
(20 to 12 AWG)
2
rigid: 0.5 to 4 mm
(20 to 12 AWG)
2
flexible: 0.5 to 2.5 mm
(20 to 14 AWG)
2
rigid: 0.2 to 6 mm
(24 to 10 AWG)
2
flexible: 0.2 to 4 mm
(24 to 12 AWG)
2
rigid: 0.5 to 6 mm
(20 to 10 AWG)
2
flexible: 0.5 to 4 mm
(20 to 12 AWG)
rigid: 0.5 to 4 mm
2
(20 to 12 AWG)
flexible: 0.5 to 2.5 mm
2
(20 to 14 AWG)
2
max. 1.5 mm
(16 AWG)
2
max. 0.5 mm
(20 AWG)
Gold-plated
Silver-plated
2
max. 2.5 mm
(14 AWG)
2
max. 0.5 mm
(20 AWG)
Gold-plated

Cable glands

The actuators and electronic units are supplied without cable
glands. Suited cable glands must be installed on site.
Tap holes for cable glands
Signal cable
Motor cable
*
Adapter for PG or NPT thread must be ordered separately

Selection of suited connection cables

Please observe the following information when selecting cables:
Use shielded cables for the motor/brake cable, the
sensor cable, and the signal cable to the control
system/controller.
Connect the shielding of the motor/brake cable and the
sensor cable on both sides (to the actuator and to the
Contrac electronic unit).
Screw terminals (optional)
Motor / brake / heater /
0.2 to 2.5 mm
signals:
(24 to 14 AWG)
Motor / brake / signals:
Gold-plated
Heater:
Silver-plated
Power supply / signals:
0.2 to 2.5 mm
(24 to 14 AWG)
Power supply /signals:
Gold-plated
metric
optional adapters for*
M20 × 1.5 (2 ×)
PG 16 (2 ×)
M25 × 1.5 (1 ×)
PG 21 (1 ×)
2
2
NPT ½ in (2 ×)
NPT ¾ in (1 ×)