Compressors; Electrical - Lennox 13CHA SERIES Installation Instructions Manual

Packaged electric unit
Table of Contents

Advertisement

Compressors

Units are shipped with the compressor mountings
factory−adjusted and ready for operation.
CAUTION
Do not loosen compressor mounting bolts.

Electrical

All wiring should be done in accordance with the
current National Electric Code ANSI/NFPA No. 70 in the
United States. In Canada, wiring must be done in
accordance with the current CSA C22.2 Part 1. Local
codes may take precedence.
Use wiring with a temperature limitation of 75_C min.; run
the 208 or 230 volt, 60 hertz electric power supply through a
fused disconnect switch to control box of unit and connect
as shown in the wiring diagram located on the inside of the
control access panel. Refer to figure 5 for electrical access.
Electrical Access
Thermostat
Entry
Line Voltage
Entry
Figure 5
Unit must be electrically grounded in accordance with local
codes or in the absence of local codes with the National
Electric Code, ANSI/NFPA No. 70 (latest edition) or CSA
C22.2 Part 1 (latest edition).
Power supply to the unit must comply with all applicable
codes and NEC or CEC. A fused disconnect switch should
be field provided for the unit. The switch must be separate
from all other circuits. If any of the wire supplied with the
unit must be replaced, replacement wire must be of the
type shown on the wiring diagram.
Electrical wiring must be sized to carry minimum circuit
ampacity
marked
on
the
unit.
USE
COPPER
CONDUCTORS ONLY. Each unit must be wired with a
separate branch circuit and be properly fused.
Unit is equipped with a single−pole contactor. Line
voltage is present at all components when unit is not
in operation. Disconnect all remote electric power
supplies before opening access panel. Unit may
have multiple power supplies. Failure to disconnect
all power supplies could result in personal injury or
death.
When connecting electrical power and control wir-
ing to the unit, waterproof type connectors MUST be
used so that water or moisture cannot be drawn into
the unit during normal operation.
Unit must be grounded in accordance with national
and local codes. Failure to ground unit properly can
result in personal injury or death.
See figure 7 for typical field wiring connections and figure 8
for typical unit wiring diagram.
Optional Electric Heat
Optional electric heat is available and must be purchased
separately. Install the electric heat section as outlined in the
installation instructions packaged with the electric heat
section.
Thermostat
The room thermostat should be located on an inside wall
where it will not be subject to drafts, sun exposure or heat
from
electrical
manufacturer's instructions enclosed with thermostat for
general installation procedure. Color coded insulated wires
(# 18 AWG) should be used to connect thermostat to unit.
Blower Control Board
The circulating air blower is controlled by a blower control
board located in the unit control box. Blower operation is
NOT delayed after a call for either heating or cooling. A
blower
off" delay of 90 seconds begins when the
thermostat demand is satisfied. These delays are not
adjustable. See figure 6.
NOTE − With the proper thermostat and subbase, continu-
ous blower operation is possible by closing the R to G cir-
cuit. Cooling blower delay is also functional in this mode.
Page 7
WARNING
CAUTION
WARNING
fixtures
or
appliances.
Follow

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

13cha-2413cha-3613cha-3013cha-4813cha-6013cha-42

Table of Contents