Parameter
Unit's system voltage and frequency
Unit configuration
Engine type
Engine data input types
Battery Voltage
Communications
* See Section 2.2.6.
Figure 3-1 Configuration Parameters
Follow the instructions in Figure 3-2 to enter the
configuration mode while the engine is not running and
then step through the parameters. Use the up (
down (
) arrow buttons to select the appropriate setting
for the application.
Note: Be sure to save your settings before exiting the
configuration mode.
controller reverts to the last saved settings when
the master switch is moved to the OFF/RESET
position.
Voltage/frequency setting (Uu).
voltage and frequency to the value shown in Figure 3-1.
Note: This parameter sets the nominal system voltage
and frequency. To adjust the output (measured)
voltage, see Section 3.4.
Unit configuration (Uc).
generator set type: marine, standby, or mobile.
Engine configuration (Ec). The engine configuration
must match the generator set engine type. The Ec
setting for units built after November 2, 2009, is diffferent
than the setting for earlier units. See Figure 3-1 and
Section 2.2.6.
26
Section 3 Controller
Setting
Uu01
Uc01
Ec06
Ec11
Ed01
Bt12
Cn00
Cn01
Cn06 *
) and
See Figure 3-4.
The
Set the system
This parameter sets the
Definition
Single phase, 3 wire, 60 Hz, 120/240 VAC
Standby
RGEN30 (serial numbers below 2272938
RGEN30 (serial numbers above 2272938)
RGEN30
Battery voltage 12 VDC
No CAN communications, 48-hour power down
J1939 (use for Remote Digital Gauge), no power down
Enables J1939 communications and 1-hour controller power
down after engine stop for either:
a. Remote start/stop switch
b. Automatic transfer switch
c. Remote Digital Gauge with remote start/stop switch and
replacement harness
Advanced configuration mode (Adnc). The data
input types, battery voltage, and communications
setting can be changed in the advanced configuration
mode.
Press the up arrow button when Adnc is
displayed to enter the advanced configuration mode.
See Figure 3-3.
Engine data input types (Ed). This setting defines the
type of senders used on the generator set engine.
Battery voltage (Bt). This setting toggles between 12
and 24 VDC for the engine starting battery voltage. The
RGEN30 uses a 12-volt battery, Bt12.
Communications setting (Cn). This setting allows the
user to set the controller for communication with
optional meters. The RGEN30 is factory-set for no CAN
communications, Cn00. Change this setting to Cn01 or
Cn06 if an optional Remote Digital Gauge is used. See
Figure 3-1.
*
)
*
XP-6341 6/10