Greenheck FSD-311V Installation, Operation And Maintenance Instructions

Greenheck FSD-311V Installation, Operation And Maintenance Instructions

Combination fire smoke dampers
Hide thumbs Also See for FSD-311V:

Advertisement

®
Installation, Operation and Maintenance Instructions
Installation Supplements
Refer to the appropriate Greenheck installation supplements
for special requirements:
• Concrete Floor with Steel Deck
• Drive Slip Breakaway Connection
• Field Installed Sleeve
• Fire Resistant Ventilated Duct Assembly
• Firestop Material
• Greenheck Test Switch
• Grille Installation
• Metal Stud in Shaftwall
• No Flow Smoke Detector
• Open or Close Indicator
• Quick Connect Breakaway Connections
• Resettable Link
• Sealant Supplement
• Single Side Retaining Angle
• Single 3-Sided Retaining Angle
• Sleeve Extension
• Smoke Detector
• Tunnel Corridor
Safety Warning:
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, injury or
death. Read the installation, operating, and maintenance
instructions thoroughly before installing or servicing this
equipment.
Due to continuing research, Greenheck reserves the right to change specifications without notice.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the
job is complete.
Typical
Actuator
RRL Control
Device Standard
Document Number 461666
FSD-3XXV Series
Combination Fire Smoke Dampers
(with factory installed sleeve and actuator)
FSD-3XXV Series Dampers are intended for installation
in accordance with combination fire smoke damper
requirements established by:
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101, & 105
IBC International Building Codes
New York City (MEA listing #260-91-M)
California State Fire Marshal
Listing #3225-0981:103 and 3230-0981:104
"UL CLASSIFIED (see complete marking on
product)"
"UL CLASSIFIED to Canadian safety standards
(see complete marking on product)"
UL Standard 555 & 555S (Classification R13317)
Receiving and Handling
Upon receiving dampers, check for both obvious and
hidden damage. If damage is found, record all necessary
information on the bill of lading and file a claim with
the final carrier. Check to be sure that all parts of the
shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage
and protection from dirt, dust and the weather is highly
recommended. Do not store at temperatures in excess of
100°F (38°C).
Warranty
Greenheck warrants this equipment to be free from
defects in material and workmanship for a period of one
year from the purchase date. Any units or parts which
prove to be defective during the warranty period will be
repaired or replaced at our option. Greenheck shall not
be liable for damages resulting from misapplication or
misuse of its products. Greenheck will not be responsible
for any installation or removal costs. Greenheck will not
be responsible for any service work or backcharges
without prior written authorization.
1 1/2 Hour
Vertical Blade

Advertisement

Table of Contents
loading

Summary of Contents for Greenheck FSD-311V

  • Page 1 Due to continuing research, Greenheck reserves the right to change specifications without notice. This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the...
  • Page 2: Table Of Contents

    Electrical Code ANSI/NFPA-70 latest edition, any local Verify power before wiring actuator. Greenheck is not codes that may apply, and wiring diagrams developed responsible for any damage to, or failure of the unit in compliance with the job or project design and caused by incorrect field wiring.
  • Page 3: Installation

    Installation - Failure to follow these instructions will void all warranties. These instructions apply to 1 hour rated combination fire smoke dampers mounted (blades must be vertical) in: masonry, block, or stud walls. Specific requirements in these instructions are mandatory. Dampers must be installed in accordance with these instructions to meet the requirements of UL555 and UL555S.
  • Page 4: Securing The Damper/Sleeve Assembly To Wall And Floor Openings

    WALL OPENINGS Model Section Size Section Size Damper/sleeve assemblies must be installed in wall FSD-311V 50 x 32 100 x 32 openings using retaining angles on at least one side of the wall as described below: • Retaining angles for 11/2 hour rated dampers with a width and height 48 in.
  • Page 5: Connection And Operation Of Temperature Control Devices

    6. CONNECTION AND OPERATION OF TEMPERATURE RESPONSE DEVICES (RRL STANDARD, OCI OPTION, AND TOR OPTION) RRL - Dampers will be supplied with a thermostat-type temperature response device, as a standard. The device is a RRL (resettable link device), which only incorporates one thermostat and therefore the damper remains closed as soon as its sensor temperature is reached.
  • Page 6: Recommended Preparation Of Openings In Wood And Metal Stud Walls

    In metal stud construction, Damper exposed steel surfaces need Sleeve not be covered with gypsum wallboard. 7. RECOMMENDED PREPARATION OF OPENINGS IN WOOD AND METAL STUD WALLS Wooden Stud Construction • Frame wall openings as shown. (see Fig. 10 & 10A) Gypsum Wallboard •...
  • Page 7: Breakaway Connections

    8. DUCT-SLEEVE CONNECTIONS Fire Damper Sleeve Traditional Breakaway Style Transverse Joints 6 in. long 1 /16 in. max. thickness plastic cleats; Transverse joints illustrated at right have always been 12 in. c-c (min. 1 per side) approved as breakaway connections. SMACNA testing Flanged system angles has also approved the following variations as breakaway connections.
  • Page 8: Maintenance

    No power supplied to the actuator Add power supply Our Commitment As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties.