Combination fire smoke dampers

Advertisement

Quick Links

Installation, Operation and Maintenance Instructions
Installation Supplements
Refer to the appropriate Greenheck installation
supplements for special requirements:
• Metal Stud in Shaftwall
• Metal Stud in Drywall
• Wood Stud in Shaftwall
• Smoke Detector
• No Flow Smoke Detector
• Tunnel Corridor
• Single Side Retaining Angle
• Grille Installation
• Field Installed Sleeve
• Quick Connect Breakaway Connections
• Sealant Supplement
• Fire Resistant Ventilated Duct Assembly
• Drive Slip Breakaway Connection
• Concrete Floor with Steel Deck
• Sleeve Extension
• Open or Close Indicator
• Resettable Link
Safety Warning:
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, injury or
death. Read the installation, operating, and maintenance
instructions thoroughly before installing or servicing this
equipment.
Due to continuing research, Greenheck reserves the right to change specifications without notice.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when
the job is complete.
Typical
Actuator
RRL Control
Device Standard
Part Number 461666
Combination Fire Smoke Dampers
( with factory installed sleeve and actuator)
FSD-3XXV Series Dampers are intended for installation
in accordance with combination fire smoke damper
requirements established by:
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101, & 105
BOCA National Building Codes
ICBO Uniform Building Codes
IBC International Building Codes
SBCCI Standard Building Codes
New York City (MEA listing #260-91-M)
California State Fire Marshal
Listing #3225-0981:103 and 3230-0981:104
"UL CLASSIFIED (see complete marking on
product)"
"UL CLASSIFIED to Canadian safety standards
(see complete marking on product)"
UL Standard 555 & 555S (Classification R13317)
Receiving and Handling
Upon receiving dampers, check for both obvious
and hidden damage. If damage is found, record all
necessary information on the bill of lading and file
a claim with the final carrier. Check to be sure that
all parts of the shipment, including accessories, are
accounted for.
Dampers must be kept dry and clean. Indoor storage
and protection from dirt, dust and the weather is highly
recommended. Do not store at temperatures in excess
of 100°F (38°C).
Greenheck warrants this equipment to be free from
defects in material and workmanship for a period of one
year from the purchase date. Any units or parts which
prove to be defective during the warranty period will
be repaired or replaced at our option. Greenheck shall
not be liable for damages resulting from misapplication
or misuse of its products. Greenheck will not be
responsible for any installation or removal costs.
Greenheck will not be responsible for any service work
or backcharges without prior written authorization.
FSD-3XXV Series
1 1/2 Hour
Vertical Blade
Warranty

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FSD-3XXV Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Greenheck FSD-3XXV Series

  • Page 1 Due to continuing research, Greenheck reserves the right to change specifications without notice. This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when...
  • Page 2: Table Of Contents

    Verify power before wiring actuator. Greenheck is not in compliance with the job or project design and responsible for any damage to, or failure of the unit specifications.
  • Page 3: Installation

    Installation - Failure to follow these instructions will void all warranties. These instructions apply to 1 hour rated combination fire smoke dampers mounted (blades must be vertical) in: masonry, block, or stud walls. Specific requirements in these instructions are mandatory. Dampers must be installed in accordance with these instructions to meet the requirements of UL555 and UL555S.
  • Page 4: Duct To Sleeve Connections

    3. DUCT TO SLEEVE CONNECTIONS 4. SECURING THE DAMPER/SLEEVE ASSEMBLY TO WALL OPENINGS Dampers are supplied with sleeves and actuators from the factory and can be installed without the need for Damper/sleeve assemblies must be installed in wall additional field installed sleeves. openings using retaining angles on at least one side of the wall as described below: Gauge of factory furnished sleeve determines the type...
  • Page 5: Actuator Connections

    5. ACTUATOR CONNECTIONS RATINGS (Fig. 4, 5 & 6) Electrical and/or pneumatic connections to damper Integral Switch Type: Single Pole, double throw actuators should be made in accordance with wiring Electrical Capacity: 10 Amps, hp, 120 or 240 Vac and piping diagrams developed in compliance with Amp, 125 Vdc;...
  • Page 6: Breakaway Connections

    Round and Oval Duct Breakaway Connections Round or flat oval ducts connected to Type R or O damper collars shall be attached with #10 (19mm) sheet metal screws as follows: • Ducts to 22 in. (558mm) wide or diameter and smaller shall have three screws.
  • Page 7: Maintenance

    RRL or TOR sensor Heat Push reset button located on backside of tripped RRL or TOR Damper does not No power supplied to the actuator Add power supply operate Copyright © 2008 Greenheck Fan Corporation 461666 FSD-3XXV Rev. 8 January 2008...