Pay attention to the right temperature and gas group classification, see EN 60079-0. Only use original spare parts to maintain the explosion safety ! Landustrie version 06-12 | operation & maintenance manual DWP & DNP-EX series 3 / 16 Subject to modifications...
Please be also aware that some of the components can be very useful for reuse. The owner is responsible for careful disposal and processing of the materials. Do this in according to the local environmental regulations. Landustrie version 06-12 | operation & maintenance manual DWP & DNP-EX series 4 / 16 Subject to modifications...
Check that the motor is adequately cooled. At full load conditions, at least 2/3 of the motor housing should be submerged. Landustrie version 06-12 | operation & maintenance manual DWP & DNP-EX series 5 / 16 Subject to modifications...
Landustrie is able to deliver this certified equipment. Hoisting cable: If applied, please replace the stainless steel hoisting cable every two years, or accordingly to local regulations. Landustrie version 06-12 | operation & maintenance manual DWP & DNP-EX series 6 / 16 Subject to modifications...
We do strongly recommend to connect the pump to the mains by authorized personal only. Please ensure this is done accordingly and in compliance with local regulations Landustrie version 06-12 | operation & maintenance manual DWP & DNP-EX series 7 / 16 Subject to modifications...
2x 4 core cable Optional: Water detection in motor and oil housing. Only allowed with intrinsic safe amplifier. Motor in delta Motor in star Landustrie version 06-12 | operation & maintenance manual DWP & DNP-EX series 8 / 16 Subject to modifications...
1x 10 or 12 core cable + 1x 4 core cable Optional: Water detection in motor and oil housing. Only allowed with intrinsic safe amplifier. Landustrie version 06-12 | operation & maintenance manual DWP & DNP-EX series 9 / 16 Subject to modifications...
The motors are provided with fasteners of at least property class A2-70 Contact the manufacturer for information on the dimensions of the flameproof joints Landustrie version 06-12 | operation & maintenance manual DWP & DNP-EX series 10 / 16 Subject to modifications...
The accurate oil level is reached when the oil level is just below the filling plug. If the level is too low, please add accordingly. Make sure the pump cannot fall over during this procedure!. Landustrie version 06-12 | operation & maintenance manual DWP & DNP-EX series 11 / 16 Subject to modifications...
EC Declaration of conformity: Service Contract: Although the quality standards of the Landustrie pumps are very high, we do strongly recommend to close a service contract with your local supplier. For service- or technical information, please contact: Landustrie version 06-12 | operation & maintenance manual DWP & DNP-EX series...