TOUCH 1500
User Interface Terminal for RAYCHEM NGC
Systems Installation Instructions
TOUCH 1500
installed in a panel
KIT CONTENTS
Qty
Description
1
TOUCH 1500 display
10
Mounting clips
1
ADAM 4069-CID2 relay module
1
5-ft 9-pin RS-232 (null modem) cable
APPROVALS/CERTIFICATIONS
Nonhazardous Locations
E180881
I.T.F.
General
Area of use
Nonhazardous, Indoors (IP65, NEMA 4)
Supply voltage
10 – 30 Vdc
Amperage rating Steady state
Surge current
Operating
0°C to 50°C (32°F to 122°F) w/o space heater, –30°C to 50°C
temperature
(–22°F to 122°F) using space heater and screen cover
Storage
–20°C to 60°C (–4°F to 140°F)
temperature
Dimensions
449.9 mm W X 315.6 mm H X 141.7 mm D
(17.74 in. W X 12.44 in. H X 5.58 in. D)
Alarm Outputs
Relay output
One Form C relay rated at 3 A @ 250 Vac.
Relay is used as a common alarm.
LCD Display
Display
LCD is a 15-in XGA, color TFT transflective device with
integral CCFL backlight
Touch Screen
4-wire resistive touch screen interface for user entry
WARNING:
FIRE HAZARD: The Touch 1500 must not be used in
hazardous locations. Electrical components within the unit
could ignite flammable gases. Do not install the unit where it
may be exposed to flammable gases.
1.8 A
16 A
IMPORTANT:
The TOUCH 1500 is an electronic unit. During installation, take
the following precautions to avoid damage to its electronic
components.
• Handle with care to avoid mechanical damage.
• Keep electronics dry.
DESCRIPTION
The nVent RAYCHEM TOUCH 1500 is a panel mounted touch screen display used in
conjunction with nVent RAYCHEM NGC-40 and NGC-20 (Europe only) control and monitoring
devices. The TOUCH 1500 is rated IP 65 (NEMA 4) and is approved for nonhazardous indoor
locations. The TOUCH 1500 kit includes all hardware required for mounting in a suitable
electrical panel. These instructions describe how to mount the TOUCH 1500 in an electrical
panel and are intended only for personnel experienced in panel construction.
TOOLS REQUIRED
• Masking tape
• Metal file
• Jig saw (recommend using carbon steel blade with 24TPI)
ADDITIONAL MATERIALS (TO BE ORDERED SEPARATELY)
Qty Description
2
9 pin D-Sub to 10 pin terminal block PCB Phoenix Contacts
2
Serial Communication cable
11 Terminal Blocks
1
Type ZS1 Fuse Block
4
PE Terminal (Earth Ground)
6
End plates / Partition
1
End plate / Partition
6
End Plate Stops
2
Jumpers, 2 Position
2
Jumpers, 3 Position
1
Fuse, 1 amp, 250 V
1
Power Supply, 24 Vdc, 2.5 Amp
1
Push to test alarm light; Idec 24 Vdc
Network Connection
Local/
* RS-232/RS-485 ports may be used to communicate
Remote Port
with host computers DTS (nVent RAYCHEM Supervisor
Software) or DCS
Local RS-232
A non-isolated, 9 pin D sub male
Remote RS-485
2-wire isolated, 9 pin D sub male
Data rate
9600 to 57600 baud
Maximum cable
For RS-485 not to exceed 1200 m (4000 ft). Cable to be
length
shielded twisted pair.
Field Port
RS-485, 2-wire isolated. Used to communicate with
external devices, such as nVent RAYCHEM
NGC-40-BRIDGE. Maximum cable length not to exceed
1200 m (4000 ft). Cable to be shielded twisted pair.
Signals
2-wire isolated, 9 pin D sub male
Data rate
To 9600 baud
LAN
10/100 Base-T Ethernet port with Link and Activity Status
LEDs (X2)
USB Ports
USB 2.0 Host port Type A receptacle (X4)
• Avoid exposure to static electricity.
• Avoid contamination with metal filings, liquids, or other
foreign matter.
• Use agency-approved conduit bushings, adapters, and cable
glands to keep the enclosure protected from dust and fluids.
• #16 (3/16) drill bit
• Phillips screwdriver
Manufacturer
Manufacturer PN
2315162
L-COM
"CSMN9MF-xx
xx=Length in Ft."
Weidmuller
163205
Weidmuller
161649
Weidmuller
1632080000
Weidmuller
1632090000
Weidmuller
1896330000
Weidmuller
38356
Weidmuller
1608950000
Weidmuller
1608960000
Square D
MLD-1
Mean Well
DR-120-24
Idec
ALW29911-D-R-24