NOTES
1. All wiring supervised.
2. All circuits are power limited
per article 760 of NEC.
3. The ribbon cables for J1 and
J2 must be:
- within the same room
- within 20 ft.
- in rigid conduit.
4. Wiring for TB3 and TB4 is
18AWG min., 16 AWG max.
5. CAN network max. line
resistance 15S.
6. Refer to the NIC-C
Installation Instructions, P/N
315-033240 for CAN
network termination
instructions.
Figure 3
SIM-16RC Wiring Without An RNI
NOTES
1. Contacts are unsupervised.
2. 1A max @ 24VDC resistive.
3. All wiring must remain
inside the enclosure or
within 20 feet in rigid
conduit.
4. The ribbon cables for J1 and
J2 must be:
- within the same room
- within 20 ft.
- in rigid conduit.
5. Wiring for TB3 and TB4 is
18AWG min., 16 AWG max.
Figure 4
SIM-16RC Relay Connections
Siemens Industry, Inc.
Building Technologies Division
TO PSC-12/PSX-12, TB3
OR ANY REGULATED
POWER LIMITED POWER
SUPPLY LISTED FOR
FIRE PROTECTIVE
SIGNALING USE
TB3
+24 V
24 V RET
SHIELD
CAN +
CAN –
SHIELD
TO PSC-12, TB1
SEE NIC-C
INSTALLATION
INSTRUCTIONS,
15
P/N 315-033240
16
FOR WIRING DETAILS
TB3
6
1
15
16
3
SIM-16RC
1
J2
2
SIM-16RC
TB4
COM
6
Programmable
N.C.
5
Relay 2
N.O.
4
COM
3
Programmable
N.C.
2
Relay 1
N.O.
1
1
J2
2
P/N 315-050715-1