Siemens SIM-16RC Installation Instructions page 3

Supervised input module ribbon cable

Advertisement

NOTES
1. All wiring supervised.
2. All circuits are power limited
per article 760 of NEC.
3. The ribbon cables for J1 and
J2 must be:
- within the same room
- within 20 ft.
- in rigid conduit.
4. Wiring for TB3 and TB4 is
18AWG min., 16 AWG max.
5. CAN network max. line
resistance 15S.
6. Refer to the NIC-C
Installation Instructions, P/N
315-033240 for CAN
network termination
instructions.
Figure 3
SIM-16RC Wiring Without An RNI
NOTES
1. Contacts are unsupervised.
2. 1A max @ 24VDC resistive.
3. All wiring must remain
inside the enclosure or
within 20 feet in rigid
conduit.
4. The ribbon cables for J1 and
J2 must be:
- within the same room
- within 20 ft.
- in rigid conduit.
5. Wiring for TB3 and TB4 is
18AWG min., 16 AWG max.
Figure 4
SIM-16RC Relay Connections
Siemens Industry, Inc.
Building Technologies Division
TO PSC-12/PSX-12, TB3
OR ANY REGULATED
POWER LIMITED POWER
SUPPLY LISTED FOR
FIRE PROTECTIVE
SIGNALING USE
TB3
+24 V
24 V RET
SHIELD
CAN +
CAN –
SHIELD
TO PSC-12, TB1
SEE NIC-C
INSTALLATION
INSTRUCTIONS,
15
P/N 315-033240
16
FOR WIRING DETAILS
TB3
6
1
15
16
3
SIM-16RC
1
J2
2
SIM-16RC
TB4
COM
6
Programmable
N.C.
5
Relay 2
N.O.
4
COM
3
Programmable
N.C.
2
Relay 1
N.O.
1
1
J2
2
P/N 315-050715-1