Typical Purge Refrigeration Circuit; Operating Cycle - Trane PRGD series Installation, Operation And Maintenance Manual

Earthwise purge system with tracer adaptiview control for water-cooled centravac chillers with r-123 refrigerant
Table of Contents

Advertisement

S S e e q q u u e e n n c c e e o o f f O O p p e e r r a a t t i i o o n n s s
During the purge refrigeration circuit Off cycle, the time
remaining is displayed as the Time Until Next Purge
Run in the purge report of the Tracer® AdaptiView™
display.
If the controls determine it is necessary to run the
purge while the chiller compressor is Off, the purge will
be started and run until 60 consecutive minutes have
passed without any pump-out of non-condensables.
If the chiller compressor starts before the purge Off
cycle has elapsed, the purge starts and transfers to
Adaptive Mode Procedure—Chiller Compressor On.
Figure 4, p.
14, illustrates this process.
Figure 6. Purge refrigeration circuit showing temperatures at various locations in operating cycle
Temperatures at numbered locations:
1. After expansion device: -16°F (-26.7°C)
2. Compressor suction line temperature: greater than 60°F (15.5°C) when few non-condensables are present
3. Compressor discharge temperature: 150°F (65.5°C)
4. Condensing temperature: 85°F (29.4°C)
5. Liquid line temperature: 75°F (23.9°C)
The purge condensing-unit compressor suction
temperature (Location 2 in the preceding figure) varies
16
Typical Purge Refrigeration
Circuit Operating Cycle
At typical operating temperatures of 70°F (21.1°C)
ambient and 100°F (37.8°C) condensing, the purge
refrigeration cycle should have the temperatures
shown in the following figure for Locations 1–5.
N N o o t t e e : : To troubleshoot the system by taking these
temperatures, refer to
Temperature Measurements," p.
with the amount of non-condensables collected in the
purge tank. If the amount of non-condensables
"Taking Surface
30.
PRGD-SVX01F-EN