If the chiller compressor is turned Off, the purge
refrigeration circuit Off cycle is determined by the
purge control. The purge Off-cycle duration is
determined by the pump-out time, which is the greater
of the following two values:
Daily Pumpout—24 hours (the pump-out time over
the last 24 hours whether the chiller is On or Off)
Figure 5. Adaptive chiller OFF flow chart
The purge will be shut down for a corresponding
period of time, as shown in the following table:
PRGD-SVX01F-EN
S S e e q q u u e e n n c c e e o o f f O O p p e e r r a a t t i i o o n n s s
Average Daily Pumpout—7 days (the pump-out
time with the chiller On over the last 7 days)
N N o o t t e e : : These two values can be seen on the Tracer ®
AdaptiView ™ display.
Pumpout Time with chiller On or Off
(over the last 24 hours or daily average
over the last 7 days, whichever is
greater)
Pumpout Time ≤ 1 minute
1 minute < Pumpout Time ≤ 3 minutes
3 minutes < Pumpout Time ≤ 5 minutes
Pumpout Time > 5 minutes
Purge Off
cycle
duration
3 days
2 days
1 day
6 hours
15