Output driver

Advertisement

P/N 315-090830-8
Figure 1
Wiring Connection
TABLE 1
Connection to SR-35 Module*
Note: When using SR-35 with MOD-16, jumpers
P1-P8 on SR-35 must be in position B.
MOD-16
TB1-1
TB1-2
TB1-8
To PSR-1, TB3-1, or to
PS-35, TB1-5
To PSR-1, TB3-2, or to
PS-35, TB1-6
*For additional information see:
SR-35 Instructions (P/N 315-087691)
PS-35 Instructions (P/N 315-085062)
PSR-1 Instructions (P/N 315-090911)
NOTES:
SR-35 Screw Terminal
4
8
32
33
35
2
1.
18 AWG minimum for LED and 24V
lamp connections.
2.
14 AWG minimum for supply connec-
tions (TB1-9 and 10, TB2-9 and 10).
3.
All wiring must be in accordance with
NEC 760.
4.
All wiring must conform to local codes
and to the authority having jurisdiction
over the installation.
5.
All wiring to MOD-16 is unsupervised
and must not leave enclosure.
6.
For additional information see MOI-7
Module instructions, P/N 315-092799.
7.
A maximum of 8 MOD-16s can be
used with the MOI-7.
8.
When using SR-35, refer to Table 1.
9.
Both TB1-9 (or 10) and TB2-9 (or 10)
must be connected to the common of
the power supply.