OTHER CONTROLS
Setting Optional Modes

Smart Load Control (SLC) Function

(Fn14)
Smart Load Control Function could assist in reducing energy by low-
ering compressor lift during off-peak hours and shoulder seasons.
The function adjusts compressor lift by reading outdoor ambient
temperature, humidity (if FN16 is set to on), and current heating or
cooling demand in real time (rolling twenty [20] minute log).
Smart Load Control Options:
• Smooth Mode (oP1): Maximize energy savings; rate of temperature
change less important.
• Normal Mode (oP2): Balance the temperature change rate with the
energy consumed.
• Peak Mode (oP3): Quickly cool / heat the building; energy con-
sumption is less important.
All three (3) options only run for twenty (20) minutes of operation
after a compressor start. Following the twenty (20) minute morning
warm-up (or cool-down period), Smart Load Control will then use the
same algorithm irrelevant of which Smart Load Control option selected. If the outdoor unit is operating in cooling, Smart Load Control adjusts
the target low pressure; if the outdoor unit is operating in heating, Smart Load Control adjusts the target high pressure.
Smart Load Control can be used in almost every application except those where the outdoor unit is supporting a Dedicated Outdoor Air
System (contact an LG representative for information). Smart Load Control will not have an impact on operation if the system is running in
simultaneous cooling / heating (heat recovery systems only).
Use on both heat pump and heat recovery systems.
Table 33: Setting the Smart Load Control Function.
Settings
Smart Load Control Operation
oFF (Default)
oP1
oP2
oP3
72
Mode
Off
Not Selected; Disabled
On
Smooth
On
Normal
On
Peak
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Figure 22: Setting the Smart Load Control Function.
Turn No. 5 on the master outdoor unit PCB
DIP switch bank SW01 to ON.
Select from "oFF," "op1" through "op3" options (see table) by using the
Press the SW01D Reset Button one (1) time to reset PCB. The
Smart Load Control function is set.
Details (First Twenty [20] Minutes)
Maximize Energy Savings
Balance the Room Temperature Rate of Change with Energy
Quickly Change the Temperature.
-
Consumed