Checking Input Voltage In Case Of Power On - LG Multi V5 Service Manual

Hide thumbs Also See for Multi V5:
Table of Contents

Advertisement

CHECKING INPUT VOLTAGE IN CASE
OF POWER ON
Please refer to the Safety Precautions on pages 4-7 for more detail to prevent injury or death regarding the operation and service
WARNING
troubleshooting of the Multi V product.
Figure 79: Checking Input Voltage.
Inverter
PCB
R
S
220V
Terminal
R
S
T
210
Inverter
PCB
T
R
S
T
460V
Terminal
R
S
T
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Figure 80: Multi-Meter.
Red
Black
Table 90: Input Voltage Measurements.
Multi-Meter
Check
Mode
Black Red
Input Voltage
(3-Phase/3-Wire
AC
220V)
Input Voltage
(3-Phase /3-Wire
AC
460V)
Measured Value
Normal
Abnormal
R
S
R
T
220V±15%
S
T
Normal
R
S
R
T
460V±15%
S
T
Not