Checking Main Pcb Dc Voltage In Case Of Power On - LG Multi V5 Service Manual

Hide thumbs Also See for Multi V5:
Table of Contents

Advertisement

Please refer to the Safety Precautions on pages 4-7 for more detail to prevent injury or death regarding the operation and service
WARNING
troubleshooting of the Multi V product.
Checking Main PCB DC Voltage
Figure 81: Checking Main PCB DC Voltage (SMPS Voltage).
5V
GND2
Table 91: Main PCB DC Voltage (SMPS Voltage) Measurements.
Multi-Meter
Check
Mode
Black
5V
Main Ext.
GND2
12V
DC
5V
Comm.
GND3
12V
WARNING
Use caution when measuring the voltage; GND is separated. There is risk of electric shock, and physical injury or death.
CHECKING MAIN PCB DC VOLTAGE
12.0V
Vdc
5.0V
Vdc
12.0V
Vdc
5.0V
Vdc
Measured Value
Red
Normal
Abnormal
5V
4.5V~5.5V
12V 11.5V~12.5V
5V
4.5V~5.5V
12V 11.5V~12.5V