3.1.
UPSTREAM CIRCUIT PROTECTIVE DEVICES/ELECTRICAL
CONNECTIONS
To ensure satisfactory installation of this equipment be sure to observe "Cable Terminal
Information" regarding power cable connection tightness and "Requirements for Upstream
Circuit Protective Devices" located in this manual.
All mechanical and electrical connections must be checked for tightness prior to placing this
equipment in service to ensure proper operation and to validate applicable warranty
coverage.
3.2.

TRANSFER SWITCHES WITH INTEGRAL OVER CURRENT PROTECTION

For models of transfer switch with integral over current protection, the over current protection
must be set prior to operation. The equipment will be shipped from the factory with a long-
time current setting of 100% (of the equipment rating) and maximum short-
time/instantaneous current and time delay settings.
Refer to Section 5.2.2 of this manual for additional information on operation of the Transfer
switch following an over current trip condition.
Refer to information supplied with the transfer switch documentation package for adjustment
procedures on the power switching units over current protection trip unit. Contact the factory
if any additional information is required.
PM062 REV 10 15/04/07
TS 870 TRANSFER SWITCH
WARNING!
Do Not Energize this equipment until
device settings have been verified to
ensure proper system protection &
coordination.
Failure to do so may
result in equipment failure.
3