Equipment Storage; Environmental Conditions; Notes To Installer - Marathon TS 870 Installation, Operating & Service Manual

Automatic transfer switches with tsc 900 controller
Table of Contents

Advertisement

2.

EQUIPMENT STORAGE

The following procedures are required for correct storage of the transfer switch prior to installation.
2.1.

ENVIRONMENTAL CONDITIONS

Failure to store and operate equipment under the specified environmental conditions may
cause equipment damage and void warranty.
2.1.1.
EQUIPMENT STORAGE
The transfer switch shall be stored in an environment with a temperature range not
exceeding -4° to +158° Fahrenheit (-20° to +70° Celsius) and a humidity range not
exceeding 5%-95% non-condensing. Before storing, unpack sufficiently to check for
concealed damage. If concealed damage is found, notify the ATS supplier and the
Carrier immediately. Repack with the original, or equivalent packing materials. Protect
from physical damage. Do not stack. Store indoors in a clean, dry, well ventilated
area free of corrosive agents including fumes, salt and concrete/cement dust. Apply
heat as necessary to prevent condensation.
2.1.2.
EQUIPMENT OPERATING
The transfer switch shall be operated in an environment with a temperature range not
exceeding +5° to +122° Fahrenheit (-15° to +50° Celsius) and a humidity range not
exceeding 5%-95% non-condensing.
3.

NOTES TO INSTALLER

Arc Flash and Shock Hazard. Will cause severe injury or death.
Do not open equipment until ALL power sources are disconnected
This equipment must be installed and serviced only by qualified electrical
personnel utilizing safe work practices and appropriate Personal Protective
Equipment (PPE). Failure to do so may cause personal injury or death
PM062 REV 10 15/04/07
TS 870 TRANSFER SWITCH
CAUTION!!!
DANGER!!!!
2